HomeMy WebLinkAboutGREENHOUSE KITCHEN 1730 W. RIDGEWAY AV OF W A T4' INVOICE DATE DUE DATE INVOICE# TOTAL DUE
4,! 07/16/2026 08/20/2026 2027-00000025 $80.00
• ,
T T O
4S 7 v 11‘
Customer#: 23829 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
GREENHOUSE KITCHEN 715 Mulberry St
PO BOX 708 WATERLOO, IA 50703
CEDAR FALLS, IA 50613
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION- 1730 W. RIDGEWAY AVE FOR BILLING INQUIRY: (319)291-4323
#500-7/14/26
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23829 07/16/2026 08/20/2026 2027-00000025 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
tv Inspection Report
` 425 E.3rd Street
Greenhouse Kitchen-1730 W Ridgeway AVE,BLDG 1730 W Ridgeway Ave-STE
500,Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
07/14/2026 Annual Inspection(1Yr) (cBO"I(� �i�''}`ems 7865
Lead Inspector Shift Station l��/ Unit
BRAD BALDWIN N/A NIA N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
� 41 CD @26
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
08115/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-07/16/2026 @ 07:49
•$80 annual inspection fee
BRAD BALDWIN-07116/2026 @ 07:49
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-07116/2026 @ 07:49
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completedeelpost stinspection
Ryan Drewes-2026 Date: BRAD BALDWIN 07/16/2026
CHECKLISTS
GENERATED ON 7/16/26, 7:57 AM 1 OF 5
Emergency Equipment
Status Code Description
Fail 1203.2.15-Means of egress illumination.
OEmergency power shall be provided for means of egress Location:Above door to bathroom hallway
illumination in accordance with Sections 1008.3 and 1104.5.1, Comments:Repair or replace egress lights on exit sign that failed to
illuminate during test.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Dining area
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights(2)on exit sign that failed
to illuminate during test.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Men's bathroom
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights on exit sign that failed to
illuminate during test.Was not able to access women's bathroom
during 7114126 inspection,lights shall be tested and repaired if not
functioning properly
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Bathroom hallway
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights on exit sign that failed to
illuminate during test.
General Housekeeping
Status Code Description
Fail 304.3.1-Spontaneous ignition.
Ct Materials susceptible to spontaneous ignition,such as oily Location:Kitchen
rags,shall be stored in a listed disposal container.Contents Comments:Provide listed container with self closing lid for disposal
of such containers shall be removed and disposed of daily. of soiled rags(fats,oils or grease).See attachment.
g
0:
• f
GENERATED ON 7/16/26, 7:57 AM 2 OF 5
Fire Service Features
Status Code Dscrintion
Fail 505.1-Address identification.
New and existing buildings shall be provided with approved Location:Front of building
address identification.The address identification shall be Comments:"Suite 500"numbers shall be installed to comply with
legible and placed in a position that is visible from the street code requirements.Numbers shall be in contrast with the building
or road fronting the property.Address identification and easily visible from the road.
characters shall contrast with their background.Address
numbers shall be Arabic numbers or alphabetical letters.
Numbers shall not be spelled out.Each character shall be not
less than 4 inches(102 mm)high with a minimum stroke
width of 112 inch(12.7 mm).Where required by the fire code
official,address identification shall be provided in additional
approved locations to facilitate emergency response.Where
access is by means of a private road and the building cannot
be viewed from the public way,a monument,pole or other
sign or means shall be used to identify the structure.Address
identification shall be maintained.
Electrical Safety
Code Description
Fail 603.5.3-Installation.
Relocatable power tap cords shall not extend through walls, Location:Kitchen
ceilings,floors,under doors or floor coverings,or be subject Comments:Power stripshall be properly mounted or supported
to environmental or physical damage. P P Y to
avoid hanging by wires.
Fail 603.6-Extension cords.
0 Extension cords and flexible cordsshall not be a substitute Location:Menu TV
for permanent wiring and shall be listed and labeled in Comments:TV cord shall not pass through wall.If adding new outlet,
accordance with UL 817.Extension cords and flexible licensed electrical contractor shall obtain permit and inspection.
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 7/16/26, 7:57 AM 3 OF 5
Portable Fire Extingusihers
Status Cale Description
Fail 906.2-General requirements.
Portable lire extinguishers shall be selected,installed and Location:Extinguishers
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to all extinguishers,currently
Exceptions:1.The distance of travel to reach an extinguisher past due for service since Oct 2025.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10,3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
4 OF 5
GENERATED ON 7/16/28, 7:57 AM
`® Statement of Fees
FEE
p Invoice Date
Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number
Check Number Transaction Number
NIA
WA NIA
5 OF 5
GENERATED ON 7/16/26, 7:57 AM