COMMERCIAL INSPECTION - 149 ARGYLE ST- 6-2-23 FOR BILLING INQUIRY: (319)291-4323
L Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24130 07/18/2023 08/20/2023 2024-00000029 $80.00
Less Prepayment $0.00
Total Due — $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
\ �►
(
WATERLOO FIRE RESCUE 11\
4PTER
\
INSPECTION REPORT j
SALVATION ARMY MEN'S HOUSE,149 ARGYLE ST,BLDG 149 ARGYLE ST,WATERLOO IA 50703
DETAILS
Inspection Date:06/02/2023 Inspection Type:Annual Inspection(1 Yr) Inspection Number:506 Shift: N/A Station: N/A
Unit: N/A I Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1103.9-Carbon monoxide Carbon monoxide alarms detection shall be installed in existing dwelling units and
alarmsdetection. sleeping units Group I-1, 1-2, 1-4 and R occupancies and in classrooms in Group E
occupancies where those units include any of the conditions identified in Sections
915.1.2 through 915.1.6.The carbon monoxide alarms shall be installed in the
locations specified in Section 915.2 and the installation shall be in accordance with
Section 915.4. Exceptions: 1.Carbon monoxide alarms are permitted to be solely
battery operated where the code that was in effect at the time of construction did
not require carbon monoxide detectors to be provided.2.Carbon monoxide alarms
are permitted to be solely battery operated in dwelling units that are not served from
a commercial power source.3.A carbon monoxide detection system in accordance
with Section 915.5 shall be an acceptable alternative to carbon monoxide alarms.
Inspector:JEREMIAH VANDYKE-Comments:Unable to locate Carbon Monoxide alarm
detectors to test.
Location: Not Provided
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:Exit sign above main entrance door was
tested and failed.
Location: Main front entrance.
Printed on 06/02/2023 @ 14:30
Page 1 of 4
STATUS CODE DESCRIPTION
FAI L 506.1 -Where required. Where access to or within a structure or an area is restricted because of secured
openings or where immediate access is necessary for life-saving or fire-fighting
purposes,the fire code official is authorized to require a key box to be installed in an
approved location.The key box shall be of an approved type listed in accordance with
UL 1037,and shall contain keys to gain necessary access as required by the fire code
official.
Inspector:JEREMIAH VANDYKE-Comments:Knox box must be ordered by building
owner.Can be ordered at Knoxbox.com. Please call if having issues with ordering.
Location: Not Provided
FAIL 506.2-Key box maintenance. The operator of the building shall immediately notify the fire code official and provide
the new key where a lock is changed or rekeyed.The key to such lock shall be secured
in the key box.
Inspector:JEREMIAH VANDYKE-Comments: Master key needed for access into
building and all rooms inside including office,sleeping quarters,and mechanical
rooms.
Location: Not Provided
FAIL 509.1 -Identification. Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements fire protection systems shall be
identified for the use of the fire department.Approved signs required to identify fire
_`F protection system equipment and equipment location shall be constructed of
durable materials,permanently installed and readily visible.
Inspector:JEREMIAH VANDYKE-Comments:Signage needed on door stating
"Sprinkler Riser Room"&"Main Electrical Panel"made of durable materials,
permanently installed and readily visible.
Location: Room where sprinkler riser is located.
FAIL 603.4.1 -Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and
legible sign stating"ELECTRICAL ROOM"or similar approved wording.The
disconnecting means for each service,feeder or branch circuit originating on a
switchboard or panelboard shall be legibly and durably marked to indicate its
r
purpose unless such purpose is clearly evident.Where buildings or structures are
supplied by more than one power source,markings shall be provided at each service
11 equipment location and at all interconnected electric power production sources
identifying all electric power sources at the premises in accordance with NFPA 70.
Inspector:JEREMIAH VANDYKE-Comments:Signage stating"Electrical Room"needed
on door.
Location: Electrical panel room
Printed on 06/02/2023 @ 14:30
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEREMIAH VANDYKE-Comments:Clothes Dryer Exhaust Duct system must
be cleaned from the dryer to the outside DOCUMENTED by who and when serviced.
Location:All clothes dryers in building.
FAIL 904.2.2-Commercial hood Each required commercial kitchen exhaust hood and duct system required by
and duct systems. Section 606 to have a Type I hood shall be protected with an approved automatic fire-
extinguishing system installed in accordance with this code.
Inspector:JEREMIAH VANDYKE-Comments:As described in Code.
Location:Community Kitchen
FAIL 906.4-Cooking equipment Fire extinguishers provided for the protection of cooking equipment shall be of an
fires. approved type compatible with the automatic fire-extinguishing system agent.
Cooking equipment involving solid fuels or vegetable or animal oils and fats shall be
protected by a Class K-rated portable extinguisher in accordance with Sections 906.1,
Item 2,906.4.1 and 906.4.2 as applicable.
Inspector:JEREMIAH VANDYKE-Comments:As described in Code.Class K fire
portable fire extinguisher is needed.
Location:Community Kitchen
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEREMIAH VANDYKE-Comments:New fire alarm panel was installed and is
past due for annual inspection by 112 days.Fire alarm contractor will need to get
proper permit for install and contact fire inspector for testing of fire alarm panel.
Location: Not Provided
GENERAL NOTES
JEREMIAH VANDYKE-06/02/2023 @ 13:39 Fire extinguishers serviced/compliant by Superior Fire in Many 2023.
JEREMIAH VANDYKE-06/02/2023 @ 13:41 S-(Annual)Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS,INC.Reviewed
Compliant
Printed an 06/02/2023 @ 14:30
Page 3 of 4
• 1 •
GENERAL NOTES
JEREMIAH VANDYKE-06/02/2023 @ 14:20 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address.Phone#319-291-2515.
JEREMIAH VANDYKE-06/02/2023 @ 14:20 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-06/02/2023 @ 14:21 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-06/02/2023 @ 14:21 Inspection Fee=$80.00
REINSPECTION DATE
07/02/2023
CONTACT SIGNATURE
Rosie Julion Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:06/02/2023 @ 13:45