COMMERCIAL INSPECTION- 1210 FLAMMANG DR- 5-31-23
FOR BILLING INQUIRY: (319)291-4323
I
L Description
I Total Price j
INSPECTION 20,000
OCCUPANCY FEE $90.00
$10.00
CUSTOMER# BILLING`DATE DUE DATE
24125 I 07/18/2023 INVOICE# CHARGES
I 08/20/2023 _
I 2024 0000003 4 $100.00
Less Prepayment $0.00
Total Due --> $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five
percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
u3
W A TERL 00 FIRE RESCUE
INSPECTION REPORT
STUFF ECT, 1210 FLAMMANG DR,BLDG 1210 FLAMMANG DR,WATERLOO IA S0702 , \
DETAILS
Inspection Date:05/31/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number: 1728 Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:All emergency egress lights in building
need to be addressed by Electrician with work order complete or invoice.
Location:Entire building
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:Missing Exit sign that must be replaced
above door.
Location:Loading dock area
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEREMIAH VANDYKE-Comments:All emergency EGRESS AND EXIT lights in
building need to be addressed by Electrician with work order complete or invoice.
Location:Entire building
Printed on 0610 1/2 023 @ 15:58
Page 1 of 6
STATUS CODE DESCRIPTION
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments:Panel states Radio Trouble,needs
addressed by fire alarm contractor.
•
Location: IT room in back
s 1.
:. .�A . 3Z
411110
FAIL 506.2-Key box maintenance. The operator of the building shall immediately notify the fire code official and provide
the new key where a lock is changed or rekeyed.The key to such lock shall be secured
in the key box.
Inspector:JEREMIAH VANDYKE-Comments:Keys needed for access for ALL locked
doors to be placed in Knox box.
Location: Not Provided
FAIL 509.1 -Identification. Fire protection equipment shall be identified in an approved manner.Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements fire protection systems shall be
identified for the use of the fire department.Approved signs required to identify fire
protection system equipment and equipment location shall be constructed of
durable materials,permanently installed and readily visible.
Inspector:JEREMIAH VANDYKE-Comments:Signage stating"FDC"made of durable
material needed above FDC connection.
Location:Outside above fire department connection.
Printed on 06/01/2023 @ 15:58
Page 2 of 6
STATUS CODE DESCRIPTION
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the electrical service
equipment is wider than 30 inches(762 mm),the minimum working space shall be
- not less than the width of the equipment.Storage of materials shall not be located
within the designated working space. Exceptions: 1.Where other dimensions are
required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
ER
Inspector:Ins
„�, p J EMIAH VANDYKE-Comments:Clearance of 36 inches in front of
electrical panels.
Location:IT room
FAIL 603.4.1 -Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and
legible sign stating"ELECTRICAL ROOM"or similar approved wording.The
disconnecting means for each service,feeder or branch circuit originating on a
switchboard or panelboard shall be legibly and durably marked to indicate its
purpose unless such purpose is clearly evident.Where buildings or structures are
supplied by more than one power source,markings shall be provided at each service
equipment location and at all interconnected electric power production sources
identifying all electric power sources at the premises in accordance with NFPA 70.
Inspector:JEREMIAH VANDYKE-Comments:Signage needed on door stating"Main
Electrical Panel".
Location: IT room/main electrical room
FAIL 603.5.2-Application and Relocatable power taps and current taps shall be directly connected to a
usePower supply. permanently installed receptacle.Exceptions: 1.Where approved for use in a Group A
occupancy or in a meeting room in a Group S occupancy,not more than five
relocatable power taps shall be permitted to be connected together or connected to
an extension cord for temporary use to supply power to electronic equipment.2.
Current taps and relocatable power taps shall not be required to connect directly to
a permanently installed receptacle outlet where used for 90 days or less for the
purpose of testing the performance of such devices.
Inspector:JEREMIAH VANDYKE-Comments:Power tap daisy chained under desk.
Location:Pricing area.
FAIL 603.5.3-Installation. Relocatable power tap cords shall not extend through walls,ceilings,floors,under
doors or floor coverings,or be subject to environmental or physical damage.
Printed on 06/01/2023 @ 15:58
Page 3of6
STATUS CODE DESCRIPTION
Inspector:JEREMIAH VANDYKE-Comments:Under rubber mat.
Viti* Location: Pricing area.
4.7
=s
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
damage or physical impact. Extension cords shall be used only with portable
appliances. Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEREMIAH VANDYKE-Comments:Red extension cord cannot be used as
•
permanent wiring and under rubber mat.Yellow extension cord needs to be
removed from ceiling.
Location: Pricing area and Main electrical room in back.
FAIL 704.1 -Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.Joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEREMIAH VANDYKE-Comments:Missing ceiling tile.
Location:Outside women's restroom.
GENERAL NOTES
JEREMIAH VANDYKE-05/31/2023 @ 16:11 Fire extinguishers serviced/compliant by Hawkeye Fire anfpd safety in May 2023.
Pnntea on 06/01/2023 @ 15:58
Page 4 of 6
GENERAL NOTES
JEREMIAH VANDYKE-06/01/2023 @ 15:51 04/13/2023 S-(Annual)Fire Alarm HAWKEYE COMMUNICATION Reviewed Compliant
JEREMIAH VANDYKE-06/01/2023 @ 15:52 04/10/2023 S-(Annual)Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS,INC.
Reviewed Compliant
JEREMIAH VANDYKE-06/01/2023 @ 15:57 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone#319-291-2515.
JEREMIAH VANDYKE-06/01/2023 @ 15:57 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-06/01/2023 @ 15:57 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-06/01/2023 @ 15:58 Inspection Fee=$100.00
REINSPECT/ON DATE
07/01/2023
CONTACT SIGNATURE
Chris Jung Reason for not collecting a signature:NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:06/01/2023 @ 15:52 Li/
L6
Printed on 06/01/2023 @ 15:58
Page 5 of 6