COMMERCIAL INSPECTION- 1150 FLAMMANG DR- 5-31-23 FOR BILLING INQUIRY: (319)291-4323
L Description v
I Total�Pricej
INSPECTION 20,000 $90.00
OCCUPANCY FEE
$10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24124 07/18/2023 08/20/2023 2024-00000033 $100.00
Less Prepayment $0.00
Total Due $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
v-
WATERLOO FIRE RESCUE "
otstk,INSPECTION REPORT
STUFF ETC.,1150 FLAMMA/VG DR,BLDG 1150 FLAAMAN6DR-STE200,WATERLOO IA 50702
DETAILS
Inspection Date:05/31/2023 Inspection Type:Annual Inspection(1 Yr) Inspection Number: 10366 Shift: N/A Station: N/A
Unit: N/A i Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A i Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1010.1.3-Door opening The force for pushing or pulling open interior swinging egress doors,other than fire
force Forces to unlatch and doors,shall not exceed 5 pounds(22 N).These forces do not apply to the force
open doors. required to retract latch bolts or disengage other devices that hold the door in a
closed position. For other swinging doors,as well as sliding and folding doors,the
door latch shall release when subjected to a 15-pound(67 N)force.The door shall be
set in motion when subjected to a 30-pound(133 N)force.The door shall swing to a
full-open position when subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following: 1.Where door hardware operates by push or
pull,the operational force to unlatch the door shall not exceed 15 pounds(66.7 N).
2.Where door hardware operates by rotation,the operational force to unlatch the
door shall not exceed 28 inch-pounds(315 N-cm).The force to open doors shall
comply with the following: 1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force for pushing or pulling
open the door shall not exceed 5 pounds(22 N).2.For other swinging doors,sliding
doors or folding doors,and doors required to be fire rated,the door shall require
not more than a 30-pound(133 N)force to be set in motion and shall move to a full-
open position when subjected to not more than a 15-pound(67 N)force.
Inspector:JEREMIAH VANDYKE-comments:Marked exit double doors is hard to open
and needs to be repaired.
Location: Back storage area double doors
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:Egress lights tested and failed.Must be
addressed by electrician with work order or invoice.
Location: Entire building
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:Exit lights tested and failed.Must be
addressed by electrician with work order or invoice.
Location: Entire Building
Printed on 06/01/2023 @ 16:06
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEREMIAH VANDYKE-Comments:All EXIT and EGRESS lights must be
addressed by electrician with work order or invoice.
Location: Entire Building.
GENERAL NOTES
JEREMIAH VANDYKE-06/01/2023 @ 16:03 Fire extinguishers serviced/compliant by Hawkeye Fire and Safety in May 2023.
JEREMIAH VANDYKE-06/01/2023 @ 16:04 04/13/2023 S-(Annual)Fire Alarm HAWKEYE COMMUNICATION Reviewed Compliant
JEREMIAH VANDYKE-06/01/2023 @ 16:04 04/10/2023 S-(Annual)Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC.
Reviewed Compliant
JEREMIAH VANDYKE-06/01/2023 @ 16:04 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address.Phone#319-291-2515.
JEREMIAH VANDYKE-06/01/2023 @ 16:04 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-06/01/2023 @ 16:04 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
REINSPECTION DATE
07/01/2023
CONTACT SIGNATURE
Chris Jung Reason for not collecting a signature: NA
Printed on 06/01/2023 @ 16:06
Page 2 of 3
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:06/01/2023 @ 16:05 J
QUESTIONS AIOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 06/01/2023 @ 16:06
Page 3 of 3