Loading...
HomeMy WebLinkAboutTHREE AMIGO'S-2820 FALLS AVE Waterloo Fire Rescue t Inspection Report 425 E.3rd Street Three Amigo's-2820 Falls AVE,BLDG 2820 Falls Ave,Waterloo IA 50701 INSPECTION DETAILS Inspection Date Inspection Type �^ Inspection Number 06123/2026 Annual Inspection(1Yr) - is`, 18632 1 "`GGGG TTTT . Lead Inspector Shift Station Unit BRAD BALDWIN N/A NIA N/A Other Inspectors N/A SUMMARY OF INSPECTION 0 41 0 9 ® 26 Passed codes Failed codes N/A codes NEXT STEPS Please direct questions about your Inspection to: Reinspection Date BRAD BALDWIN 07/1612026 brad.baldwin@waterloo-ia.org,3192914319 GENERAL NOTES BRAD BALDWIN-06/2312026 @ 12:42 •$80 annual inspection fee BRAD BALDWIN-06123/2026 @ 12:42 •Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224 BRAD BALDWIN-06123/2026 @ 12:42 •Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards corrected BRAD BALDWIN-06123/2026 @ 12:42 •If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re- inspection fees start at$100,then$150,and$200 for all subsequent re-inspections. BRAD BALDWIN-06/23/2026 @ 12:45 Christmas lighting noted throughout dining area is allowed for temporary use(90 days)2021 IFC:603.8 SIGNATURES Contact signature Inspector signature No signature Report completededpost stinspection Thomas Hernadus Date: BRAD BALDWIN 06/23/2026 CHECKLISTS GENERATED ON 6/23/26, 1:06 PM 1 OF 6 Means of Egress Status Code Description Fail 1010.1.3-Door opening force Forces to unlatch and open Ox doors. Location:East exit(dining area) The force for pushing or pulling open interior swinging Comments:Repair or replace exit door that failed to open during egress doors,other than fire doors,shall not exceed 5 inspection,door shall open with less than 151bs of force. pounds(22 N).These forces do not apply to the force Replacement of door requires permit and inspection obtained. required to retract latch bolts or disengage other devices that hold the door in a closed position.For other swinging doors, as well as sliding and folding doors,the door latch shall release when subjected to a 15-pound(67 N)force.The door shall be set in motion when subjected to a 30-pound(133 N) force.The door shall swing to a full-open position when subjected to a 15-pound(67 N)force.The forces to unlatch doors shall comply with the following:1.Where door hardware operates by push or pull,the operational force to unlatch the door shall not exceed 15 pounds(66.7 N).2.Where door hardware operates by rotation,the operational force to unlatch the door shall not exceed 28 inch-pounds(315 N-cm). The force to open doors shall comply with the following: 1.For interior swinging egress doors that are manually operated,other than doors required to be fire rated,the force for pushing or pulling open the door shall not exceed 5 pounds(22 N).2.For other swinging doors,sliding doors or folding doors,and doors required to be fire rated,the door shall require not more than a 30-pound(133 N)force to be set in motion and shall move to a full-open position when subjected to not more than a 15-pound(67 N)force. Fail 1010.1.3-Door opening force Forces to unlatch and open Ox doors. Location:West exit(on stairs to basement) The force for pushing or pulling open interior swinging Comments:Repair or replace exit door that failed to open during egress doors,other than fire doors,shall not exceed 5 inspection,door shall open with less than 15lbs of force. pounds(22 N).These forces do not apply to the force Replacement of door requires permit and inspection obtained. required to retract latch bolts or disengage other devices that hold the door in a closed position.For other swinging doors, as well as sliding and folding doors,the door latch shall release when subjected to a 15-pound(67 N)force.The door shall be set in motion when subjected to a 30-pound(133 N) force.The door shall swing to a full-open position when subjected to a 15-pound(67 N)force.The forces to unlatch doors shall comply with the following:1.Where door hardware operates by push or pull,the operational force to unlatch the door shall not exceed 15 pounds(66.7 N).2.Where door hardware operates by rotation,the operational force to unlatch the door shall not exceed 28 inch-pounds(315 N-cm). The force to open doors shall comply with the following: 1.For interior swinging egress doors that are manually operated,other than doors required to be fire rated,the force for pushing or pulling open the door shall not exceed 5 pounds(22 N).2.For other swinging doors,sliding doors or folding doors,and doors required to be fire rated,the door shall require not more than a 30-pound(133 N)force to be set in motion and shall move to a full-open position when subjected to not more than a 15-pound(67 N)force. Emergency Equipment Status Code Desorption Fail 1203.2.6-Exit signs. Ox Emergency power shall be provided for exit signs as required Location:East exit in Section 3013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign and lights combo that failed to the required load for a duration of not less than 90 minutes. illuminate during test. GENERATED ON 6/23/26,1:06 PM 2 OF 6 Additional Codes Status Code Description Fail 603.1 - General. Electrical equipment, wiring and systems required by this Location: Kitchen code or the International Building Code shall be installed, Comments: REPEAT VIOLATION: Remove microwave plugged to used and maintained in accordance with NFPA 70 and extension cord. Microwave shall be relocated to plug directly to Sections 603.2 through 603.10. permanent outlet or new outlet installed with obtaining permit and inspection. GENERATED ON 6/23/26, 1:06 PM 3 OF 6 Electrical Safety Celt Description Fail 603.2.2-Unapproved conditionsOpen electrical terminations. Open junction boxes and open-wiring splices shall be Location:Basement-Above exercise equipment prohibited.Approved covers shall be provided for all switch Comments:Electrical wiring connections shall be made properly in and electrical outlet boxes. box with box cover installed. Fail 603.2.2-Unapproved conditionsOpen electrical terminations. Open junction boxes and open-wiring splices shall be Location:Basement prohibited.Approved covers shall be provided for all switch Comments:Install missing box covers and electrical outlet boxes. F }, ' K ! • :pay I GENERATED ON 6/23/26, 1:66 PR 4 OF 6 Fail 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute Location:Basement-Furnace for permanent wiring and shall be listed and labeled in Comments:Remove condensation um accordance with UL 817.Extension cords and flexible pump plugged to extension cord. Pump shall plug directly to a permanent wall outlet.If adding a new cordsshall not be affixed to structures,extended through outlet,permit and inspection shall be obtained walls,ceilings or floors,or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact.Extension cords shall be used only with portable appliances.Extension cords marked for indoor use shall not be used outdoors. Commercial Cooking Hood Suppression System Sta"" Code Description Fail 606.3.3-Cleaning. Hoods,grease-removal devices,fans,ducts and other Location:Kitchen hood exhaust appurtenances shall be cleaned at intervals as required by Comments:Exhaust system cleaning 13 days past due as of 6/23126. Sections 606.3.3.1 through 606.3.3.3. Provide cleaning and report to be uploaded to Compliance Engine with any deficiencies corrected. Fail 606.3.3.2-Grease accumulation. If during the inspection it is found that hoods,grease-removal Location:Kitchen hood exhaust and cooking equipment devices,fans,ducts or other appurtenances have an Comments:Clean all accumulations of filters dripping grease, accumulation of grease,such components shall be cleaned in grease today and noted heavy grease on gas line supplys to and on cooking accordance with ANSIIIKECA C10. equipment. GENERATED ON 6/23/26, 1:06 PM 5 OF 6 Statement of Fees FEE Invoice Date Inspection Fee Date Paid Amount Paid NIA $80.00 Invoice Number Check Number Transaction Number NIA NIA NIA GENERATED ON 6/23/26, 1:66 PM 6 OF 6 OF W qr INVOICE DATE DUE DATE INVOICE# TOTAL DUE 1% 0 06/30/2026 08/05/2026 2026-00000614 $80.00 O *-. T O 4. 4s7v17N9 Customer#: 22167 Please Make Check Payable and Remit To: City of Waterloo ATTN: City Clerk/Accounts Receivable 3 AMIGOS 715 Mulberry St 2820 FALLS AVE WATERLOO, IA 50703 WATERLOO, IA 50701 Amount Enclosed: DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT KEEP THIS PORTION FOR YOUR RECORDS COMMERCIAL FIRE INSPECTION - 2820 FALLS AVE- 06/23/2026 FOR BILLING INQUIRY: (319)291-4323 Description Total Price INSPECTION 2,000 $70.00 OCCUPANCY FEE $10.00 CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES 22167 06/30/2026 08/05/2026 2026-00000614 $80.00 Less Prepayment $0.00 Total Due---> $80.00 City of Waterloo Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of Administrative Services Offset Program if not paid in full within ninety days.