COMMERCIAL FIRE INSPECTION - 875 FISHER DR-07/06/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23710 07/15/2026 08/19/2026 2027-00000010 $80.00
Less Prepayment $0.00
Total Due -+ $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
4 Inspection Report 425 E.3rd Street
Kwik Star-875 Fisher DR,BLDG 875 Fisher Dr,Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
0710612026 Annual Inspection(1Yr) /0 ��/- 17404
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A N/A NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 42 0 15 @ 27
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 08/03/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-07/0612026 @ 15:10
•$80 annual inspection fee
BRAD BALDWIN-0710612026 @ 15:10
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-0710612026 @ 15:10
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-07/0612026 @ 15:10
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-0710912026 @ 08:11
Fire Marshall Weliver approved the storage of fueled equipment(power washer,snow blower)in"Utility Room/Water Softener Room".Equipment shall
maintained proper clearances from fuel fired appliances and all combustibles.
SIGNATURES
Contact signature Inspector signature
No signature
Report completedeelpost stinspection
Alicia 2025-store leader Date: BRAD BALDWIN 07/09/2026
CHECKLISTS
GENERATED ON 7/9/26, 8:17 AM 1 OF 7
Means of Egress
S.a Code Description
Fail 1010.1.3-Door opening force Forces to unlatch and open
doors. Location:Utility room-East exit door
The force for pushing or pulling open interior swinging Comments:Repair or replace door to open with less than 15lbs of
egress doors,other than fire doors,shall not exceed 5 force.Replacement of door requires permit obtained and inspection.
pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected toa 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:LWhere door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
GENERATED ON 7/9/26, 8:17 AM 2 OF 7
Additional Codes
Code Description
Fail 102.4-Application of building code.
The design and construction of new structures shall comply Location:Roof permit
with the International Building Code,and any alterations, Comments:Contractor shall obtain inspection of work when
additions,changes in use or changes in structures required complete,currently work in progress.
by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Fail 102.4-Application of building code.
The design and construction of new structures shall comply Location:Electric permit-Carwash
with the International Building Code,and any alterations, Comments:Contractor(Tatroe Electric)shall obtain inspection when
additions,changes in use or changes in structures required work complete,
by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Fail 2303.2-Emergency disconnect switches.
An approved emergency disconnect switch shall be provided Location:Behind register counter
at an approved location to stop the transfer of fuel to the fuel Comments:Provide identifying signage in approved location for
dispensers in the event of a fuel spill or other emergency.The disconnect switch.
emergency disconnect switch for exterior fuel dispensers
shall be provided with ready access and shall be located
within 100 feet(30 480 mm)of,but not less than 20 feet(6096
mm)from,the fuel dispensers.For interior fuel-dispensing
operations,the emergency disconnect switch shall be
provided with ready access and be installed at an approved
location.Such devices shall be distinctly labeled as:
"EMERGENCY FUEL SHUTOFF."Signs shall be
provided in approved locations.
Fail 2305.2-Equipment maintenance and inspection.
Motor fuel-dispensing facility equipment shall be maintained Location:Fuel pump station#5
in proper working order at all times in accordance with Comments:91 octane fuel pump currently out of service.Repairs
Sections 2305.2.1 through 2305.2.5. shall be made to operate in proper working order.
Fail 2305.2-Equipment maintenance and inspection.
Motor fuel-dispensing facility equipment shall be maintained Location:Fuel pump station#10
in proper working order at all times in accordance with Comments:87 octane fuel pump currently out of service.Repairs
Sections 2305.2.1 through 2305.2.5. shall be made to operate in proper working order.
Fail 2305.2-Equipment maintenance and inspection.
OMotor fuel-dispensing facility equipment shall be maintained Location:Fuel pump station#13
in proper working order at all times in accordance with Comments:All fuel pumps currently out of service.Repairs shall be
Sections 2305.2.1 through 2305.2.5. made to operate in proper working order.
Fail 313.1-General.
0 Fueled equipment including,but not limited to,motorcycles,
mopeds,lawn-care equipment,portable generators and
portable cooking equipment,shall not be stored,operated or
repaired within a building.Exceptions:1.Buildings or rooms
constructed for such use in accordance with the International
Building Code.2.Where allowed by Section 314.3.Storage of
equipment utilized for maintenance purposes is allowed in
approved locations where the aggregate fuel capacity of the
stored equipment does not exceed 10 gallons(38 L)and the
building is equipped throughout with an automatic sprinkler
system installed in accordance with Section 903.3.1.1.
GENERATED ON 7/9/26, 8:17 AM 3 OF 7
Emergency Equipment
Star Description
Fail 1203.2.15-Means of egress illumination.
C Emergency power shall be provided for means of egress Location:Front exit
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights on exit sign that failed to
illuminate during test.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Car wash-mechanical room
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights on exit sign that failed to
illuminate during test.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Above windshield wiper fluid shelving
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights,lights very dim when
tested.
General Housekeeping
Status Code Description
Fail 304.3.1-Spontaneous ignition.
Materials susceptible to spontaneous ignition,such as oily Location:Kitchen
rags,shall be stored in a listed disposal container.Contents
Comments:Provide listed container for disposal of oily rags.Provide
of such containers shall be removed and disposed of daily.
documentation of disposable wipes being used to inspector as
possible alternative,will verify with Fire Marshall if approved.
GENERATED ON 7/9/26, 8:17 AN 4 OF 7
Electrical Safety
S;atos code Description
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Kitchen
equipment shall be provided in accordance with Section Comments:Remove obstructions(including paperwork magnetized
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or to panel)to clear view of electric panels,maintain proper clearances
less,and Section 110.33 of NFPA 70 for electrical equipment at all times.
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
Aiwa
nIrth
3054,5__
uii J t,-�
5 OF
GENERATED ON 7/9/26, 9:17 AM
Portable Fire Extingusihers
Stz:�= Description
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:Car wash
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to extinguishers(2),currently
Exceptions:1.The distance of travel to reach an extinguisher past due.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:Utility room-Near water softeners
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to extinguisher,currently past
Exceptions:1.The distance of travel to reach an extinguisher due since June 2026
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.