HomeMy WebLinkAboutELK'S CLUB Waterloo Fire Rescue
Inspection Report
t� 425 E.3rd Street
Elk's Club-407 E Park AVE,BLDG 407 E Park Ave,Waterloo IA 50703
INSPECTION DETAILS
Inspection Date Inspection Type ��� � � Inspection Number
06/02/2026 Annual Inspection(1Yr) r 17426
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
N/A
SUMMARY OF INSPECTION
e 55 0 15 ( 10
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
07/01/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-06/08/2026 @ 07:03
$100 annual inspection fee
BRAD BALDWIN-06108/2026 @ 07:03
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-06/08/2026 @ 07:04
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-06108/2026 @ 07:04
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Sherri Simon 2026 Date: BRAD BALDWIN 06/08/2026
CHECKLISTS
GENERATED ON 6/8/26, 8:17 AM 1 OF 6
Emergency Equipment
`:a"s Code Description
Fail 1203.2,15-Means of egress illumination.
OEmergency power shall be provided for means of egress Location:Billiards room
illumination in accordance with Sections 1008.3 and 1104,5.1. Comments:Repair or replace emergency egress light that failed test.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Hallway near Red Stag Room
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Egress(can light)near elevator 2 shall be repaired or
replaced.Light failed test during inspection
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Ballroom
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Provide documentation of all egress lighting tested and
repaired if non-functional.Document shall be signed and dated and
mailed to inspector
Fire Service Features
Code Description
Fail 505.1-Address identification.
New and existing buildings shall be provided with approved Location:Park Ave side of building
address identification.The address identification shall be Comments:Provide address identification numbers on building
legible and placed in a position that is visible from the street easily visible from the road in approved location
or road fronting the property.Address identification
characters shall contrast with their background.Address
numbers shall be Arabic numbers or alphabetical letters.
Numbers shall not be spelled out.Each character shall be not
less than 4 inches(102 mm)high with a minimum stroke
width of 112 inch(12.7 mm).Where required by the fire code
official,address identification shall be provided in additional
approved locations to facilitate emergency response.Where
access is by means of a private road and the building cannot
be viewed from the public way,a monument,pole or other
sign or means shall be used to identify the structure.Address
identification shall be maintained.
Additional Codes
_tss Code Description
Fail 603.1-General.
Electrical equipment,wiring and systems required by this Location:"Down"kitchen
code or the International Building Code shall be installed, Comments:Remove microwave plugged to power strip.Appliances
used and maintained in accordance with NFPA 70 and including motors or heating elements shall plug directly to
Sections 603.2 through 603.10. permanent wall outlet.
2 OF 6
GENERATED ON 6/8/26, 8:17 AM
Electrical Safety
Status Code Description
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
OOpen junction boxes and open-wiring splices shall be Location:"Up"kitchen
prohibited.Approved covers shall be provided for all switch Comments:Replace broken outlet cover behind condiment fridge
and electrical outlet boxes.
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Boiler room-above stairs
prohibited.Approved covers shall be provided for all switch Comments:Provide knockout plug in opening in box to avoid shock
and electrical outlet boxes. hazard
s M1y
i
Fail 603.4-Working space and clearancesclearance.
Ox A working space of not Working space around electrical Location:Basement custodial closet
equipment shall be provided in accordance with Section Comments:Remove storage blocking access to electric panels,
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or maintain clear access and 36"clearance from panels at all time
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
Fail 603.5.3-Installation.
Ox Relocatable power tap cords shall not extend through walls, Location:"Up"kitchen
ceilings,floors,under doors or floor coverings,or be subject Comments:Properly mount power strip below security camera TV to
to environmental or physical damage.
avoid hanging by wires.
GENERATED ON 6/8/26, 8:17 AM 3 OF 6
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Park Ave lounge
for permanent wiring and shall be listed and labeled in Comments:Remove brown extension to security camera,will
accordance with UL 817.Extension cords and flexible approve to replace with power strip with manual reset properly
cordsshall not be affixed to structures,extended through mounted for low wattage electronics only.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Brass lounge
for permanent wiring and shall be listed and labeled in Comments:Remove extension cord to"fake fireplace"
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
S:a Code Description
Fail 606.3.3-Cleaning.
Hoods,grease-removal devices,fans,ducts and other Location:Kitchen exhaust hood
appurtenances shall be cleaned at intervals as required by Comments:Provide annual cleaning and contractor report including
Sections 606.3.3.1 through 606.3.3.3. any deficiencies to Compliance Engine.Currently due for cleaning on
6112126.Cleaning is scheduled for 6/11126
Fire Resistant Construction Maintenance
Status Code Description
Fail 704.1-Maintaining protection.
0 Where required when the building was originally constructed, Location:Brass lounge
materials and systems used to protect joints and voids in the Comments:Replace missing ceiling tile.
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
GENERATED ON 6/8/26, 8:17 AM 4 OF 6
•
Portable Fire Extingusihers
Status Code Description
Fail 906.2-General requirements.
Ox Portable fire extinguishers shall be selected,installed and Location:Billiards room
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to extinguisher,currently past
Exceptions:1.The distance of travel to reach an extinguisher due for service.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
Fail 906.2-General requirements.
OPortable fire extinguishers shall be selected,installed and Location:Boiler room
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to extinguisher,currently past
Exceptions:1.The distance of travel to reach an extinguisher due for service.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 6/8/26, 8:17 AM 5 OF 6
Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $100.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 6/8/26, 8:17 AM 6 OF 6
O F W4
TF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
A �0 06/10/2026 07/15/2026 2026-00000535 $100.00
• ' 1 111 11 1 •
T-^ ! O
�S 7V11N
Customer#: 9492 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
ELK'S CLUB 715 Mulberry St
407 E PARK AV WATERLOO, IA 50703
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-407 E. PARK AVE-06/02/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
9492 06/10/2026 07/15/2026 2026-00000535 $100.00
Less Prepayment $0.00
Total Due -* $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.