COMMERCIAL FIRE INSPECTION-1850 W RIDGEWAY AVE#7- FOR BILLING INQUIRY: (319)291-4323
07/07/2026
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24039 07/15/2026 08/19/2026 2027-00000017 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
' Inspection Report
���Y' 425 E.3rd Street
Sidecar Coffee-1850 W Ridgeway AVE,BLDG 1850 W Ridgeway Ave-STE 7,
Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type J Inspection Number
0710712026 Annual Inspection(1Yr) a'-f'0q 4 11583
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
040 08 Q26
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 0811012026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-07107/2026 @ 13:53
•$80 annual inspection fee
BRAD BALDWIN-07I07/2026 @ 13:53
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-07/0712026 @ 13:53
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-07107/2026 @ 14:00
Fire extinguisher due annually serviced September 2026.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Andy Fuchtman Date: BRAD BALDWIN 07/07/2026
CHECKLISTS
1 OF 5
GENERATED ON 7/7/26, 2:09 PM
Emergency Equipment
Status Code Description
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Front exit
in Section 1013.6.3.The system shall be capable of powering
Comments:Repair or replace exit sign and egress lights combo that
the required load for a duration of not less than 90 minutes.
failed to illuminate during test.
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Back exit
in Section 1013.6.3.The system shall be capable of powering
Comments:Repair or replace exit sign and egress lights combo that
the required load for a duration of not less than 90 minutes.
failed to illuminate during test.
General Housekeeping
Status Code
Description
Fail 315.3.1-Ceiling clearance.
Storage shall be maintained 2 feet(610 mm)or more below Location:Storage closet
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches(457 mm)below sprinkler head deflectors in Comments:Remove storage within 18"below sprinkler head.
sprinklered areas of buildings.Exceptions:1.The 2-foot(610
mm)ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings.2.The 18-inch(457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1,903.3.1.2 or
903.3.1.3.
Fire Sprinkler System
S.:Cur Code
Description
Fail 903.3.3-Obstructed locations.
Automatic sprinklers shall be installed with regard to Location:Sprinkler system
obstructions that will delay activation or obstruct the water
Comments:Several sprinkler heads noted with dust/debris,carefully
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being clean all debris from heads.
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
OENEPATED ON 7/7/26, 2:06 PM
2 OF 5
Electrical Safety
S'e ,s Code Description
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Mechanical room
equipment shall be provided in accordance with Section Comments:Remove all storage within 36"from electric panels.
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or Maintain proper clearances at all times.
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
Il4.¢-
.--- - i I e
S e'
—3'
} 0
1
i • y 'kg
• go
{ A
f 1y
Fail 603.4.1-Labeling.
Doors into electrical control panel rooms shall be marked Location:Mechanical room
with a plainly visible and legible sign stating"ELECTRICAL Comments:Provide approved permanent signage"Electric Room"on
ROOM"or similar approved wording.The disconnecting door for firefighters access,laminated paper will not be accepted.
means for each service,feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident.Where buildings or structures are supplied by more
than one power source,markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
Fail 603.5.3-Installation.
Relocatable power tap cords shall not extend through walls, Location:Mechanical room
ceilings,floors,under doors or floor coverings,or be subject Comments:Power strip hanging by wires next to electric panel shall
to environmental or physical damage. be properly mounted to avoid hanging by wires
3 OF 5
GENERATED ON 7/7/26, 2:09 PM
Fail 603.6-Extension cords.
Ox Extension cords and flexible cordsshall not be a substitute Location:Front wall of store-Speaker near ceiling
for permanent wiring and shall be listed and labeled in
accordance with UL 817.Extension cords and flexible Comments:Flexible wiring shall not extend through concealed space
(above drop ceiling).Remove white cord to speaker from ceiling
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings, space.Exception:Low voltage wiring
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 7/7/26, 2:09 PM