COMMERCIAL INSPECTION- 603 S HACKETT RD - 6-30-23 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24136 07/18/2023 08/20/2023 2024-00000036 $80.00
Less Prepayment $0.00
Total Due-+ $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
\'\c?s'
WATERLOO FIRE RESCUE �ptE.
n (.0
INSPECTION REPORT aLl ezo
603 S HACKETT RD,WATERLOO/A 50701 U `" 6 '
DETAILS
Inspection Date:06/30/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number: 10600 Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1103.8.1 -Where required. Existing Group I-1 and R occupancies shall be provided with single-station smoke
alarms in accordance with Section 907.2.11. Interconnection and power sources shall
be in accordance with Sections 1103.8.2 and 1103.8.3,respectively. Exceptions:
1.Where the code that was in effect at the time of construction required smoke
alarms and smoke alarms complying with those requirements are already provided.
2.Where smoke alarms have been installed in occupancies and dwellings that were
not required to have them at the time of construction,additional smoke alarms shall
not be required provided that the existing smoke alarms comply with requirements
that were in effect at the time of installation.3.Where smoke detectors connected to
a fire alarm system have been installed as a substitute for smoke alarms.
Inspector:JEREMIAH VANDYKE-Comments: Missing smoke alarm. Please check all
+£ tenant rooms that smoke alarms are properly installed.
Location: Bedroom D
FAIL 506.1 -Where required. Where access to or within a structure or an area is restricted because of secured
openings or where immediate access is necessary for life-saving or fire-fighting
purposes,the fire code official is authorized to require a key box to be installed in an
approved location.The key box shall be of an approved type listed in accordance with
UL 1037,and shall contain keys to gain necessary access as required by the fire code
official.
Inspector:JEREMIAH VANDYKE-Comments:Knox box must be ordered by building
owner.Can be ordered at Knoxbox.com.Please call if having issues with ordering.
Location: Not Provided
FAIL 506.2-Key box maintenance. The operator of the building shall immediately notify the fire code official and provide
the new key where a lock is changed or rekeyed.The key to such lock shall be secured
in the key box.
Inspector:JEREMIAH VANDYKE-Comments:Master key needed for access into
building and all rooms inside including office,sleeping quarters,and mechanical
rooms.
Location: Not Provided
Printed on 06/30/2023 @ 13:52
Page 1 of 6
STATUS CODE DESCRIPTION
FAIL 509.1 -Identification. Fire protection equipment shall be identified in an approved manner.Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements fire protection systems shall be
identified for the use of the fire department.Approved signs required to identify fire
protection system equipment and equipment location shall be constructed of
durable materials,permanently installed and readily visible.
Inspector:JEREMIAH VANDYKE-Comments:Room containing main electrical panel
and sprinkler riser must state"Main Electrical Panel-Sprinkler Riser Room".
Location: Room containing main sprinkler riser.
FAIL 509.1 -Identification. Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements fire protection systems shall be
identified for the use of the fire department.Approved signs required to identify fire
protection system equipment and equipment location shall be constructed of
durable materials, permanently installed and readily visible.
Inspector:JEREMIAH VANDYKE-Comments:Signage needed on office door stating
"FACP".
Location: Main front office.
FAIL 603.4.1 -Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and
legible sign stating"ELECTRICAL ROOM"or similar approved wording.The
disconnecting means for each service,feeder or branch circuit originating on a
switchboard or panelboard shall be legibly and durably marked to indicate its
purpose unless such purpose is clearly evident.Where buildings or structures are
supplied by more than one power source,markings shall be provided at each service
equipment location and at all interconnected electric power production sources
identifying all electric power sources at the premises in accordance with NFPA 70.
Inspector:JEREMIAH VANDYKE-Comments:Room containing main electrical panel
and sprinkler riser must state"Main Electrical Panel-Sprinkler Riser Room".Back
storage room#42 needs"Electrical Panel"on door or near door.
Location:Rooms containing electrical panels X2.
Printed on 06/30/2023 @ 13:52
Page 2 of 6
STATUS CODE DESCRIPTION
FAIL 705.2-Inspection and Opening protectives in fire-resistance-rated assemblies shall be inspected and
maintenance. maintained in accordance with NFPA 80. Opening protectives in smoke barriers shall
be inspected and maintained in accordance with NFPA 80 and NFPA 105.Openings in
smoke partitions shall be inspected and maintained in accordance with NFPA 105.
Fire doors and smoke and draft control doors shall not be blocked,obstructed,or
otherwise made inoperable. Fusible links shall be replaced promptly whenever fused
or damaged.Opening protectives and smoke and draft control doors shall not be
`-- modified.
Inspector:JEREMIAH VANDYKE-Comments:Door stops need to
fire rated doors. p be removed from all
* 4
Location:All marked fire doors in entire building.
Printed on 06/30/2023 @ 13:52
Page 3of6
STATUS CODE DESCRIPTION
FAIL 906.4-Cooking equipment Fire extinguishers provided for the protection of cooking equipment shall be of an
fires. approved type compatible with the automatic fire-extinguishing system agent.
Cooking equipment involving solid fuels or vegetable or animal oils and fats shall be
protected by a Class K-rated portable extinguisher in accordance with Sections 906.1,
Item 2,906.4.1 and 906.4.2 as applicable.
ra
Inspector:JEREMIAH VANDYKE-Comments:As described in Code.Class K fire
portable fire extinguisher is needed.
ti
Location:2 kitchen locations.Planning on removing back/staff stove/oven.
"
st .\e
0
I`
1 I I \ 1
FAIL 912.4.2-Clear space around A working space of not less than 36 inches(914 mm)in width,36 inches(914 mm)in
connections. depth and 78 inches(1981 mm)in height shall be provided and maintained in front of
and to the sides of wall-mounted fire department connections and around the
circumference of free-standing fire department connections,except as otherwise
required or approved by the fire code official.
Inspector:JEREMIAH VANDYKE-Comments:Need to clear storage around sprinkler
pipe.
Location:Back storage area room#42.
'.1
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEREMIAH VANDYKE-Comments:New fire alarm panel was installed and is
past due for annual inspection by 142 days.Fire alarm contractor will need to upload
report to Compliance Engine website.
Location: Not Provided
GENERAL NOTES
JEREMIAH VANDYKE-06/30/2023 @ 13:50 Clothes Dryer cleaned by Martin Ainsworth on 6/21/2023 and is recorded on log.
Printed on 06/30/2023 @ 13:52
Page 4 of 6
•
GENERAL NOTES
JEREMIAH VANDYKE-06/30/2023 @ 13:50 Fire extinguishers compliant/serviced by Superior Fire in March 2023.
JEREMIAH VANDYKE-06/30/2023 @ 13:50 02/01/2023 S-(Annual)Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC.
Reviewed Compliant
JEREMIAH VANDYKE-06/30/2023 @ 13:51 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone#319-291-2515.
JEREMIAH VANDYKE-06/30/2023 @ 13:51 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-06/30/2023 @ 13:51 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-06/30/2023 @ 13:51 Inspection Fee=$80.00
REINSPECT/ON DATE
07/30/2023
CONTACT SIGNATURE
Martin Ainsworth-maintenance Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:06/30/2023 @ 13:52
Printed on 06/30/2023 @ 13:52
Page 5 of 6