HomeMy WebLinkAbout421 OAK AVENUE - THE ROSE Waterloo Fire Rescue
1 Inspection Report 425 E.3rd Street
The Rose-421 Oak AVE,BLDG 421 Oak Ave,Waterloo IA 50703
"jt,,t E oi.. 0 'w100
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
05/26/2026 Residential Common Areas Inspection 4 O U 16797
Lead Inspector Shift Station
Unit
JEREMIAH VANDYKE N/A N/A N/A
Other Inspectors
BRAD BALDWIN
SUMMARY OF INSPECTION
025 04 ® 4
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
JEREMIAH VANDYKE
Reinspection Date
jeremiah.vandyke@waterloo-ia.org
06/25/2026
GENERAL NOTES
JEREMIAH VANDYKE-05126/2026 @ 09:49
Fire extinguisher 2026
i_,
b/
20f6/2O27/2O2a
JEREMIAH VANDYKE-05/2612026 @ 14:41
Roll down fire door inspected 5/25/2026
JEREMIAH VANDYKE-05/26/2026 @ 14:42
Clothes dryers vents cleaned by AKA 2/11/2026,
JEREMIAH VANDYKE-05/26/2026 @ 14:53
Re-inspection dates are automatically generated 30 days out from the initial inspection.Normal operating hours for inspections&re-inspections are
Monday-Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on a weekend,the re-inspection will typically be performed
GENERATED ON 5/26/26, 2:55 PM
1 OF 4
the following Monday or Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier re-inspection.....Re inspection fees
may be assessed for subsequent re-inspections.Re-inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-0512612026 @ 14:53
Lt.Van Dyke•jeremiah.vandyke@waterloo-ia.Org-Work:319-291-4460-Cell:319.083-1615
JEREMIAH VANDYKE-0512612026 @ 14:54
Inspection Fee=$80.00(To be mailed out by City via snail mail.)
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Gladys Rainey
Date: JEREMIAH VANDYKE 0512612026
CHECKLISTS
Residential Common Areas Inspection
Status Code oescrlption
Fail 1104.5-Illumination emergency power.
Where means of egress illumination is provided,the power Location:Egress lights X3 near 301,320,&226.
supply for means of egress illumination shall normally be Comments:Egress lights X3 near 301,320,&226.
provided by the premises'electrical supply.In the event of
power supply failure,illumination shall be automatically
provided from an emergency system for the following
occupancies where such occupancies require two or more
means of egress:1.Group A having 50 or more occupants.
Exception:Assembly occupancies used exclusively as a
place of worship and having an occupant load of less than
300.2.Group B buildings three or more stories in height,
buildings with 100 or more occupants above or below a level
of exit discharge serving the occupants or buildings with
1,000 or more total occupants.3.Group E in interior exit
access and exit stairways and ramps,corridors,windowless
areas with student occupancy,shops and laboratories.
4.Group F having more than 100 occupants.Exception:
Buildings used only during daylight hours and that are
provided with windows for natural light in accordance with
the International Building Code.5.Group I.6.Group M.
Exception:Buildings less than 3,000 square feet(279 m2)in
gross sales area on one story only,excluding mezzanines.
7.Group R-1.Exception:Where each sleeping unit has direct
access to the outside of the building at grade.8.Group R-2.
Exception:Where each dwelling unit or sleeping unit has
direct access to the outside of the building at grade.
Fail 20151FC-Fire alarm testing and maintenance
Is the fire alarm system powered,operational and displaying Location:Fire alarm past due on compliance engine 139 days..
normal operation(no troubles,supervisory,or alarms)? Comments:Contact contractor to upload inspection report to
compliance engine.
OF a
GENERATED ON 5/26/26, 2:55 RR
Additional Codes
5catus Code Description
Fail 904.12.1 - Maintenance.
Not less than semiannually, an inspection shall be conducted Location: Hood suppression system is past due 123 days according
by a trained person to assess whether the system is in to compliance engine.
working order. Not less than annually, a certified fire
Comments: Contact contractor to upload report for hood
suppression contractor having knowledge of and training in
suppression to compliance engine.
the installation, operation and maintenance of the specific
fire-extinguishing system shall inspect, test, service and
maintain such system in accordance with this section and the
manufacturer's specifications and servicing
manuals. Records of inspections and testing shall be
maintained.
Fail 907.8.4 - Inspection, testing and maintenance.
OThe building owner shall be responsible to maintain the fire Location: Compliance engine has 1 Deficiency Found: Answer: Wet
and life safety systems in an operable condition at all times. system 2.5" Reliable BFG-300 control valve with tamper doesn't
Service personnel shall meet the qualification requirements report to the panel. System side OS&Y valve tamper needs
of NFPA 72 for inspection, testing and maintenance of such adjustment so when closing it reports to the panel.
systems. Records of inspection, testing and maintenance
shall be maintained. Comments: Contact contractor to update compliance engine that the
system has been corrected.
GENERATED ON 5/26/26, 2:55 PM
3 OF 4
0 Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
4 OF 4
GENERATED ON 5/26/26, 2:55 PM
OF eir WA 7- INVOICE DATE DUE DATE INVOICE# TOTAL DUE
to 06/01/2026 07/06/2026 2026-00000509 $80.00
u.,ff/f4.. l C
• 11111■luull 11 I I •
> T "T O
�S 7dI7��
Customer#: 23235 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
THE ROSE OF WATERLOO 715 Mulberry St
ATTN: DIANE MURPHY - OPEN ARMS WATERLOO, IA 50703
421 OAK AVE
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-421 OAK AVE-05/26/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23235 06/01/2026 07/06/2026 2026-00000509 $80.00
Less Prepayment $0.00
Total Due-* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.