COMMERCIAL INSPECTION - 5 N ELK RUN RD - 6-28-23
FOR BILLING INQUIRY: (319)291-4323
LDescription
Total Price
INSPECTION 1
$40.00
OCCUPANCY FEE
$10.00
CUSTOMER# BILLING DATE DUE DATE I INVOICE#
24132 07/18/2023 08/20/2023 2024-00000032 CHARGES
$50.00
Less Prepayment $0.00
Total Due $50.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
, `NeJ3
WATERLOO FIRE RESCUE LI ) a
INSPECTION REPORT
Iry
ANNA'S KITCHEN,Sip N ELK RUN RD,BLDG 5 N ELK RUN RD,WATERLOO IA 50703
-6 tVi
DETAILS
Inspection Date:06/28/2023 ; Inspection Type:Annual Inspection(1Yr) j Inspection Number:335 j Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE ; Other Inspectors:BROCK WELIVER j Fee:$50.00
STATUS CODE DESCRIPTION
a a->: '_ 1004.9-Posting of occupant Every room or space that is an assembly occupancy shall have the occupant load of
load. the room or space posted in a conspicuous place,near the main exit or exit access
doorway from the room or space,for the intended configurations.Posted signs shall
be of an approved legible permanent design and shall be maintained by the owner or
the owner's authorized agent.
Inspector:JEREMIAH VANDYKE-Comments:Fire Inspector will bring occupancy load
sign out.
Location: Not Provided
FAIL 102.4-Application of building The design and construction of new structures shall comply with the International
code. Building Code,and any alterations,additions,changes in use or changes in
structures required by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Inspector:JEREMIAH VANDYKE-Comments:Contact City of Waterloo Building
Department for proper installation of the outside shade covers for customers.Will
require inspection by County Building inspector.
,,,, , iv; Fi E__:- ,i
I r Location:Outside
r91-
FAIL 304.3.1 -Spontaneous Materials susceptible to spontaneous ignition,such as oily rags,shall be stored in a
ignition. listed disposal container.Contents of such containers shall be removed and
disposed of daily.
Printed on 06/28/2023 @ t 5:15
Page 1 of 5
STATUS CODE DESCRIPTION
Inspector:JEREMIAH VANDYKE-Comments:UL listed container is needed in kitchen
for greasy rag disposal.
Location: Kitchen
@ASO
l
w -
FAIL 603.2-Abatement of unsafe Identified electrical hazards shall be abated.Identified hazardous electrical conditions
conditions and electrical in permanent wiring shall be brought to the attention of the responsible code official.
hazards. Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes Conditions that constitute an electrical shock or fire hazard
shall be abated not be used.
Inspector:JEREMIAH VANDYKE-Comments:Panel covered was removed for
construction and must be installed.
Location: Main electrical panel
FAIL 603.4.1 -Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and
legible sign stating"ELECTRICAL ROOM"or similar approved wording.The
disconnecting means for each service,feeder or branch circuit originating on a
switchboard or panelboard shall be legibly and durably marked to indicate its
purpose unless such purpose is clearly evident.Where buildings or structures are
supplied by more than one power source,markings shall be provided at each service
equipment location and at all interconnected electric power production sources
identifying all electric power sources at the premises in accordance with NFPA 70.
Inspector:JEREMIAH VANDYKE-Comments:Signage needed for door stating"Main
Electrical Panel"
Location: Main electrical panel/furnace room.
Printed on 06/28/2023 @ 15:15
Page 2 of 5
STATUS CODE DESCRIPTION
FAIL 606.3.3.1 -Inspection. Hoods,grease-removal devices,fans,ducts and other appurtenances shall be
inspected at intervals specified in Table 606.3.3.1 or as approved by the fire code
official. Inspections shall be completed by qualified individuals.
Inspector:JEREMIAH VANDYKE-Comments:Contact AKA cleaning who did the hood
cleaning to have them upload cleaning report to Compliance Engine.
Location: Kitchen hood
FAIL 904.13.5.2-Extinguishing Automatic fire-extinguishing systems shall be serviced not less frequently than every
system service. six months and after activation of the system. Inspection shall be by qualified
individuals,and a certificate of inspection shall be forwarded to the fire code official
upon completion.
Inspector:JEREMIAH VANDYKE-Comments:Contact Pro shield to have hood
suppression system inspected and have contractor upload report to Compliance
Engine after work completed.
Location: Kitchen
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned,properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3, portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEREMIAH VANDYKE-Comments:Fire extinguisher needed in dining area
and properly mounted in conspicuous location.
Location: Dining area
Printed on 06/28/2023 @ 15:15
Page 3of5
STATUS CODE DESCRIPTION
FAIL 906.4.2-Class K portable fire Where hazard areas include deep fat fryers,listed Class K portable fire extinguishers
extinguishers for deep fat shall be provided as follows: 1.For up to four fryers having a maximum cooking
fryers. medium capacity of 80 pounds(36.3 kg)each:one Class K portable fire extinguisher
of a minimum 1.5-gallon(6 L)capacity.2.For every additional group of four fryers
having a maximum cooking medium capacity of 80 pounds(36.3 kg)each:one
additional Class K portable fire extinguisher of a minimum 1.5-gallon(6 L)capacity
shall be provided.3.For individual fryers exceeding 6 square feet(0.55 m2)in surface
area:Class K portable fire extinguishers shall be installed in accordance with the
extinguisher manufacturer's recommendations.
Inspector:JEREMIAH VANDYKE-Comments:Class K extinguisher to be serviced and
hung in conspicuous spot.
Location: Kitchen area.
GENERAL NOTES
JEREMIAH VANDYKE-06/28/2023 @ 14:58 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-06/28/2023 @ 14:58 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-06/28/2023 @ 14:58 Inspection Fee=$50.00
REINSPECTION DATE
07/28/2023
CONTACT SIGNATURE
Snjezana Jovanovic Reason for not collecting a signature:NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:06/28/2023 @ 15:14