HomeMy WebLinkAboutSTUDIO 13-304 W. 4TH ST 3t.s 2 w i
Waterloo Fire Rescue
'MC Inspection Report WEIN
425 E.3rd Street
Studio 13-304 W 4th ST,BLDG 304 W 4th St,Waterloo IA 50702
INSPECTION DETAILS
Inspection Date Inspection Type �i Inspection Number
06123/2026 Annual Inspection(1Yr) a i ga ift 17104
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA N/A
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 25 0 10 Q 40
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 07/16/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-0612312026 @ 14:34
•$80 annual inspection fee
BRAD BALDWIN-06123/2026 @ 14:34
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-06123/2026 @ 14:34
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-06123/2026 @ 14:34
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Jason Zeman(2025) Date: BRAD BALDWIN 06/24/2026
CHECKLISTS
1 OF 6
GENERATED ON 6/24/26, 8:37 AM
Emergency Equipment
Status Code Description
Fall 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Back exit
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign and egress lights combo that
the required load for a duration of not less than 90 minutes. }ailed to illuminate during inspection
Fire Service Features
5'.atns Code Description
Fail 509.2-Equipment access.
Approved access shall be provided and maintained for all fire Location:Basement-Gas utility
protection system equipment to permit immediate safe Comments:Remove storage obstructing clear path of access to gas
operation and maintenance of such equipment.Storage,trash meter utility
and other materials or objects shall not be placed or kept in valves and maintain no storage within 36"of utility
such a manner that would prevent such equipment from controls.
being readily accessible.
GENERATED ON 6/24/20,9:37 MI
2 OF 6
Electrical Safety
S ,n s Code Description
Fail 603.2 - Abatement of unsafe conditions and electrical
Ox hazards. Location: Above drop ceiling - Back exit hallway
Identified electrical hazards shall be abated. Identified Comments: Per Electrical Inspector, Tim Moyer: Recessed light
hazardous electrical conditions in permanent wiring shall be fixture above ceiling installed non-compliant to electrical code
brought to the attention of the responsible code official. standards shall be removed with wiring capped or removed.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
APS
~
2
11
s ar at �c
Fail 603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location: Basement - "Green Room"
prohibited. Approved covers shall be provided for all switch Comments: Provide missing electrical junction box cover above N.
and electrical outlet boxes.
Fail 603.4.1 - Labeling.
ODoors into electrical control panel rooms shall be marked Location: Basement- "Green Room"
with a plainly visible and legible sign stating "ELECTRICAL Comments: Provide permanent approved signage on door indicating
ROOM" or similar approved wording. The disconnecting electrical panel inside room. Laminated paper will not be accepted.
means for each service, feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident. Where buildings or structures are supplied by more
than one power source, markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
Fail 603.6 - Extension cords.
OExtension cords and flexible cordsshall not be a substitute Location: Claw machine
for permanent wiring and shall be listed and labeled in Comments: Remove extension cord plugged to machine, extension
accordance with UL 817. Extension cords and flexible cord shall not to be used as substitute for permanent wiring.
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 6/24/26, 8:37 AM 3 OF 6
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Above ceiling-Back exit hallway
for permanent wiring and shall be listed and labeled in Comments:Flexible wiring shall not be located in concealed spaces
accordance with UL 817.Extension cords and flexible (above ceilin
cordsshall not be affixed to structures,extended through g,in walls,below flooring).Cords found plugged to light
fixture and adapter shall be permanently removed from above ceiling.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
t
3:01
F ' •
f
Fire Resistant Construction Maintenance
Status Cc:''' Description
Fail 704.1-Maintaining protection.
0 Where required when the building was originally constructed, Location:Office&back exit hallway
materials and systems used to protect joints and voids in the
Comments:Replace all missing ceiling tiles
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
GENERATED ON 6/24/26, 8:37 AM 4 OF 6
Additional Codes
S at, Coos• Description
Fail 807.3-Acceptance criteria and reports.
Where required to exhibit improved fire performance, Location:Stage
curtains,draperies,fabric hangings and other similar Comments:Provide documentation of curtains in compliance with
combustible decorative materials suspended from walls or code requirements or remove from usage.
ceilings shall be tested by an approved agency and meet the
flame propagation performance criteria of Test Method 1 or
Test Method 2,as appropriate,of NFPA 701 or exhibit a
maximum rate of heat release of 100 kW when tested in
accordance with NFPA 289,using the 20 kW ignition source.
Reports of test results shall be prepared in accordance with
the test method used and furnished to the fire code official
upon request.
Portable Fire Extingusihers
Status Code Description
Fail 906.2-General requirements.
Ux Portable fire extinguishers shall be selected,installed and Location:All extinguishers
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to all extinguishers,last recorded
Exceptions:1.The distance of travel to reach an extinguisher service completed July 2024.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 6/24/28, 8:37 AM 5 OF 6
Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
N►A $80.00
Invoice Number Check Number Transaction Number
N►A N►A NIA
GENERATED ON 6/24/28, 8:37 AM 6 OF 6
OF WA PF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
0 06/30/2026 08/05/2026 2026-00000619 $80.00
• ' 11 U 1 •
> Y.=! O
7d1.3 �
Customer#: 24983 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
ZEMAN, JASON 715 Mulberry St
304 W. 4TH STREET WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed.
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION - 304 W. 4TH ST- 06/23/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE _ INVOICE# CHARGES
24983 06/30/2026 08/05/2026 2026-00000619 $80.00
Less Prepayment $0.00
Total Due—> $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.