COMMERCIAL INSPECTION-3165 W AIRLINE HWY- 6-29-23 FOR BILLING INQUIRY: (319)291-4323
Description ( Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24137 07/18/2023 08/20/2023 2024-00000025 $80.00
Less Prepayment $0.00
Total Due —> $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
\ o
WATERLOO FIRE RESCUE t �P�a����
INSPECTION REPORT \
H \
3165 WAIRLINE WY,WATERLOO/A S0703 ��
b06\
DETAILS
Inspection Date:06/29/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number: 10584 Shift: N/A Station: N/A
Unit: N/A j Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:All emergency and egress lights need to
be repaired or tested.
Location: Main shop/office
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:All emergency and egress lights need to
be repaired or tested.
Location: Main shop/office.
FAIL 4006.1 -Hazard identification Unless otherwise exempted by the fire code official,visible hazard identification
signs. signs,as specified in NFPA 704 for the specific material contained,shall be placed on
stationary containers and above-ground tanks;at entrances to locations where
hazardous materials are stored,dispensed, used or handled in quantities requiring a
permit;and at specific entrances and locations designated by the fire code official.
Inspector:JEREMIAH VANDYKE-Comments:Proper placards and label needed on
entrance doors and on tank.
Location: 1.Main Shop and Warehouse holding flammable materials 2.Tank outside
of main shop needs to marked.
Printed on 06/29/2023 @ 11:11
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 603.4.1 -Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and
legible sign stating"ELECTRICAL ROOM"or similar approved wording.The
disconnecting means for each service,feeder or branch circuit originating on a
switchboard or panelboard shall be legibly and durably marked to indicate its
purpose unless such purpose is clearly evident.Where buildings or structures are
supplied by more than one power source,markings shall be provided at each service
equipment location and at all interconnected electric power production sources
identifying all electric power sources at the premises in accordance with NFPA 70.
Inspector:JEREMIAH VANDYKE-Comments:Signage needed on door stating"Main
Electrical Panel".Storage near panels must be clear if panels by 36 inches.
Location: Room with main electrical panel.
GENERAL NOTES
JEREMIAH VANDYKE-06/29/2023 @ 10:58 Fire extinguishers serviced/compliant by Pro Shield in September 2022.
JEREMIAH VANDYKE-06/29/2023 @ 10:59 No fire alarm or sprinklers systems.
JEREMIAH VANDYKE-06/29/2023 @ 10:59 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone#319-291-2515.
JEREMIAH VANDYKE-06/29/2023 @ 11:00 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-06/29/2023 @ 11:00 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-06/29/2023 @ 11:00 Inspection Fee=$80.00
REINSPECTION DATE
07/29/2023
Printed on 06/29/2023 @ 11:11
Page 2of3