COMMERCIAL FIRE INSPECTION- 1850 W RIDGEWAY AVE STE FOR BILLING INQUIRY: (319)291-4323
3-07/14/202
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23105 07/15/2026 08/19/2026 2027-00000001 $80.00
Less Prepayment $0.00
Total Due-* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
tact Inspection Report 425 E.3rd Street
Bankers Life-1850 W Ridgeway AVE,BLDG 1850 W Ridgeway Ave-STE 3,
Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type 7 ^,,�r Inspection Number
07114/2026 Annual Inspection(1Yr) /1 C4-5 f 11644
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
041 07 @26
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 0811112026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-0711412026 @ 13:42
•$80 annual inspection fee
BRAD BALDWIN-07114/2026 @ 13:42
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-07114/2026 @ 13:42
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completedeelpost ostinspection
Summer Mast Date: BRAD BALDWIN 07/1412026
CHECKLISTS
General Housekeeping
Status Code Description
Fail 305.1-Clearance from ignition sources.
V Clearance between ignition sources,such as luminaires, Location:Electrical room
heaters,flame-producing devices and combustible materials, Comments:Remove storage from within 36"of water heater.
shall be maintained in an approved manner.
GENERATED ON 7/14/26, 1:45 PM 1 OF 5
Electrical Safety
5,.... Code
Description
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Lorie's office
Identified electrical hazards shall be abated.Identified Comments:Replace damaged(burnt)outlet.
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
r
4 3'
'1"
-.
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
{ Open junction boxes and open-wiring splices shall be Location:Electrical room
prohibited.Approved covers shall be provided for all switch
and electrical outlet boxes. Comments:Replace missing light switch cover
GENERATED ON 7/14/26, 1:45 PM
2 OF 5
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Electrical room
equipment shall be provided in accordance with Section Comments:Remove storage within 36"of electric panels.Maintain
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or clear path of access to panels at all times.
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
Ik°t F'
1. a ,
T ,-
q++' y\ i ,, ti +
4 \ y. I ftr
11 /
' 1'= , f
/ 11 , '
\1111
i4
WA
3 OF 5
GENERATED ON 7/14/26, 1:45 PM
Fail 603.5.2-Application and usePower supply.
Relocatable power taps and current taps shall be directly Location:Electric room-below IT rack
connected to a permanently installed receptacle.Exceptions:
Comments:Power strip daisy chained to another and hanging by
1.Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy,not more than five wires shall beto corrected.Power strip approved to plug directly to
relocatable power taps shall be permitted to be connected back-up battery device.
together or connected to an extension cord for temporary use
to supply power to electronic equipment.2.Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
A\l'.. . 101 ilfit i /,
iftli
1 . '' 4
Mfg
' ,
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Justin Batter's desk
for permanent wiring and shall be listed and labeled in
Comments:Remove extension cord for power strip.Strip shall plug
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through directly to a wall outlet.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Additional Codes
Status Code Description
Fail 603.9.1-Listed and labeled.
Ox Only listed and labeled portable,electric space heaters shall Location:Lucas Johansen's office
be used.
Comments:Provide documentation of commercially listed space
heater or remove from building.