COMMERCIAL FIRE INSPECTION- 1830 E. SHAULIS RD- FOR BILLING INQUIRY: (319)291-4323
07/07/2026
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13948 07/15/2026 08/19/2026 2027-00000019 $80.00
Less Prepayment _ $0.00
Total Due-+ $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
t k Inspection Report 425E.3rd Street
<,k South Hills Golf Course-1830 E Shaulis RD,BLDG 1830 E Shaulis Rd,Waterloo IA
50701
INSPECTION DETAILS
Inspection Date Inspection Type �� Inspection Number
07/07/2026 Annual Inspection(1Yr) _ 13 q� j �V,� 16531
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
030 07 ® 38
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
08/03/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-07107/2026 @ 13:50
•S80 annual inspection fee
BRAD BALDWIN-0710712026 @ 13:50
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-07/0712026 @ 13:50
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and S200 for all subsequent re-inspections.
BRAD BALDWIN-07107/2026 @ 13:50
Inspector did not gain access to north parking lot accessory building during 7/7126 inspection.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
JB Date: BRAD BALDWIN 07/09/2026
CHECKLISTS
GENERATED ON 7/9/26, 2:29 PM 1. OF 6
Additional Codes
Code Description
Fail 1010.2.4-Locks and latches.
Locks and latches shall be permitted to prevent operation of Location:Banquet room
doors where any of the following exist:1.Places of detention Comments:Permanent approved signage shall be installed to(east)
or restraint.2.In Group I-1,Condition 2 and Group 1-2 exit door stating,"THIS DOOR SHALL REMAIN UNLOCKED DURING
occupancies where the clinical needs of persons receiving BUSINESS HOURS"
care require containment or where persons receiving care
pose a security threat,provided that all clinical staff can
readily unlock doors at all times,and all such locks are keyed
to keys carried by all clinical staff at all times or all clinical
staff have the codes or other means necessary to operate the
locks at all times.2.3.In buildings in occupancy Group A
having an occupant load of 300 or less,Groups B,F,M and S,
and in places of religious worship,the main door or doors are
permitted to be equipped with key-operated locking devices
from the egress side provided:2.1.3.1.The locking device is
readily distinguishable as locked.2.2.3.2.A readily visible
durable sign is posted on the egress side on or adjacent to
the door stating:"THIS DOOR TO REMAIN UNLOCKED WHEN
THIS SPACE IS OCCUPIED."The sign shall be in letters 1 inch
(25 mm)high on a contrasting background.2.3.3.3.The use
of the key-operated locking device is revocable by the fire
code official for due cause.3.4.Where egress doors are used
in pairs,approved automatic flush bolts shall be permitted to
be used,provided that the door leaf having the automatic
flush bolts does not have a doorknob or surface-mounted
hardware.4.5.Doors from individual dwelling or sleeping
units of Group R occupancies having an occupant load of 10
or less are permitted to be equipped with a night latch,dead
bolt or security chain,provided such devices are openable
from the inside without the use of a key or tool.5.6.Fire
doors after the minimum elevated temperature has disabled
the unlatching mechanism in accordance with listed fire door
test procedures.6.7.Doors serving roofs not intended to be
occupied shall be permitted to be locked,preventing entry to
the building from the roof.8.Other than egress courts,where
occupants must egress from an exterior space through the
building for means of egress,exit access doors shall be
permitted to be equipped with an approved locking device
where installed and operated in accordance with all of the
following:8.1.The maximum occupant load shall be posted
where required by Section 1004.9.Such sign shall be
permanently affixed inside the building and shall be posted in
a conspicuous space near all the exit access doorways.8.2.A
weatherproof telephone or two-way communication system
installed in accordance with Sections 1009.8.1 and 1009.8.2
shall be located adjacent to not less than one required exit
access door on the exterior side.8.3.The egress door locking
device is readily distinguishable as locked and shall be a key-
operated locking device.8.4.A clear window or glazed door
opening,not less than 5 square feet(0.46 m2)in area,shall
be provided at each exit access door to determine if there are
occupants using the outdoor area.8.5.A readily visible
durable sign shall be posted on the interior side on or
adjacent to each locked required exit access door serving the
exterior area stating:"THIS DOOR TO REMAIN UNLOCKED
WHEN THE OUTDOOR AREA IS OCCUPIED."The letters on
the sign shall be not less than 1 inch(25.4 mm)high on a
contrasting background.8.6.The occupant load of the
occupied exterior area shall not exceed 300 occupants in
accordance with Section 1004.9.Locking devices are
permitted on doors to balconies,decks or other exterior
spaces serving individual dwelling or sleeping units.
10.Locking devices are permitted on doors to balconies,
decks or other exterior spaces of 250 square feet(23.23
m2)or less,serving a private office space.
GENERATED ON 7/9/26, 2:29 PM 2 OF 6
Fail 5807.2.1-Securing containers.
Containers,cylinders and tanks shall be secured in Location:Office
accordance with Section 5303.5.3. Comments:Secure compressed gas cylinders with chain to avoid tip
over.
General Housekeeping
Stan.: Ccds Description
Fail 305.1-Clearance from ignition sources.
Clearance between ignition sources,such as luminaires, Location:Water heater
heaters,flame-producing devices and combustible materials, Comments:Remove storage within 36"of appliance.Maintain proper
shall be maintained in an approved manner. clearances at all times
Fire Service Features
_- Cod2 Description
Fail 505.1-Address identification.
New and existing buildings shall be provided with approved Location:Front of building
address identification.The address identification shall be Comments:Permanent address identification numbers shall be
legible and placed in a position that is visible from the street installed in contrast with the building visible from the road to comply
or road fronting the property.Address identification with code standards.
characters shall contrast with their background.Address
numbers shall be Arabic numbers or alphabetical letters.
Numbers shall not be spelled out.Each character shall be not
less than 4 inches(102 mm)high with a minimum stroke
width of 1/2 inch(12.7 mm).Where required by the fire code
official,address identification shall be provided in additional
approved locations to facilitate emergency response.Where
access is by means of a private road and the building cannot
be viewed from the public way,a monument,pole or other
sign or means shall be used to identify the structure.Address
identification shall be maintained.
GENERATED ON 7/9/26, 2:29 PM 3 OF 6
Electrical Safety
S;<o,s Code Description
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Golf cart building
prohibited.Approved covers shall be provided for all switch Comments:Provide cover to box on ceiling to avoid open wire
and electrical outlet boxes. connections.
r
i t M
R �i
ice,
GENERATED ON 7/9/26, 2:29 PM 4 OF 6
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Electrical room-Pro Shop
equipment shall be provided in accordance with Section Comments:Remove storage within 36"of electrical panels.Maintain
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or proper clearances at all times.
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
JJ
pM L
art.
E
1
t Ni
fear
Fail 603.4.1-Labeling.
Doors into electrical control panel rooms shall be marked Location:Electrical room-Pro Shop
with a plainly visible and legible sign stating"ELECTRICAL Comments:Provide approved permanent signage on door to electric
ROOM"or similar approved wording.The disconnecting panels.Laminated paper will not be accepted.
means for each service,feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident.Where buildings or structures are supplied by more
than one power source,markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
GENERATED ON 7/9/26, 2:29 PM 5 OF 6