HomeMy WebLinkAbout127 JEFFERSON STREET - HAB PETROLEUM Waterloo Fire Rescue Inspection Report 425 E.3rd Street HAB Petroleum-127 Jefferson ST,BLDG 127 Jefferson St,Waterloo IA 50702 INSPECTION DETAILS 2 )1 ' Inspection Date Inspection Type of•L/`/ 11i Inspection Number 05/05/2026 Annual Inspection(1Yr) 17180 Lead Inspector Shift Station Unit BRAD BALDWIN N/A NIA N/A Other Inspectors N/A SUMMARY OF INSPECTION 29 G 13 ® 36 Passed codes Failed codes NIA codes NEXT STEPS Please direct questions about your Inspection to: Reinspection Date BRAD BALDWIN 05/28/2026 brad.baldwin@waterloo-ia.org,3192914319 GENERAL NOTES BRAD BALDWIN-05106/2026 @ 07:23 •$80 annual inspection fee BRAD BALDWIN-05/06/2026 @ 07:23 •Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224 BRAD BALDWIN-05106/2026 @ 07:23 •Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards corrected BRAD BALDWIN-0510612026 @ 07:24 •If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re- inspection fees start at$100,then$150,and S200 for all subsequent re-inspections. SIGNATURES Contact signature Inspector signature No signature Report completed post inspection Mohammad Bhatti Date: BRAD BALDWIN 05106/2026 CHECKLISTS GENERATED ON 5/6/26, 11:41 AM OF Means of Egress Siam. Code Description Fail 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be Location:Exit facing 1st St. continuously maintained free from obstructions or Comments:Remove all obstructions to clear path of egress to exit. impediments to full instant use in the case of fire or other Maintain clear path to exit at all times. emergency where the building area served by the means of egress is occupied.An exit or exit passageway shall not be used for any purpose that interferes with a means of egress. i _ :', t. 1 ,_ -' ;- fv �, ._111110k r S. a -VW-- _ I Fe. { ... t 6 !' i3 ., 1 • .k, "'` ` 'Ca t I 111 2 OF 8 GENERATED ON 5/6/26, 11:41 AM Additional Codes Status Code Description Fail 102.4-Application of building code. The design and construction of new structures shall comply Location:2025 Remodel Permit with the International Building Code,and any alterations, Comments:Final inspection shall be obtained for remodel permit. additions,changes in use or changes in structures required by this code,which are within the scope of the International Framing inspection has passed but no final inspection on record as Building Code,shall be made in accordance therewith. of 516126. Fail 5303.5.3-Securing compressed gas containers,cylinders and tanks. Location:Near old back exit Compressed gas containers,cylinders and tanks shall be Comments:Secure compressed gas cylinders with chain to avoid tip secured to prevent falling caused by contact,vibration or over. seismic activity.Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1.Securing containers,cylinders and tanks to a fixed object with one or more restraints.2.Securing containers,cylinders and tanks on a cart or other mobile device designed for the movement of compressed gas containers,cylinders or tanks. 3.Nesting of compressed gas containers,cylinders and tanks at container filling or servicing facilities or in sellers' warehouses not open to the public.Nesting shall be allowed provided that the nested containers,cylinders or tanks,if dislodged,do not obstruct the required means of egress. 4.Securing of compressed gas containers,cylinders and tanks to or within a rack,framework,cabinet or similar assembly designed for such use.Exception:Compressed gas containers,cylinders and tanks in the process of examination,filling,transport or servicing. Fail 603.1-General. ,x 1 Electrical equipment,wiring and systems required by this Location:Near front exit code or the International Building Code shall be installed, Comments:Remove microwave plugged to power strip.All used and maintained in accordance with NFPA 70 and Sections 603.2 through 603.10. appliances with motors or heat producing elements shall plug directly to permanent wall outlet. GENERATED ON 5/6/26, 11:41 AM 3 OF 8 Emergency Equipment star:- Code Description Fail 1203.2.15-Means of egress illumination. Emergency power shall be provided for means of egress Location:Men's bathroom illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Emergency egress light removed shall be replaced and in proper working condition. 111 Fail 1203.2.15-Means of egress illumination. Emergency power shall be provided for means of egress Location:Women's bathroom illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress light that failed to illuminate during test Fire Service Features Desu iption Stir„ Code Fail 505.1-Address identification. New and existing buildings shall be provided with approved Location:Front of building facing Jefferson St. address identification.The address identification shall be Comments:Address numbers are currently not in contrast with the legible and placed in a position that is visible from the street building and easily visible from the road.Numbers shall be relocated or road fronting the property.Address identification to a contrasting location or colors altered to be visible from the road. characters shall contrast with their background.Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out.Each character shall be not less than 4 inches(102 mm)high with a minimum stroke width of 112 inch(12.7 mm).Where required by the fire code official,address identification shall be provided in additional approved locations to facilitate emergency response.Where access is by means of a private road and the building cannot be viewed from the public way,a monument,pole or other sign or means shall be used to identify the structure.Address identification shall be maintained. 4 OF 8 GENERATED ON 5/6/26, 11:41 AM Electrical Safety Status Code Description Fail 603.2.2-Unapproved conditionsOpen electrical terminations. Open junction boxes and open-wiring splices shall be Location:Ceiling-above hallway towards bathrooms prohibited.Approved covers shall be provided for all switch Comments:Provide missing cover to box. and electrical outlet boxes. • • Fail 603.2.2-Unapproved conditionsOpen electrical terminations. Open junction boxes and open-wiring splices shall be Comments:Provide missing switch cover prohibited.Approved covers shall be provided for all switch and electrical outlet boxes. 11.11 w_ 5 OF 6 GENERATED ON 5/6/26, 11:41 AM Fail 603.5-Relocatable power taps and current taps.Multiplug adapters. Location:Ceiling-hallway toward bathrooms Multiplug adapters,such as cube adapters,unfused plug Comments:Remove green multi plug adapter,may replace with strips or any other device not complying with NFPA 70 shall properly mounted power strip with manual reset for low wattage be prohibited.The construction and use of current taps and electrical equipment only relocatable taps shall be in accordance with NFPA 70 and this code. Fail 603.5.3-Installation. Relocatable power tap cords shall not extend through walls, Location:Near front exit&"Live Bait"fridge ceilings,floors,under doors or floor coverings,or be subject Comments:Power strip shall be properly mounted to avoid hanging to environmental or physical damage. by wires Fire Resistant Construction Maintenance Status Code Description Fail 704.1-Maintaining protection. Where required when the building was originally constructed, Location:Entire space materials and systems used to protect joints and voids in the Comments:Install ceiling tiles in all missing locations throughout following locations shall be maintained.The materials and building. systems shall be securely attached to or bonded to the adjacent construction,without openings visible through the construction.1.Joints in or between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or rooflceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.Unprotected joints and voids do not need to be protected where such joints and voids were not required to be protected when the building was originally constructed.Where the system design number is known,the system shall be inspected to the listing criteria and manufacturer's installation instructions. GENERATED ON 5/6/26, 11:41 AM 6 OF 8 Portable Fire Extingusihers Status Code Description Fail 906.2-General requirements. Ox Portable fire extinguishers shall be selected,installed and Comments:Provide annual service to all fire extinguishers.Currently maintained in accordance with this section and NFPA 10. due May 2026 Exceptions:1.The distance of travel to reach an extinguisher shall not apply to the spectator seating portions of Group A-5 occupancies.2.Thirty-day inspections shall not be required and maintenance shall be allowed to be once every 3 years for dry-chemical or halogenated agent portable fire extinguishers that are supervised by a listed and approved electronic monitoring device,provided that all of the following conditions are met:2.1.Electronic monitoring shall confirm that extinguishers are properly positioned,properly charged and unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a building or cabinet in a noncorrosive environment. 2.4.Electronic monitoring devices and supervisory circuits shall be tested every 3 years when extinguisher maintenance is performed.2.5.A written log of required hydrostatic test dates for extinguishers shall be maintained by the owner to verify that hydrostatic tests are conducted at the frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be permitted to be located at staff locations. GENERATED ON 5/6/26, 11:41 AN 7 OF 8 Statement of Fees FEE Invoice Date Inspection Fee Date Paid Amount Paid NIA $80.00 Invoice Number Check Number Transaction Number NIA NIA NIA GENERATED ON 5/6/26, 11:41 AM 8 OF 8 F W q . INVOICE DATE DUE DATE INVOICE# TOTAL DUE o F,p ,� e 0 06/01/2026 07/06/2026 2026-00000496 $80.00 )vs,"o 4S ivtl‘ Customer#: 23091 Please Make Check Payable and Remit To: City of Waterloo ATTN: City Clerk/Accounts Receivable HAB PETROLEUM 715 Mulberry St 127 JEFFERSON WATERLOO, IA 50703 WATERLOO, IA 50701 Amount Enclosed: DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT KEEP THIS PORTION FOR YOUR RECORDS COMMERCIAL FIRE INSPECTION-127 JEFFERSON-05/05/2026 FOR BILLING INQUIRY: (319)291-4323 Description Total Price INSPECTION 2,000 $70.00 OCCUPANCY FEE $10.00 CUSTOMER# BILLING DATE DUE DATE a INVOICE# CHARGES 23091 06/01/2026 07/06/2026 2026-00000496 $80.00 Less Prepayment $0.00 Total Due—* $80.00 City of Waterloo Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of Administrative Services Offset Program if not paid in full within ninety days.