COMMERCIAL FIRE INSPECTION - 441 E. TOWER ST- 06/09/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
21369 06/18/2026 07/23/2026 2026-00000569 $80.00
Less Prepayment $0.00
Total Due -* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
425 E.3rd Street
Qom."+ Chilitos Mexican Bar-441 E Tower Park DR,BLDG 441 E Tower Park Dr,Waterloo IA
50702
INSPECTION DETAILS
Inspection Date Inspection Type )) Inspection Number
06/09/2026 Annual Inspection(1Yr) C ,co 17827
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
034 ® 16 ® 30
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
07/02/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-06110/2026 @ 06:58
•$80 annual inspection fee
BRAD BALDWIN-06110/2026 @ 06:58
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-06110/2026 @ 06:58
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-06/10/2026 @ 06:58
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature2I?
Report completedeelpost stinspection
Aurora Torres Date: BRAD BALDWIN 06110/2026
CHECKLISTS
GENERATED ON 6/10/26, 7:43 AM 1 OF 10
Means of Egress
Status Code Description
Fail 1032.2-Reliability.
Required exit accesses,exits and exit discharges shall be Location:Back exit
continuously maintained free from obstructions or Comments:Remove obstructions to clear path of egress to exit door
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Emergency Equipment
s,,-t 5 Code Description
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Front exit(exterior door)
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign and lights that failed to
the required load for a duration of not less than 90 minutes. illuminate during test
General Housekeeping
Status Code Description
Fail 304.3.1-Spontaneous ignition.
Materials susceptible to spontaneous ignition,such as oily Location:Kitchen
rags,shall be stored in a listed disposal container.Contents Comments:Provide listed container for disposal of oily rags.See
of such containers shall be removed and disposed of daily. attached
Fag l&I
oie
• • _
GENERATED ON 6/10/26, 7:43 AM 2 OF 10
Electrical Safety
Scat s Code Description
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Women's bathroom
Identified electrical hazards shall be abated.Identified Comments:Floor fan cord pinched in doorway shall be removed
hazardous electrical conditions in permanent wiring shall be immediately
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:North exterior of building
Identified electrical hazards shall be abated.Identified Comments:Licensed electrician shall make necessary repairs to
hazardous electrical conditions in permanent wiring shall be damaged conduit to avoid exposed wiring.Obtain invoice of work
brought to the attention of the responsible code official. completed to provide to inspector.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
�. s� "! e
s 't tie , s h r-,..x , 4-,
s
7.--yp e\,,, , - :. -----_, —.1s-:-..,41
vli t-
itl'y
Y f ''' Vi
Wl
''k r ' Rz
lift
3 OF 10
GENERATED ON 6/10/26, 7:43 AM
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Northwest dining area
for permanent wiring and shall be listed and labeled in Comments:Remove extension cord plugged to Dos Equis lighted
accordance with UL 817.Extension cords and flexible sign.Flexible wiring also not allowed to extend through drop ceiling
cordsshall not be affixed to structures,extended through in to concealed spaces.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
1 ,
WO
1
s
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Outdoor patio
for permanent wiring and shall be listed and labeled in Comments:Per City Electrical Inspector:Remove extension cord
accordance with UL 817.Extension cords and flexible plugged to patio"tree"with lights.Licensed electrician shall be
cordsshall not be affixed to structures,extended through obtained to inspect proper wiring connections and wiring to the tree
walls,ceilings or floors,or under doors or floor coverings, and make any necessary repairs,report or repair invoice shall be
nor shall such cords be subject to environmental damage or kept and shown to inspector
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Outdoor patio bar
for permanent wiring and shall be listed and labeled in Comments:Remove brown extension cord in bar
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 6/10/26, 7:43 AM 4 OF 10
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Bar
for permanent wiring and shall be listed and labeled in Comments:Remove white multi-plug extension cord plugged to pink
accordance with UL 817.Extension cords and flexible power strip.
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 6/10/26, 7:43 AM 5 OF 10
Additional Codes
sa[_is Crde Description
Fail 606.2-Where required.
A Type I hood shall be installed at or above all commercial Location:Kitchen-Mini fryer
cooking appliances and domestic cooking appliances used Comments:Cooking equipment producing grease laden vapors shall
for commercial purposes that produce grease vapors. be installed under hood exhaust system.Currently mini fryer is
Exceptions:1.Factory-built commercial exhaust hoods that outside of hood coverage.Mini fryer shall also be removed from
are listed and labeled in accordance with UL 710,and plugged to an extension cord.
installed in accordance with Section 304.1 of the International
Mechanical Code,shall not be required to comply with
Sections 507.1.5,507.2.3,507.2.5,507.2.8,507.3.1,507.3.3,
507.4 and 507.5 of the International Mechanical Code.
2.Factory-built commercial cooking recirculating systems that
are listed and labeled in accordance with UL 7108,and
installed in accordance with Section 304.1 of the International
Mechanical Code,shall not be required to comply with
Sections 507.1.5,507.2.3,507.2.5,507.2.8,507.3.1,507.3.3,
507.4 and 507.5 of the International Mechanical Code.Spaces
in which such systems are located shall be considered to be
kitchens and shall be ventilated in accordance with Table
403.3.1.1 of the International Mechanical Code.For the
purpose of determining the floor area required to be
ventilated,each individual appliance shall be considered as
occupying not less than 100 square feet(9.3 m2).3.Where
cooking appliances are equipped with integral down-draft
exhaust systems and such appliances and exhaust systems
are listed and labeled for the application in accordance with
NFPA 96,a hood shall not be required at or above them.4.A
Type I hood shall not be required for an electric cooking
appliance where an approved testing agency provides
documentation that the appliance effluent contains 5 mglm3
or less of grease when tested at an exhaust flow rate of 500
cfm(0.236 m31s)in accordance with UL 710B.
•
•
if >
rA
Fail 606.3.1-Ventilation system.
The ventilation system in connection with hoods shall be Location:Kitchen-Fryer
operated at the required rate of air movement,and grease Comments:Filter not in place shall be installed.
filters listed and labeled in accordance with UL 1046 shall be
in place where equipment under a kitchen grease hood is
used.
GENERATED ON 6/10/26, 7:43 AM 6 OF 10
Fail 606.3.4-Extinguishing system service.
0 Automatic fire-extinguishing systems protecting commercial Location:Kitchen-All exhaust hoods
cooking systems shall be serviced as required in Section Comments:Several suppression head covers noted off,covers shall
904.13.5. be maintained coveringsuppression heads at all times.
4 v ,
9
Ilk
€cj
- t; ' t \ ‘
' .''' ' , illik\,, \\ , '
Ili : a ,._,......-
GENERATED ON 6/10/26, 7:43 AM 7 OF 10
Commercial Cooking Hood Suppression System
S'auls ;-.cL;_ Description
Fail 606.3.3.1-Inspection.
Hoods,grease-removal devices,fans,ducts and other Location:Kitchen exhaust hood suppression
appurtenances shall be inspected at intervals specified in Comments:Provide suppression system inspection report with any
Table 606.3.3.1 or as approved by the fire code official. deficiencies corrected.Contractor must upload report to Compliance
Inspections shall be completed by qualified individuals. Engine.Currently 147 days past due for uploaded report
Fail 606.3.3.2-Grease accumulation.
If during the inspection it is found that hoods,grease-removal Location:Kitchen-Main hood
devices,fans,ducts or other appurtenances have an Comments:Accumulation of grease noted on hood exhaust
accumulation of grease,such components shall be cleaned in suppression lines today,remove all excess grease.
accordance with A NSIIIKECA C10.
iii , ..4 v ‘,,, :
rif
II
;)
4 N. , 1
. , . , ,
T b
41111,
L e
g, m,`
rs-
34 4 t
GENERATED ON 6/10/26, 7:43 AN 8 OF 10
Fire Resistant Construction Maintenance
Status Code Description
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Kitchen-Above microwave and dishwashing station
materials and systems used to protect joints and voids in the Comments:Provide missing ceiling tiles.
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Portable Fire Extingusihers
Status Code Description
Fail 906.2-General requirements.
OPortable fire extinguishers shall be selected,installed and Location:Kitchen-Class K extinguisher
maintained in accordance with this section and NFPA 10. Comments:Annual service due in July 2026
Exceptions:1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 6/10/26, 7:43 AN 9 OF 10