HomeMy WebLinkAboutLONGHORN STEAKHOUSE-1425 E. SAN MARNAN DR Waterloo Fire Rescue
NitID Inspection Report 425 E.3rd Street
04707 Longhorn Steakhouse-1425 E San Marnan DR,BLDG 1425 E San Marnan Dr,
Waterloo IA 50702
INSPECTION DETAILS
Inspection Date Inspection Type \ Inspection Number
06/29/2026 Annual Inspection(1Yr) ,Lana "VV 21953
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
058 04 ® 12
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
0712212026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-06130/2026 @ 08:07
•$80 annual inspection fee
BRAD BALDWIN-06/30/2026 @ 08:07
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-06/30/2026 @ 08:08
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-0613012026 @ 08:08
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completedeelpost stinspection
Faith McRae 2025 Date: BRAD BALDWIN 06/30/2026
CHECKLISTS
GENERATED ON 6/30/26, 8:16 AM 1 OF 3
Emergency Equipment
Status Cole Description
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Bathroom hallway
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights that failed to illuminate
during test.
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Behind hostess stand
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign that failed to illuminate during
the required load for a duration of not less than 90 minutes. test
Fire Sprinkler System
Status Code Description
Fail 903.3.3-Obstructed locations.
Ox Automatic sprinklers shall be installed with regard to Location:Kitchen
obstructions that will delay activation or obstruct the water Comments:Remove dust and debris from sprinkler head above
distribution pattern and shall be in accordance with the kitchen bulletin board.
applicable automatic sprinkler system standard that is being
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
Fail 903.3.3-Obstructed locations.
CJAutomatic sprinklers shall be installed with regard to Location:Kitchen
obstructions that will delay activation or obstruct the water Comments:Remove dust and debris from sprinkler head above
distribution pattern and shall be in accordance with the utensils/plates shelving.
applicable automatic sprinkler system standard that is being
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
GENERATED ON 6/30/26, 8:16 AM 2 OF 3
'1 Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA N►A NIA
GENERATED ON 6/30/28, 8:16 AN 3 OF 3
O� W A 74' INVOICE DATE DUE DATE INVOICE# TOTAL DUE
06/30/2026 08/05/2026 2026-00000594 $80.00
O
Customer#: 14982 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
LONGHORN STEAKHOUSE#5374 715 Mulberry St
P.O. BOX 695016 WATERLOO, IA 50703
ORLANDO, FL 32869
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION- 1425 E. SAN MARNAN DR- FOR BILLING INQUIRY: (319)291-4323
06/29/2026
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
14982 06/30/2026 08/05/2026 2026-00000594 $80.00
Less Prepayment $0.00
Total Due—* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.