HomeMy WebLinkAbout321 W 4TH STREET - LA PLACITA MEXICAN STORE OF W q7.4' INVOICE DATE DUE DATE INVOICE# TOTAL DUE
41� 06/18/2026 07/23/2026 2026-00000573 $80.00
f.0
)a o
4S 1tlI7`�
Customer#: 10626 Please Make Check Payable and Remit To:
City of Waterloo
ATTN.: City Clerk/Accounts Receivable
LA PLACITA MEXICAN STORE 715 Mulberry St
321 W 4TH ST WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION- 321 W. 4TH ST-06/12/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
10626 06/18/2026 07/23/2026 2026-00000573 $80.00
Less Prepayment $0.00
Total Due -+ $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
°''„1,1 Inspection Report
� 425 E.3rd Street
La Placita-321 W 4th ST,BLDG 321 W 4th St,Waterloo IA 50702
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
06/12/2026 Annual Inspection(1Yr) (1)(Qa(e 90.1:6 17431
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
N/A
SUMMARY OF INSPECTION
0 39 C 7 ® 29
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 07/08/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-0611212026 @ 12:25
•$80 annual inspection fee
BRAD BALDWIN-06/12/2026 @ 12:25
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-06112/2026 @ 12:25
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-06112/2026 @ 12:25
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completedeelpost stinspection
Araceli Carillo(2025) Date: BRAD BALDWIN 06/12/2026
CHECKLISTS
GENERATED ON 6/12/26, 3:28 PM 1 OF
Emergency Equipment
Stanis Code Description
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:High bay egress lights(3)above shelving/dining
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Provide documentation of testing and proper operation
of ceiling egress lights with signature and date.Can email to
inspector.
General Housekeeping
Maws Code Description
Fail 304.3.1-Spontaneous ignition.
Materials susceptible to spontaneous ignition,such as oily Location:Kitchen
rags,shall be stored in a listed disposal container.Contents Comments:Oily rags shall be disposed of in listed container,a larger
of such containers shall be removed and disposed of daily. or another container shall be provided if current container is not
large enough to dispose of all dirty rags on-site.
2 OF 6
GENERATED ON 6/12/26, 3:28 PM
Additional Codes
Status Code Description
Fail 315.3-Storage in buildings.
0 Storage of materials in buildings shall be orderly and stacks Location:Kitchen
shall be stable.Storage of combustible materials shall be Comments:Relocate oily rag container to avoid close proximity to
separated from heaters or heating devices by distance or heat source of cooking equipment
shielding so that ignition cannot occur.
`A,>
a III
1.
�ws
Fail 5303.5.3-Securing compressed gas containers,cylinders
0 and tanks. Location:Water heater room
Compressed gas containers,cylinders and tanks shall be Comments:Secure compressed gas cylinders with chain to avoid tip
secured to prevent falling caused by contact,vibration or over.
seismic activity.Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers,cylinders and tanks to a fixed object
with one or more restraints.2.Securing containers,cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers,cylinders or tanks.
3.Nesting of compressed gas containers,cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks,if
dislodged,do not obstruct the required means of egress.
4.Securing of compressed gas containers,cylinders and
tanks to or within a rack,framework,cabinet or similar
assembly designed for such use.Exception:Compressed gas
containers,cylinders and tanks in the process of
examination,filling,transport or servicing.
GENERATED ON 6/12/26, 3:28 PM 3 OF 6
Electrical Safety
„;u Code Description
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Behind meat display cases
equipment shall be provided in accordance with Section Comments:Remove storage within 36 inches of electrical panels.
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
027
Commercial Cooking Hood Suppression System
Status Cnde Description
Fail 606.3.3-Cleaning.
OHoods,grease-removal devices,fans,ducts and other Location:Kitchen exhaust hood
appurtenances shall be cleaned at intervals as required by Comments:Report of cleaning 67 days past due on Compliance
Sections 606.3.3.1 through 606.3.3.3. Engine.Contractor shall upload report including any deficiencies
corrected.AKA tagged hood,serviced April 2026.
GENERATED ON 6/12/26, 3:28 PM 4 OF 6
Portable Fire Extingusihers
Status Code Description
Fail 906.6-Unobstructed and unobscured.
l_J Portable fire extinguishers shall not be obstructed or Location:Kitchen
obscured from view.In rooms or areas in which visual Comments:Remove obstructions to clear access to Class K
obstruction cannot be completely avoided,means shall be extinguisher.
provided to indicate the locations of extinguishers.
it 4
'' rt"- �.r
I
i
i
404. 1 I
GENERATED ON 6/12/26, 3:28 PM 5 OF 6
Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 6/12/26, 3:28 PM 6 OF 6