t Inspection Report 425 E.3rd Street
Three Amigo's-2820 Falls AVE,BLDG 2820 Falls Ave,Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type �^ Inspection Number
06123/2026 Annual Inspection(1Yr) - is`, 18632
1 "`GGGG TTTT .
Lead Inspector Shift
Station Unit
BRAD BALDWIN N/A NIA N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
0 41 0 9 ® 26
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
07/1612026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-06/2312026 @ 12:42
•$80 annual inspection fee
BRAD BALDWIN-06123/2026 @ 12:42
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-06123/2026 @ 12:42
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-06123/2026 @ 12:42
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-06/23/2026 @ 12:45
Christmas lighting noted throughout dining area is allowed for temporary use(90 days)2021 IFC:603.8
SIGNATURES
Contact signature Inspector signature
No signature
Report completededpost stinspection
Thomas Hernadus Date: BRAD BALDWIN 06/23/2026
CHECKLISTS
GENERATED ON 6/23/26, 1:06 PM 1 OF 6
Means of Egress
Status Code Description
Fail 1010.1.3-Door opening force Forces to unlatch and open
Ox doors.
Location:East exit(dining area)
The force for pushing or pulling open interior swinging Comments:Repair or replace exit door that failed to open during
egress doors,other than fire doors,shall not exceed 5 inspection,door shall open with less than 151bs of force.
pounds(22 N).These forces do not apply to the force Replacement of door requires permit and inspection obtained.
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
Fail 1010.1.3-Door opening force Forces to unlatch and open
Ox doors. Location:West exit(on stairs to basement)
The force for pushing or pulling open interior swinging Comments:Repair or replace exit door that failed to open during
egress doors,other than fire doors,shall not exceed 5 inspection,door shall open with less than 15lbs of force.
pounds(22 N).These forces do not apply to the force Replacement of door requires permit and inspection obtained.
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
Emergency Equipment
Status Code Desorption
Fail 1203.2.6-Exit signs.
Ox Emergency power shall be provided for exit signs as required Location:East exit
in Section 3013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign and lights combo that failed to
the required load for a duration of not less than 90 minutes. illuminate during test.
GENERATED ON 6/23/26,1:06 PM 2 OF 6
Additional Codes
Status Code Description
Fail 603.1 - General.
Electrical equipment, wiring and systems required by this Location: Kitchen
code or the International Building Code shall be installed, Comments: REPEAT VIOLATION: Remove microwave plugged to
used and maintained in accordance with NFPA 70 and extension cord. Microwave shall be relocated to plug directly to
Sections 603.2 through 603.10.
permanent outlet or new outlet installed with obtaining permit and
inspection.
GENERATED ON 6/23/26, 1:06 PM 3 OF 6
Electrical Safety
Celt Description
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Basement-Above exercise equipment
prohibited.Approved covers shall be provided for all switch Comments:Electrical wiring connections shall be made properly in
and electrical outlet boxes. box with box cover installed.
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Basement
prohibited.Approved covers shall be provided for all switch Comments:Install missing box covers
and electrical outlet boxes.
F
},
' K
! • :pay
I
GENERATED ON 6/23/26, 1:66 PR 4 OF 6
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Basement-Furnace
for permanent wiring and shall be listed and labeled in Comments:Remove condensation um
accordance with UL 817.Extension cords and flexible pump plugged to extension cord.
Pump shall plug directly to a permanent wall outlet.If adding a new
cordsshall not be affixed to structures,extended through outlet,permit and inspection shall be obtained
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
Sta"" Code Description
Fail 606.3.3-Cleaning.
Hoods,grease-removal devices,fans,ducts and other Location:Kitchen hood exhaust
appurtenances shall be cleaned at intervals as required by Comments:Exhaust system cleaning 13 days past due as of 6/23126.
Sections 606.3.3.1 through 606.3.3.3. Provide cleaning and report to be uploaded to Compliance Engine
with any deficiencies corrected.
Fail 606.3.3.2-Grease accumulation.
If during the inspection it is found that hoods,grease-removal Location:Kitchen hood exhaust and cooking equipment
devices,fans,ducts or other appurtenances have an Comments:Clean all accumulations of filters dripping grease,
accumulation of grease,such components shall be cleaned in grease
today and noted heavy grease on gas line supplys to and on cooking
accordance with ANSIIIKECA C10.
equipment.
GENERATED ON 6/23/26, 1:06 PM 5 OF 6
Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 6/23/26, 1:66 PM 6 OF 6
OF W qr INVOICE DATE DUE DATE INVOICE# TOTAL DUE
1% 0 06/30/2026 08/05/2026 2026-00000614 $80.00
O
*-. T O
4.
4s7v17N9
Customer#: 22167 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
3 AMIGOS 715 Mulberry St
2820 FALLS AVE WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION - 2820 FALLS AVE- 06/23/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
22167 06/30/2026 08/05/2026 2026-00000614 $80.00
Less Prepayment $0.00
Total Due---> $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.