Loading...
HomeMy WebLinkAboutFRIENDSHIP VILLAGE 2 STORY-600 PARK LANE µ r W Waterloo Fire Rescue letIns, -c - • Report BLDG 5 0-2 story 600 Park Lane,Waterloo IA 50702 I I` 425 E.3rd Street INSPECTION DETAILS Inspection Date Inspection Type Inspection Number 06122/2026 Residential Common Areas Inspection aa� cb '� 5700 Lead Inspector Shift Station Unit JEREMIAH VANDYKE N/A N/A N/A Other Inspectors BRAD BALDWIN SUMMARY OF INSPECTION 0 21 0 6 0 5 Passed codes Failed codes N/A codes NEXT STEPS Please direct questions about your Inspection to: Reinspection Date JEREMIAH VANDYKE 07123/2026 jeremiah.vandyke@waterloo-ia.org GENERAL NOTES JEREMIAH VANDYKE-06/23/2026 @ 10:07 Fire extinguisher serviced by Proshield Oct.2025 JEREMIAH VANDYKE-06/2312026 @ 10:07 4/9/2026 S-(Annual)Fire Alarm HAWKEYE ALARM Reviewed Compliant JEREMIAH VANDYKE-06/23/2026 @ 10:11 Dryers cleaned by Harris 4/22/2026. JEREMIAH VANDYKE-06/23/2026 @ 10:16 Lt.Van Dyke-jeremiah.vandyke@waterloo-ia.org-Work:319-291-4460-Cell:319-883-1615 JEREMIAH VANDYKE-06/23/2026 @ 10:17 Inspection Fee=$80.00(To be mailed out by City via snail mail.) SIGNATURES Contact signature Inspector signature No signature Report completed post inspection Chad Wagner Date: JEREMIAH VANDYKE 06/23/2026 CHECKLISTS GENERATED ON 6/23/26, 10:17 AM 1 OF 4 Residential Common Areas Inspection Sia:us Code Description Fail 1104.5-Illumination emergency power. Where means of egress illumination is provided,the power Location:Entire building, supply for means of egress illumination shall normally be Comments:Exit and egress lights need to be repaired or replaced. provided by the premises'electrical supply.In the event of Will start log for testing. power supply failure,illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress:1.Group A having 50 or more occupants. Exception:Assembly occupancies used exclusively as a place of worship and having an occupant load of less than 300.2.Group B buildings three or more stories in height, buildings with 100 or more occupants above or below a level of exit discharge serving the occupants or buildings with 1,000 or more total occupants.3.Group E in interior exit access and exit stairways and ramps,corridors,windowless areas with student occupancy,shops and laboratories. 4.Group F having more than 100 occupants.Exception: Buildings used only during daylight hours and that are provided with windows for natural light in accordance with the International Building Code.5.Group I.6.Group M. Exception:Buildings less than 3,000 square feet(279 m2)in gross sales area on one story only,excluding mezzanines. 7.Group R-1.Exception:Where each sleeping unit has direct access to the outside of the building at grade.8.Group R-2. Exception:Where each dwelling unit or sleeping unit has direct access to the outside of the building at grade. Fail 509.1-Identification. Fire protection equipment shall be identified in an approved Location:Signage needed in basement for fire Sprinkler riser and manner.Rooms containing controls for air-conditioning FACP on door. systems,sprinkler risers and valves,or other fire detection, Comments:Signage needed in basement for fire Sprinkler riser and suppression or control elements fire protection systems shall FACP on door. be identified for the use of the fire department.Approved signs required to identify fire protection system equipment and equipment location shall be constructed of durable materials,permanently installed and readily visible. Fail 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the Location:Basement:Discussed dryer vent tubing and having correct exhaust duct system of a clothes dryer shall be maintained in flow.Tube was bent. accordance with the manufacturer's operating Comments:Discussed dryer vent tubing and having correct flow. instructions to prevent the accumulation of lint or debris that Tube was bent. prevents the exhaust of air and products of combustion. Fail 705.2.4-Door operation. Swinging fire doors shall close from the full-open position Location:1st floor double doors hallway. and latch automatically. Comments:Door not closing and latching correctly. Fail 901.6-Inspection,testing and maintenance. Fire detection and alarm systems,emergency alarm systems, Location:Sprinkler system is 355 days past due on Compliance gas detection systems,fire-extinguishing systems, engine. mechanical smoke exhaust systems and smoke and heat Comments:Contact sprinkler contractor to inspect and upload report vents protection and life safety systems shall be maintained to compliance engine. in an operative condition at all times,and shall be replaced or repaired where defective.Nonrequired fire protection and life safety systems and equipment shall be inspected,tested and maintained or removed in accordance with Section 901.8. GENERATED ON 6/23/26, 16:17 AM 2 OF 4 Additional Codes S[aols Code Description Fail 603.2.2-Unapproved conditionsOpen electrical terminations. Open junction boxes and open-wiring splices shall be Location:Outside on south side of door D. prohibited.Approved covers shall be provided for all switch Comments:Open electrical box needs cover. and electrical outlet boxes. GENERATED ON 6/23/26, 10:17 AM 3 OF 4 0 Statement of Fees FEE Invoice Date Inspection Fee Date Paid Amount Paid NIA $80.00 Invoice Number Check Number Transaction Number NM NM NM GENERATED ON 8/23/28, 10:17 AM 4 OF 4 0F 4 r� INVOICE DATE DUE DATE INVOICE # TOTAL DUE ,� �� 06/30/2026 08/05/2026 2026-00000617 $80.00 V• fIIi4 w. :1. . . .'. ., • t 1r p Customer #: 23028 Please Make Check Payable and Remit To: City of Waterloo A TTN: City Clerk/Accounts Receivable FRIENDSHIP VILLAGE 715 Mulberry St 3 720 VILLAGE PLACE WATERLOO, IA 50703 WATERLOO, IA 50702 Amount Enclosed: DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT KEEP THIS PORTION FOR YOUR RECORDS COMMERCIAL FIRE INSPECTION - 600 PARK LANE 2-STORY - FOR BILLING INQUIRY: (319)291-4323 06/22/2026 Description Total Price INSPECTION 1 HH $70.00 OCCUPANCY FEE $10.00 CUSTOMER# BILLING DATE DUE DATE INVOICE # CHARGES 23028 06/30/2026 08/05/2026 2026-00000617 $80.00 Less Prepayment $0.00 Total Due — $80.00 City of Waterloo Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of Administrative Services Offset Program if not paid in full within ninety days.