Waterloo Fire Rescue
3 Inspection Report 425 E.3rd Street
" Pryme Tyme-626 Sycamore ST,BLDG 626 Sycamore St,Waterloo IA 50703
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
06/25/2026 Annual Inspection(1Yr) REINSPECTION � (� .�f�, ) act 20185-R6
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A N/A N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
0 0 0 7
Passed codes Failed codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 07/17/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-06/26/2026 @ 08:13
S200 re-inspection fee for failure to complete corrections on scheduled 6/25126 inspection.Complete all correction to avoid fees at following inspections.
BRAD BALDWIN-06104/2026 @ 07:29
S150 re-inspection fee,failure to complete corrections as of 4116126.Complete corrections to avoid possible fees at following inspections
BRAD BALDWIN-0610412026 @ 07:29
Withholding re-inspection fee today,complete corrections to avoid possible fees at later inspections.
BRAD BALDWIN-06104/2026 @ 07:29
•$80 annual inspection fee
BRAD BALDWIN-0610412026 @ 07:29
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-06104/2026 @ 07:29
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-06104/2026 @ 07:29
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-06/04/2026 @ 07:29
S100 re-inspection fee,failure to complete corrections as of 3119/26.
BRAD BALDWIN-06104/2026 @ 07:29
$200 reinspection fee,failure to complete corrections as of 518126.Phone calls with Keaton and Rodney on 5/8/26,Cedar Valley Handyman is scheduled to
make remaining necessary repairs but has not visited the site to do so yet.
GENERATED ON 6/26/26, 8:15 AM 1 OF 7
BRAD BALDWIN-06104/2026 @ 07:29
$200 re-inspection fee for failure to complete corrections on 613126 inspection.Phone call with Randy&Keaton today to address lack of progress,liquor
license will not be approved till fire inspection is complete.
SIGNATURES
Contact signature Inspector signature
No signature
Report completededpost stinspection
Rodney Lewis Date: BRAD BALDWIN 06/2612026
CHECKLISTS
GENERATED ON 6/26/26, 8:15 AM 2 OF 7
Reinspection
Status Code Description
Fail 1013.1-Where required.
Exits and exit access doors shall be marked by an approved Location:Near bathrooms
exit sign readily visible from any direction of egress travel. Comments:Exit sign shall be turned 90 degrees to direct egress
The path of egress travel to exits and within exits shall be towards alley exit between bathrooms.
marked by readily visible exit signs to clearly indicate the
direction of egress travel in cases where the exit or the path Additional comments:No progress on 6125126
of egress travel is not immediately visible to the occupants.
Intervening means of egress doors within exits shall be
marked by exit signs.Exit sign placement shall be such that
any point in an exit access corridor or exit passageway is
within 100 feet(30 480 mm)or the listed viewing distance of
the sign,whichever is less,from the nearest visible exit sign.
Exceptions:1.Exit signs are not required in rooms or areas
that require only one exit or exit access.2.Main exterior exit
doors or gates that are obviously and clearly identifiable as
exits need not have exit signs where approved by the fire
code official.3.Exit signs are not required in occupancies in
Group U and individual sleeping units or dwelling units in
Group R-1,R-2 or R-3.4.Exit signs are not required in
dayrooms,sleeping rooms or dormitories in occupancies in
Group 1-3.5.In occupancies in Groups A-4 and A-5,exit signs
are not required on the seating side of vomitories or openings
into seating areas where exit signs are provided in the
concourse that are readily apparent from the vomitories.
Egress lighting is provided to identify each vomitory or
opening within the seating area in an emergency.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:High bay egress lights
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Provide documentation of testing lights including repairs
made if necessary confirming working properly.Document shall
include address,date and signed,email to inspector.
Additional comments:No progress on 6/25126
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
COpen junction boxes and open-wiring splices shall be Location:Basement(west of stairs)
prohibited.Approved covers shall be provided for all switch Comments:Install cover on box
and electrical outlet boxes.
Additional comments:No progress on 6125126
(i /.. „ir . ,,,,..
it
#
r,
i
lir-
3 OF 7
GENERATED ON 6/26/26, 8:15 AM
Fail 603.5.2-Application and usePower supply.
Relocatable power taps and current taps shall be directly Location:Bar
connected to a permanently installed receptacle.Exceptions: Comments:Power strip plugged to another power strip at front of bar
1.Where approved for use in a Group A occupancy or in a shall be corrected.All power strips shall plug directly to wall outlets
meeting room in a Group B occupancy,not more than five for light duty electric only.
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use Additional comments:See attached photo taken on 6/25126
to supply power to electronic equipment.2.Current taps and inspection.Power strip.Multiple cords pinched behind cabinet and
relocatable power taps shall not be required to connect wall causing stress on wires.Create proper spacing for power strip
directly to a permanently installed receptacle outlet where and all wiring to plug in without stress on wires.Power strip shall be
used for 90 days or less for the purpose of testing the properly mounted to wall to avoid hanging by wires.
performance of such devices.
1110
ry�
Ii •
GENERATED ON 6/26/28, 8:15 AN
4 OF 7
Fail 701.5-Maintaining protection.
OMaterials,systems and devices used to repair or protect Location:Bathroom hallway
breaches and openings in fire-resistance-rated construction Comments:Obtain permit and inspection to install rated fire door to
and construction installed to resist the passage of smoke neighboring space,currently plywood covering door opening.
shall be maintained in accordance with Sections 703 through
707. Additional comments:No progress on 6125126
a
r
I
..
5 OF 7
GENERATED ON 6/26/26, 8:15 AM
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Ceiling
materials and systems used to protect joints and voids in the Comments:Obtain permit and inspection and repair hole in ceiling.
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the Additional comments:No progress on 6125126
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
rooflceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
(
/
jj
Fail 901.4.6-Appearance of equipment.
Any device that has the physical appearance of life safety or Location:Smoke detectors
fire protection equipment but that does not perform that life
Comments:All smoke detectors in building shall be maintained as
safety or fire protection function shall be prohibited.
working properly.Noted detectors beeping and covers off today
1/27126.
Additional comments:No progress on 6125/26
GENERATED ON 6/26/26, 8:15 AM
6 OF 7
Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $200.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 6/26/26, 8:15 AM 7 OF 7
OF WA 7.k% INVOICE DATE DUE DATE INVOICE# TOTAL DUE
'` (O 06/30/2026 08/05/2026 2026-00000604 $200.00
3- CA
9S oc
nit')
Customer#: 24658 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
PRYME TYME 715 Mulberry St
626 SYCAMORE ST WATERLOO, IA 50703
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION - 626 SYCAMORE- 06/25/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
REINSPECTION 3 $200.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24658 06/30/2026 08/05/2026 2026-00000604 $200.00
Less Prepayment $0.00
Total Due--> $200.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.