COMMERCIAL INSPECTION - 1117 MAXHELEN BLVD - 5-16-23 FOR BILLING INQUIRY: (319)291-4323
Description I Total
e �. Price
ce
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24126 07/18/2023 08/20/2023 2024-00000042 $100.00
Less Prepayment $0.00
Total Due $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
►,.
. ; `magi
WATERLOO FIRE RESCUE IRO V
w
„ocutto,
INSPECTION REPORT `r
Z�SOUTH HILLS SENIOR LIVING,1117 MAXHELEN BLVD,BLDG 1117 MAXHELEN BLVD, ea '
‘" ozzitio
, f
WATERLOO IA S0702 .
DETAILS
Inspection Date:05/16/2023 Inspection Type: Residential Common Areas Inspection I Inspection Number: 10264 I Shift: N/A I
Station: N/A I Unit: N/A Lead Inspector:JEREMIAH VANDYKE I Other Inspectors: N/A I Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1203.4-Maintenance. Emergency and standby power systems shall be maintained in accordance with NFPA
110 and NFPA 111 such that the system is capable of supplying service within the time
specified for the type and duration required.
Inspector:JEREMIAH VANDYKE-Comments:Generator for building and life safety
systems.
Location: Not Provided
FAIL 1203.4.2-Schedule. Inspection,testing and maintenance of emergency and standby power systems shall
be in accordance with an approved schedule established upon completion and
approval of the system installation.
Inspector:JEREMIAH VANDYKE-Comments:Generator for building and life safety
systems.
Location: Not Provided
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEREMIAH VANDYKE-Comments:Generator for building and life safety
systems.
Location: Not Provided
Printed on 05/177/2023 @ 09:01
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 1203.4.4-Switch Emergency and standby power system transfer switches shall be included in the
maintenance. inspection,testing and maintenance schedule required by Section 1203.4.2.Transfer
switches shall be maintained free from accumulated dust and dirt.Inspection shall
include examination of the transfer switch contacts for evidence of deterioration.
When evidence of contact deterioration is detected,the contacts shall be replaced in
accordance with the transfer switch manufacturer's instructions.
Inspector:JEREMIAH VANDYKE-Comments:Generator for building and life safety
systems.
Location: Not Provided
FAIL 1203.6-Supervision of Routine maintenance, inspection and operational testing shall be overseen by a
maintenance and testing. properly instructed individual.
Inspector:JEREMIAH VANDYKE-Comments:Generator for building and life safety
systems.
Location: Not Provided
FAIL 509.1 -Identification. Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements fire protection systems shall be
identified for the use of the fire department.Approved signs required to identify fire
protection system equipment and equipment location shall be constructed of
durable materials,permanently installed and readily visible.
Inspector:JEREMIAH VANDYKE-Comments:Signage stating'Sprinkler Riser Room"
constructed of durable materials,permanently installed and readily visible.
Location: 1st floor mechanical room door.
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEREMIAH VANDYKE-Comments: Record log of cleaning with date and
name for all clothes dryer systems.
Location: Not Provided
Printed on 05/17/2023 @ 09:01
Page 2 of 5
STATUS CODE DESCRIPTION
FAIL 703.1 -Maintaining Materials and firestop systems used to protect membrane and through penetrations
protection. in fire-resistance-rated construction and construction installed to resist the passage
of smoke shall be maintained.The materials and firestop systems shall be securely
attached to or bonded to the construction being penetrated with no openings visible
through or into the cavity of the construction.Where the system design number is
known,the system shall be inspected to the listing criteria and manufacturer's
installation instructions.
Inspector:JEREMIAH VANDYKE-Comments:Holes to be repaired with fire resistance
material.Currently working on leak.
Location: Near room#205 House keeping room.
FAIL 704.1 -Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEREMIAH VANDYKE-Comments:Ceiling tiles need to be replaced.
Location: Located in kitchen.
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEREMIAH VANDYKE-Comments:Door stops not allowed on fire rated
doors. Door did not close and latch due to catching on carpet.
Location:2nd floor laundry residents laundry room.
Printed on 05/17/2023 @ 09:01
Page 3 of 5
STATUS CODE DESCRIPTION
FAIL 901.6-Inspection,testing and Fire detection and alarm systems,emergency alarm systems,gas detection systems,
maintenance. fire-extinguishing systems,mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained in an operative condition
at all times,and shall be replaced or repaired where defective. Nonrequired fire
protection and life safety systems and equipment shall be inspected,tested and
maintained or removed in accordance with Section 901.8.
Inspector:JEREMIAH VANDYKE-Comments:According to Compliance engine there
are 2 deficiencies called out by Sprinkler Contractor on 7/29/2022.Owner will contact
sprinkler contractor to if they have been addressed. 1.Deficiency Found by sprinkler
contractor:Answer:4"main on dry system in attic has pipe with pinhole leaks that
are now patched and should be replaced 3rd floor north west access 7'-0"pipe
overall with 2"welds back to back at 6"off end of pipe and 0-11"piece 3rd floor north
east access 4"pipe overall lengths 9'-3"10'-6"2'-4"2.Deficiency Found by sprinkler
contractor:Answer:5-chrome pendent heads in kitchen area have corrosion at the
seat 155 degree chrome F1 semi recessed pendent could change them to 200
degrees due to them being in the kitchen A Deficiency Notice was sent on 08/15/2022
Location: Not Provided
FAIL 99999-Inspection Outcome Did the inspection pass or fail?
Inspector:JEREMIAH VANDYKE-Comments: None
Location: Not Provided
GENERAL NOTES
JEREMIAH VANDYKE-05/17/2023 @ 08:09 04/06/2023 S-Kitchen Hood Suppression SUPERIOR FIRE PROTECTION EQUIPMENT
Reviewed Compliant
JEREMIAH VANDYKE-05/17/2023 @ 08:09 04/06/2023 S-(Annual)Fire Alarm HAWKEYE ALARM Reviewed Compliant
JEREMIAH VANDYKE-05/17/2023 @ 08:09 07/29/2022 S-(Annual)Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS,INC.
Reviewed Deficient
JEREMIAH VANDYKE-05/17/2023 @ 08:10 05/25/2022 L-(Annual)Kitchen Exhaust HARRIS CLEANING SERVICE AND AH Reviewed
Compliant
JEREMIAH VANDYKE-05/16/2023 @ 15:42 Fire Extinguishers serviced/compliant by Superior Fire in April 2023.
Printed on 05/17/2023 @ 09:01
Page 4 of 5
s q
•
GENERAL NOTES
JEREMIAH VANDYKE-05/17/2023 @ 08:58 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-05/17/2023 @ 08:58 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-05/17/2023 @ 08:59 Inspection Fee=$100.00
REINSPECTION DATE
06/16/2023
CONTACT SIGNATURE
Dalt Snodgrass Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:05/17/2023 @ 08:57
LN