Inspection Report
p425 E.3rd Street
41400 Fraternal Order of Eagles Arie#764-202 E 1st ST,BLDG 202 E 1st St,Waterloo IA
50703
INSPECTION DETAILS
Inspection Date Inspection Type Q Inspection Number
/ �
06102/2026 Annual Inspection(1Yr) 1 �' 17363
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA N/A N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
037 (D( 3 ® 36
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
Reinspection Date
BRAD BALDWIN
06/24/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-06102/2026 @ 06:52
•S80 annual inspection fee
BRAD BALDWIN-0610212026 @ 06:52
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-0610212026 @ 06:53
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-06102/2026 @ 06:53
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-06/02/2026 @ 06:55
Kitchen hood exhaust cleaning due July 7115/26.Contractor completing cleaning is required to upload report of cleaning including any deficiencies
corrected to Compliance Engine.
SIGNATURES
Contact signature Inspector signature
No signatureedpost
Report completed post inspection
Jeff Murphy-Trustee 2026 Date: BRAD BALDWIN 0610212026
CHECKLISTS
GENERATED ON 6/2/26, 6:59 AM
1 OF 5
Additional Codes
Status Code Description
Fail 1010.2.4-Locks and latches.
Locks and latches shall be permitted to prevent operation of Location:North exit from bar
doors where any of the following exist:S.Places of detention Comments:Marked exit door shall not require more than a single(1)
or restraint.2.In Group 1-1,Condition 2 and Group 1-2 motion to unlock and unlatch door,currently requires two motions
occupancies where the clinical needs of persons receiving with handle and deadbolt.Hardware shall be corrected to comply
care require containment or where persons receiving care with egress requirements.
pose a security threat,provided that all clinical staff can
readily unlock doors at all times,and all such locks are keyed
to keys carried by all clinical staff at all times or all clinical
staff have the codes or other means necessary to operate the
locks at all times.2.3.In buildings in occupancy Group A
having an occupant load of 300 or less,Groups B,F,M and S,
and in places of religious worship,the main door or doors are
permitted to be equipped with key-operated locking devices
from the egress side provided:2.1.3.1.The locking device is
readily distinguishable as locked.2.2.3.2.A readily visible
durable sign is posted on the egress side on or adjacent to
the door stating:"THIS DOOR TO REMAIN UNLOCKED WHEN
THIS SPACE IS OCCUPIED."The sign shall be in letters 1 inch
(25 mm)high on a contrasting background.2.3.3.3.The use
of the key-operated locking device is revocable by the fire
code official for due cause.3.4.Where egress doors are used
in pairs,approved automatic flush bolts shall be permitted to
be used,provided that the door leaf having the automatic
flush bolts does not have a doorknob or surface-mounted
hardware.4.5.Doors from individual dwelling or sleeping
units of Group R occupancies having an occupant load of 10
or less are permitted to be equipped with a night latch,dead
bolt or security chain,provided such devices are openable
from the inside without the use of a key or tool.5.6.Fire
doors atter the minimum elevated temperature has disabled
the unlatching mechanism in accordance with listed fire door
test procedures.6.7.Doors serving roofs not intended to be
occupied shall be permitted to be locked,preventing entry to
the building from the roof.B.Other than egress courts,where
occupants must egress from an exterior space through the
building for means of egress,exit access doors shall be
permitted to be equipped with an approved locking device
where installed and operated in accordance with all of the
following:8.1.The maximum occupant load shall be posted
where required by Section 1004.9.Such sign shall be
permanently affixed inside the building and shall be posted in
a conspicuous space near all the exit access doorways.8.2.A
weatherproof telephone or two-way communication system
installed in accordance with Sections 1009.8.1 and 1009.8.2
shall be located adjacent to not less than one required exit
access door on the exterior side.8.3.The egress door locking
device is readily distinguishable as locked and shall be a key-
operated locking device.8.4.A clear window or glazed door
opening,not less than 5 square feet(0.46 m2)in area,shall
be provided at each exit access door to determine if there are
occupants using the outdoor area.8.5.A readily visible
durable sign shall be posted on the interior side on or
adjacent to each locked required exit access door serving the
exterior area stating:"THIS DOOR TO REMAIN UNLOCKED
WHEN THE OUTDOOR AREA IS OCCUPIED."The letters on
the sign shall be not less than 1 inch(25.4 mm)high on a
contrasting background.8.6.The occupant load of the
occupied exterior area shall not exceed 300 occupants in
accordance with Section 1004.9.Locking devices are
permitted on doors to balconies,decks or other exterior
spaces serving individual dwelling or sleeping units.
10.Locking devices are permitted on doors to balconies,
decks or other exterior spaces of 250 square feet(23.23
m2)or less,serving a private office space.
OF 5
GENERATED ON 6/2/25,8:58 MI
Fail 1010.2.4- Locks and latches.
Locks and latches shall be permitted to prevent operation of Location: North exit from bar (patio doors)
doors where any of the following exist: 1.Places of detention Comments: Install approved permanent signage on (2) patio doors to
or restraint. 2.In Group I-1, Condition 2 and Group 1-2 read "Door must remain unlocked during business hours"
occupancies where the clinical needs of persons receiving
care require containment or where persons receiving care
pose a security threat, provided that all clinical staff can
readily unlock doors at all times, and all such locks are keyed
to keys carried by all clinical staff at all times or all clinical
staff have the codes or other means necessary to operate the
locks at all times. 2. 3. In buildings in occupancy Group A
having an occupant load of 300 or less, Groups B, F, M and S,
and in places of religious worship, the main door or doors are
permitted to be equipped with key-operated locking devices
from the egress side provided: 2.1. 3.1. The locking device is
readily distinguishable as locked. 2.2. 3.2. A readily visible
durable sign is posted on the egress side on or adjacent to
the door stating: "THIS DOOR TO REMAIN UNLOCKED WHEN
THIS SPACE IS OCCUPIED." The sign shall be in letters 1 inch
(25 mm) high on a contrasting background. 2.3. 3.3. The use
of the key-operated locking device is revocable by the fire
code official for due cause. 3. 4. Where egress doors are used
in pairs, approved automatic flush bolts shall be permitted to
be used, provided that the door leaf having the automatic
flush bolts does not have a doorknob or surface-mounted
hardware. 4. 5. Doors from individual dwelling or sleeping
units of Group R occupancies having an occupant load of 10
or less are permitted to be equipped with a night latch, dead
bolt or security chain, provided such devices are openable
from the inside without the use of a key or tool. 5. 6. Fire
doors after the minimum elevated temperature has disabled
the unlatching mechanism in accordance with listed fire door
test procedures. 6. 7. Doors serving roofs not intended to be
occupied shall be permitted to be locked, preventing entry to
the building from the roof. 8.Other than egress courts, where
occupants must egress from an exterior space through the
building for means of egress, exit access doors shall be
permitted to be equipped with an approved locking device
where installed and operated in accordance with all of the
following: 8.1.The maximum occupant load shall be posted
where required by Section 1004.9. Such sign shall be
permanently affixed inside the building and shall be posted in
a conspicuous space near all the exit access doorways. 8.2.A
weatherproof telephone or two-way communication system
installed in accordance with Sections 1009.8.1 and 1009.8.2
shall be located adjacent to not less than one required exit
access door on the exterior side. 8.3.The egress door locking
device is readily distinguishable as locked and shall be a key-
operated locking device. 8.4.A clear window or glazed door
opening, not less than 5 square feet (0.46 m2 ) in area, shall
be provided at each exit access door to determine if there are
occupants using the outdoor area. 8.5.A readily visible
durable sign shall be posted on the interior side on or
adjacent to each locked required exit access door serving the
exterior area stating: "THIS DOOR TO REMAIN UNLOCKED
WHEN THE OUTDOOR AREA IS OCCUPIED." The letters on
the sign shall be not less than 1 inch (25.4 mm) high on a
contrasting background. 8.6.The occupant load of the
occupied exterior area shall not exceed 300 occupants in
accordance with Section 1004. 9.Locking devices are
permitted on doors to balconies, decks or other exterior
spaces serving individual dwelling or sleeping units.
10.Locking devices are permitted on doors to balconies,
decks or other exterior spaces of 250 square feet (23.23
m2) or less, serving a private office space.
GENERATED ON 6/2/26, 6:59 AM
3 OF 5
Electrical Safety
Spa',s Code Description
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Coat closet near bar
for permanent wiring and shall be listed and labeled in Comments:Remove cord extending above drop ceiling(possibly to
accordance with UL 817.Extension cords and flexible TV box above ceiling)
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 6/2/26, 6:59 AM 4 OF 5
E® Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
WA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 6/2/26, 6:59 AM 5 OF 5
OF W p TF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
A 4),(• 06/10/2026 07/15/2026 2026-00000537 $80.00
u f o
rear.+,�
'Cs 7vtl75
Customer#: 20693 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
FRATERNAL ORDER OF EAGLES 715 Mulberry St
202 E 1ST ST WATERLOO, IA 50703
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-202 E. 1ST ST-06/02/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
20693 06/10/2026 07/15/2026 2026-00000537 $80.00
Less Prepayment $0.00
Total Due — $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.