HomeMy WebLinkAboutSTUDIO 13-304 W. 4TH ST 3t.s 2 w i Waterloo Fire Rescue 'MC Inspection Report WEIN 425 E.3rd Street Studio 13-304 W 4th ST,BLDG 304 W 4th St,Waterloo IA 50702 INSPECTION DETAILS Inspection Date Inspection Type �i Inspection Number 06123/2026 Annual Inspection(1Yr) a i ga ift 17104 Lead Inspector Shift Station Unit BRAD BALDWIN NIA NIA N/A Other Inspectors NIA SUMMARY OF INSPECTION 0 25 0 10 Q 40 Passed codes Failed codes NIA codes NEXT STEPS Please direct questions about your Inspection to: Reinspection Date BRAD BALDWIN 07/16/2026 brad.baldwin@waterloo-ia.org,3192914319 GENERAL NOTES BRAD BALDWIN-0612312026 @ 14:34 •$80 annual inspection fee BRAD BALDWIN-06123/2026 @ 14:34 •Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224 BRAD BALDWIN-06123/2026 @ 14:34 •Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards corrected BRAD BALDWIN-06123/2026 @ 14:34 •If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re- inspection fees start at$100,then$150,and$200 for all subsequent re-inspections. SIGNATURES Contact signature Inspector signature No signature Report completed post inspection Jason Zeman(2025) Date: BRAD BALDWIN 06/24/2026 CHECKLISTS 1 OF 6 GENERATED ON 6/24/26, 8:37 AM Emergency Equipment Status Code Description Fall 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required Location:Back exit in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign and egress lights combo that the required load for a duration of not less than 90 minutes. }ailed to illuminate during inspection Fire Service Features 5'.atns Code Description Fail 509.2-Equipment access. Approved access shall be provided and maintained for all fire Location:Basement-Gas utility protection system equipment to permit immediate safe Comments:Remove storage obstructing clear path of access to gas operation and maintenance of such equipment.Storage,trash meter utility and other materials or objects shall not be placed or kept in valves and maintain no storage within 36"of utility such a manner that would prevent such equipment from controls. being readily accessible. GENERATED ON 6/24/20,9:37 MI 2 OF 6 Electrical Safety S ,n s Code Description Fail 603.2 - Abatement of unsafe conditions and electrical Ox hazards. Location: Above drop ceiling - Back exit hallway Identified electrical hazards shall be abated. Identified Comments: Per Electrical Inspector, Tim Moyer: Recessed light hazardous electrical conditions in permanent wiring shall be fixture above ceiling installed non-compliant to electrical code brought to the attention of the responsible code official. standards shall be removed with wiring capped or removed. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes Conditions that constitute an electrical shock or fire hazard shall be abated not be used. APS ~ 2 11 s ar at �c Fail 603.2.2 - Unapproved conditionsOpen electrical terminations. Open junction boxes and open-wiring splices shall be Location: Basement - "Green Room" prohibited. Approved covers shall be provided for all switch Comments: Provide missing electrical junction box cover above N. and electrical outlet boxes. Fail 603.4.1 - Labeling. ODoors into electrical control panel rooms shall be marked Location: Basement- "Green Room" with a plainly visible and legible sign stating "ELECTRICAL Comments: Provide permanent approved signage on door indicating ROOM" or similar approved wording. The disconnecting electrical panel inside room. Laminated paper will not be accepted. means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. Where buildings or structures are supplied by more than one power source, markings shall be provided at each service equipment location and at all interconnected electric power production sources identifying all electric power sources at the premises in accordance with NFPA 70. Fail 603.6 - Extension cords. OExtension cords and flexible cordsshall not be a substitute Location: Claw machine for permanent wiring and shall be listed and labeled in Comments: Remove extension cord plugged to machine, extension accordance with UL 817. Extension cords and flexible cord shall not to be used as substitute for permanent wiring. cordsshall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. Extension cords marked for indoor use shall not be used outdoors. GENERATED ON 6/24/26, 8:37 AM 3 OF 6 Fail 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute Location:Above ceiling-Back exit hallway for permanent wiring and shall be listed and labeled in Comments:Flexible wiring shall not be located in concealed spaces accordance with UL 817.Extension cords and flexible (above ceilin cordsshall not be affixed to structures,extended through g,in walls,below flooring).Cords found plugged to light fixture and adapter shall be permanently removed from above ceiling. walls,ceilings or floors,or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact.Extension cords shall be used only with portable appliances.Extension cords marked for indoor use shall not be used outdoors. t 3:01 F ' • f Fire Resistant Construction Maintenance Status Cc:''' Description Fail 704.1-Maintaining protection. 0 Where required when the building was originally constructed, Location:Office&back exit hallway materials and systems used to protect joints and voids in the Comments:Replace all missing ceiling tiles following locations shall be maintained.The materials and systems shall be securely attached to or bonded to the adjacent construction,without openings visible through the construction.1.Joints in or between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.Unprotected joints and voids do not need to be protected where such joints and voids were not required to be protected when the building was originally constructed.Where the system design number is known,the system shall be inspected to the listing criteria and manufacturer's installation instructions. GENERATED ON 6/24/26, 8:37 AM 4 OF 6 Additional Codes S at, Coos• Description Fail 807.3-Acceptance criteria and reports. Where required to exhibit improved fire performance, Location:Stage curtains,draperies,fabric hangings and other similar Comments:Provide documentation of curtains in compliance with combustible decorative materials suspended from walls or code requirements or remove from usage. ceilings shall be tested by an approved agency and meet the flame propagation performance criteria of Test Method 1 or Test Method 2,as appropriate,of NFPA 701 or exhibit a maximum rate of heat release of 100 kW when tested in accordance with NFPA 289,using the 20 kW ignition source. Reports of test results shall be prepared in accordance with the test method used and furnished to the fire code official upon request. Portable Fire Extingusihers Status Code Description Fail 906.2-General requirements. Ux Portable fire extinguishers shall be selected,installed and Location:All extinguishers maintained in accordance with this section and NFPA 10. Comments:Provide annual service to all extinguishers,last recorded Exceptions:1.The distance of travel to reach an extinguisher service completed July 2024. shall not apply to the spectator seating portions of Group A-5 occupancies.2.Thirty-day inspections shall not be required and maintenance shall be allowed to be once every 3 years for dry-chemical or halogenated agent portable fire extinguishers that are supervised by a listed and approved electronic monitoring device,provided that all of the following conditions are met:2.1.Electronic monitoring shall confirm that extinguishers are properly positioned,properly charged and unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a building or cabinet in a noncorrosive environment. 2.4.Electronic monitoring devices and supervisory circuits shall be tested every 3 years when extinguisher maintenance is performed.2.5.A written log of required hydrostatic test dates for extinguishers shall be maintained by the owner to verify that hydrostatic tests are conducted at the frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be permitted to be located at staff locations. GENERATED ON 6/24/28, 8:37 AM 5 OF 6 Statement of Fees FEE Invoice Date Inspection Fee Date Paid Amount Paid N►A $80.00 Invoice Number Check Number Transaction Number N►A N►A NIA GENERATED ON 6/24/28, 8:37 AM 6 OF 6 OF WA PF INVOICE DATE DUE DATE INVOICE# TOTAL DUE 0 06/30/2026 08/05/2026 2026-00000619 $80.00 • ' 11 U 1 • > Y.=! O 7d1.3 � Customer#: 24983 Please Make Check Payable and Remit To: City of Waterloo ATTN: City Clerk/Accounts Receivable ZEMAN, JASON 715 Mulberry St 304 W. 4TH STREET WATERLOO, IA 50703 WATERLOO, IA 50702 Amount Enclosed. DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT KEEP THIS PORTION FOR YOUR RECORDS COMMERCIAL FIRE INSPECTION - 304 W. 4TH ST- 06/23/2026 FOR BILLING INQUIRY: (319)291-4323 Description Total Price INSPECTION 2,000 $70.00 OCCUPANCY FEE $10.00 CUSTOMER# BILLING DATE DUE DATE _ INVOICE# CHARGES 24983 06/30/2026 08/05/2026 2026-00000619 $80.00 Less Prepayment $0.00 Total Due—> $80.00 City of Waterloo Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of Administrative Services Offset Program if not paid in full within ninety days.