HomeMy WebLinkAbout3301 GREYHOUND DRIVE - LOVES COUNTRY STORE W A r INVOICE DATE DUE DATE INVOICE# TOTAL DUE
4F4+
kk 06/18/2026 07/23/2026 2026-00000571 $80.00
. 1A0
• . „1.1 ,Ir .
Customer#: 23121 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
LOVES COUNTRY STORE 715 Mulberry St
3301 GREYHOUND DR WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-3301 GREYHOUND DR- FOR BILLING INQUIRY: (319)291-4323
06/09/2026
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23121 06/18/2026 07/23/2026 2026-00000571 $80.00
Less Prepayment $0.00
Total Due —* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
425 E.3rd Street
ice+ Loves Country Store-3301 Greyhound DR,BLDG 3301 Greyhound Dr,Waterloo IA
50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
06/09/2026 Annual Inspection(3Yr) I
15602
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A NIA N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
0 39 d 10 ® 26
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 07108/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-06/10/2026 @ 08:02
•$80 annual inspection fee
BRAD BALDWIN-06110/2026 @ 08:02
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-06110/2026 @ 08:02
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-06/10/2026 @ 08:02
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completededpost stinspection
Andy Wilson Date: BRAD BALDWIN 06/10/2026
CHECKLISTS
GENERATED ON 6/10/26, 2:53 PM 1 OF 5
Means of Egress
Status Code Description
Fail 1010.1.3-Door opening force Forces to unlatch and open
doors. Location:Exit door near showers
The force for pushing or pulling open interior swinging Comments:Repair or replace exit door that failed to open with less
egress doors,other than fire doors,shall not exceed 5 than 15Ibs of force during inspection.Replacement of door requires
pounds(22 N).These forces do not apply to the force permit and inspection obtained.
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
Emergency Equipment
Status Code Description
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Deli prep area
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress light above shelving that failed
to illuminate during test.Also,lower storage below egress light to
avoid blocking view of lighting in case of emergency.
Fire Sprinkler System
Status Code Description
Fail 903.3.3-Obstructed locations.
Automatic sprinklers shall be installed with regard to Location:Customer laundry room
obstructions that will delay activation or obstruct the water Comments:Remove dust and debris from sprinkler heads.
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
GENERATED ON 6/10/26, 2:53 PM 2 OF 5
Electrical Safety
Status Code Description
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:SE parking lot-Air station near gas pumps
Identified electrical hazards shall be abated.Identified Comments:Licensed electrician shall be obtained to make necessary
hazardous electrical conditions in permanent wiring shall be repairs to exterior receptacle.Currently unable to open and access
brought to the attention of the responsible code official. outlet and wiring pinched by cover.Obtain invoice of work completed
Electrical wiring,devices,appliances and other equipment to provide to inspector.
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
} _ , •
mow.
m
�fr r
..
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Front Loves!Wendys sign post
prohibited.Approved covers shall be provided for all switch Comments:Provide missing weather rated outlet cover.
and electrical outlet boxes.
•
40.
04-` n wM t t.. ..
,r
•
3 OF 5
GENERATED ON 6/10/26, 2:53 PM
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Ice machine room
equipment shall be provided in accordance with Section Comments:Remove obstructions to clear path of access to electric
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or panel.Maintain 36"clearance to panel at all times.
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
Additional Codes
Status Code Description
Fail 610.1.2-Maintenance.
The lint trap,mechanical and heating components,and the Location:Customer and"DAS"clothes dryers
exhaust duct system of a clothes dryer shall be maintained in Comments:Provide documentation of cleaning dryer vent piping
accordance with the manufacturer's operating from the appliances to the exterior including signed and dated.
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion.
Fail 907.8.4-Inspection,testing and maintenance.
The building owner shall be responsible to maintain the fire Location:Towel room
and life safety systems in an operable condition at all times. Comments:Replace missing smoke detector,bracket on wall without
Service personnel shall meet the qualification requirements detector present.
of NFPA 72 for inspection,testing and maintenance of such
systems.Records of inspection,testing and maintenance
shall be maintained.
Fire Resistant Construction Maintenance
Status Code Description
Fail 705.2.4-Door operation.
Swinging fire doors shall close from the full-open position Location:Towel room
and latch automatically. Comments:Repair or replace fire rated door that failed to self-shut
and latch.Replacement of door requires permit and inspection
obtained.
Fail 705.2.6-Testing.
Horizontal and vertical sliding and rolling fire doors shall be Location:Rolling fire door separating LoveslWendys
inspected and tested annually to confirm proper operation Comments:Provide documentation of annual fire drop door test
and full closure.Records of inspections and testing shall be
maintained.
GENERATED ON 6/10/26, 2:53 PM 4 OF 5
Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
N/A $80.00
Invoice Number Check Number Transaction Number
N/A NIA NIA