Inspection Report
425 E.3rd Street
Isle of Capri-777 Isle of Capri BLVD,BLDG 777 Isle of Capri Blvd,Waterloo IA
50702 la(039 FA
INSPECTION DETAILS
Inspection Date Inspection Type I 304 9 Inspection Number
05112/2026 Annual Inspection(1Yr) 4 (oIvv. 16750
Lead Inspector Shia Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
JEREMIAH VANDYKE
SUMMARY OF INSPECTION
061 09 ® 7
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
06/17/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-05/15/2026 @ 14:10
$610 annual inspection fee.
BRAD BALDWIN-0512612026 @ 12:37
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-0512612026 @ 12:37
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-05/26/2026 @ 12:37
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completededpost stinspection
Danny Lane Date: BRAD BALDWIN 05/26/2026
CHECKLISTS
GENERATED ON 5/26/26, 12:40 PM 1 OF 4
Additional Codes
Status Code Description
Fail 102A-Application of building code.
The design and construction of new structures shall comply Location:HVAC permit
with the International Building Code,and any alterations, Comments:Contractor(Young's Plumbing)shall obtain inspection of
additions,changes in use or changes in structures required work completed.Permit obtained April2024 for"Ceiling Cassette
by this code,which are within the scope of the International hung in UPS room",no inspections on file
Building Code,shall be made in accordance therewith.
Fail 507.5.3-Private fire service mains and water tanks.
Ox Private fire service mains and water tanks shall be Location:Private fire hydrant
periodically inspected,tested and maintained in accordance Comments:Licensed contractor shall make repairs to noted
with NFPA 25 at the following intervals:1.Private fire hydrants deficiency in report(see attached).Report of repairs shall be
of all types:Inspection annually and after each operation; uploaded to Compliance Engine.
flow test and maintenance annually.2.Fire service main
piping:Inspection of exposed,annually;flow test every 5
years.3.Fire service main piping strainers:Inspection and
maintenance after each use.Records of inspections,testing
and maintenance shall be maintained.
um ER
Fail 610.1.2-Maintenance.
OThe lint trap,mechanical and heating components,and the Location:Clothes dryers
exhaust duct system of a clothes dryer shall be maintained in Comments:Provide documentation of cleaning all dryer vents in the
accordance with the manufacturer&n039;s operating building from the appliances to the exterior.Document may be
instructions to prevent the accumulation of lint or debris that emailed to inspector
prevents the exhaust of air and products of combustion.
Fail 901.6-Inspection,testing and maintenance.
Fire detection and alarm systems,emergency alarm systems, Location:Sprinkler system
gas detection systems,fire-extinguishing systems, Comments:Licensed contractor shall make repairs to noted
mechanical smoke exhaust systems and smoke and heat deficiency in report(see attached).Report of repairs shall be
vents protection and life safety systems shall be maintained uploaded to Compliance Engine.
in an operative condition at all times,and shall be replaced or
repaired where defective.Nonrequired fire protection and life
safety systems and equipment shall be inspected,tested and
maintained or removed in accordance with Section 901.E.
S®
Emergency Equipment
Status Code Description
Fail 1203.4.3-Records.
ORecords of the inspection,testing and maintenance of Location:Backup generator
emergency and standby power systems shall include the date Comments:Provide annual inspection report of generator including
of service,name of the servicing technician,a summary of any deficiencies corrected to inspector.
conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken.
Such records shall be maintained.
GENERATED ON 5/26/26, 12:40 PM 2 OF 4
Commercial Cooking Hood Suppression System
Status Code Description
Fail 606.3.3.1 - Inspection.
Ox Hoods, grease-removal devices, fans, ducts and other Location: Kitchen hood suppression system
appurtenances shall be inspected at intervals specified in Comments: Contractor shall make repairs and upload repair report to
Table 606.3.3.1 or as approved by the fire code official. Compliance Engine. See attached deficiency report
Inspections shall be completed by qualified individuals.
•
sow..
MI MI
Fire Resistant Construction Maintenance
Status Code Description
Fail 704.1 - Maintaining protection.
QWhere required when the building was originally constructed, Location: Fire rated door smoke seals.
materials and systems used to protect joints and voids in the Comments: Missing or damaged door smoke seals shall be replaced
following locations shall be maintained. The materials and in rooms 903/905, 908, 917, 831, 831, 830, 829, 828, 827, 826, 825, 823,
systems shall be securely attached to or bonded to the 804, 723, 724, 725, 728, 730, 624, 626, 731, 521, "Data room" doors on
adjacent construction, without openings visible through the 7th, 6th, 5th & 4th floors, East & West end stair tower doors on 8th
construction. 1.Joints in or between fire-resistance-rated floor. Documentation of repairs completed may be provided to
walls, floors or floor/ceiling assemblies and roof or inspector by email.
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full-open position Location: Room #432
and latch automatically. Comments: Repair or replace door that failed to self-shut and latch.
Replacement of door requires permit and inspection obtained.
Fail 705.2.6 - Testing.
( ) Horizontal and vertical sliding and rolling fire doors shall be Location: Rolling fire doors
inspected and tested annually to confirm proper operation Comments: Provide documentation of annual inspections of all
and full closure. Records of inspections and testing shall be rolling fire doors in the building. Reports may be emailed to inspector
maintained.
GENERATED ON 5/26/26, 12:40 PM 3 OF 4
Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $610.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 5/26/26, 12:40 PM 4 OF 4
OF WA rF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
06/01/2026 07/06/2026 2026-00000498 $610.00
� a : o
•
• u n r' •
T—.=♦ O
Customer#: 13049 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
ISLE OF CAPRI 715 Mulberry St
ACCOUNTS PAYABLE WATERLOO, IA 50703
777 ISLE OF CAPRI BLVD
WATERLOO, IA 50701
Amount Enclosed.
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-777 ISLE OF CAPRI BLVD- FOR BILLING INQUIRY: (319)291-4323
05/12/2026
Description Total Price
INSPECTION 100,000 $600.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13049 06/01/2026 07/06/2026 2026-00000498 $610.00
Less Prepayment $0.00
Total Due — $610.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.