COMMERCIAL INSPECTION- 3606 KIMBALL AVE- 6-23-23 FOR BILLING INQUIRY: (319)291-4323
Description -r , y I Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24129 07/18/2023 08/20/2023 2024-00000038 $80.00
Less Prepayment $0.00
Total Due—> $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
‘2,(1-
WATERLOO FIRE RESCUE
�p'iERtOO
INSPECTION REPORT
YOUNG MASSAGE,3602-36066 KIMBALL AVE,BLDG 3604 KIMBALL AVE-STE 3604 KIMBALL
AVE,WATERLOO IA 50701 424i0e
DETAILS
Inspection Date:06/23/2023 j Inspection Type:Annual Inspection(1Yr) Inspection Number: 10552 Shift: N/A Station: N/A i
Unit: N/A Lead Inspector:JEFF SIEBEL Other Inspectors: BROCK WELIVER
STATUS CODE DESCRIPTION
FAIL 1010.2.9-Panic and fire exit Swinging doors serving a Group H occupancy and swinging doors serving rooms or
hardware. spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be
provided with a latch or lock other than panic hardware or fire exit hardware.
Exceptions: 1.A main exit of a Group A occupancy shall be permitted to have locking
devices in accordance with Section 1010.2.4, Item 2 3.2.Doors provided with panic
hardware or fire exit hardware and serving a Group A or E occupancy shall be
permitted to be electrically locked in accordance with Section 1010.2.12 or 1010.2.11.
3. Exit access doors serving occupied exterior areas shall be permitted to be locked in
accordance with Section 1010.2.4, Item 8.4.Courtrooms shall be permitted to be
locked in accordance with Section 1010.2.13, Item 3. Electrical rooms with equipment
rated 1,200 amperes or more and over 6 feet(1829 mm)wide,and that contain
overcurrent devices,switching devices or control devices with exit or exit access
doors,shall be equipped with panic hardware or fire exit hardware.The doors shall
swing in the direction of egress travel.
Inspector:JEFF SIEBEL-Comments:remove thumb turn on back door with panic
hardware. No other lock permitted with panic hardware.
Location: back door
FAIL 102.3-Change of use or A change of occupancy shall not be made unless the use or occupancy is made to
occupancy. comply with the requirements of this code and the International Existing Building
Code. Exception:Where approved by the fire code official,a change of occupancy
shall be permitted without complying with the requirements of this code and the
International Existing Building Code,provided that the new or proposed use or
occupancy is less hazardous,based on life and fire risk,than the existing use or
occupancy.
Inspector:JEFF SIEBEL-Comments:This building is considered a business and is
classified as a business.It would require several safety updates to be considered an
"R"or residential building.Effective immediately no person shall live or sleep in
premises.
Location: Not Provided
Printed on 06/23/2023 @ 13:45
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 102.4-Application of building The design and construction of new structures shall comply with the International
code. Building Code,and any alterations,additions,changes in use or changes in
structures required by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Inspector:JEFF SIEBEL-Comments:Obtain permits and inspections for unpermitted
work on premises:A. Plumbing for new shower,waterlines and drainage B.Plumbing
for wash machine install C.Plumbing for new improperly installed water heater D.
Electrical for new power ran to washer and dryer.
Location: Not Provided
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments: Repair all exit/egress lights including 4 not
working today.
Location: main door and 3 to back door
FAIL 603.5-Relocatable power Multiplug adapters,such as cube adapters, unfused plug strips or any other device
taps and current not complying with NFPA 70 shall be prohibited.The construction and use of current
taps.Multiplug adapters. taps and relocatable taps shall be in accordance with NFPA 70 and this code.
Inspector:JEFF SIEBEL-Comments:Remove refrigerator and microwave plugs from
power strip.Each must plug directly into permanent wall outlet.
Location:back room being used for sleep and food
FAIL 603.5-Relocatable power Multiplug adapters,such as cube adapters,unfused plug strips or any other device
taps and current not complying with NFPA 70 shall be prohibited.The construction and use of current
taps.Multiplug adapters. taps and relocatable taps shall be in accordance with NFPA 70 and this code.
Inspector:JEFF SIEBEL-Comments:remove towel warmer from extension cord/power
strip.Must plug directly into permanent wall outlet.
Location:massage room
Printed on 06/23/2023 @ 13:45
Page 2 of 5
STATUS CODE DESCRIPTION
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings, nor shall such cords be subject to environmental
damage or physical impact. Extension cords shall be used only with portable
appliances. Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEFF SIEBEL-Comments:Remove extension cord
Location:behind front desk
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned, properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3, portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual service for fire extinguishers.
Location:upstairs and downstairs
GENERAL NOTES
JEFF SIEBEL-06/23/2023 @ 13:34
JEFF SIEBEL-06/23/2023 @ 13:35
•
JEFF SIEBEL-06/23/2023 @ 13:35
JEFF SIEBEL-06/23/2023 @ 13:36
JEFF SIEBEL-06/23/2023 @ 13:37
Printed on 06/23/2023 @ 13:45
Page 3 of 5
GENERAL NOTES
JEFF SIEBEL-06/23/2023 @ 13:37
JEFF SIEBEL-06/23/2023 @ 13:37
JEFF SIEBEL-06/23/2023 @ 13:38
JEFF SIEBEL-06/23/2023 @ 13:38
JEFF SIEBEL-06/23/2023 @ 13:38
JEFF SIEBEL-06/23/2023 @ 13:39
JEFF SIEBEL-06/23/2023 @ 13:39
JEFF SIEBEL-06/23/2023 @ 13:40
JEFF SIEBEL-06/23/2023 @ 13:44 No sleeping in building allowed
JEFF SIEBEL-06/23/2023 @ 13:44 annual inspection$80
REINSPECTION DATE
07/13/2023
CONTACT SIGNATURE
Abdulah Skrgic P 11 L e ✓c
Signed on:06/23/2023 @ 13:42 I
Printed on 06/23/2023 C.13:45
Page 4 of 5
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:06/23/2023 @ 13:23
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
•
Printed on 06/23/2023 @ 13:45