COMMERCIAL INSPECTION-3754 W AIRLINE HWY- 7-13-23 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
14709 07/18/2023 08/20/2023 2024-00000026 $100.00
Less Prepayment $0.00
Total Due— $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
\flQC1
WATERLOO FIRE RESCUE �P�ERtoo
INSPECTION REPORT II
MC GOWAN'S FURNITURE,3754 W AIRLINE HWY,BLDG 3754 W AIRLINE HW)',WATERLOO IA 50703 4kt10�,
'
DETAILS
Inspection Date:07/13/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number:208 Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
4 ; - Inspector:JEREMIAH VANDYKE-Comments:Bed must be removed in front of marked
exit door.
Location: Back room.
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:All exit/egress lights were tested and
failed. Need to be replaced or repaired.
Location: Entire building.
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:All exit/egress lights were tested and
failed. Need to be replaced or repaired.
Location: Entire building.
Printed on 07/13/2023 @ 16:50
Page 1 of 3
it
STATUS CODE DESCRIPTION
FAIL 603.5-Relocatable power Multiplug adapters,such as cube adapters,unfused plug strips or any other device
taps and current not complying with NFPA 70 shall be prohibited.The construction and use of current
taps.Multiplug adapters. taps and relocatable taps shall be in accordance with NFPA 70 and this code.
Inspector:JEREMIAH VANDYKE-Comments:Can not plug multi plug adapters into
multi plug adapters or power taps/strips.Power strips are to be plugged directly into
wall outlets.ALSO extension cords can not be used as permeant wiring.
Location: Receptionist desk area.
FAIL 705.2.6-Testing. Horizontal and vertical sliding and rolling fire doors shall be inspected and tested
annually to confirm proper operation and full closure. Records of inspections and
testing shall be maintained.
Inspector:JEREMIAH VANDYKE-Comments: Fire door needs inspected and tagged.
Location:Fire door needs inspected
c }
1s€ik
41
GENERAL NOTES
JEREMIAH VANDYKE-07/13/2023 @ 16:25 Fire extinguishers serviced/compliant by Pro Shield in June 2023.
JEREMIAH VANDYKE-07/13/2023 @ 16:47 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-07/13/2023 @ 16:47 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-07/13/2023 @ 16:48 Inspection Fee=$100.00
Printed on 07/13/2023 @ 16:50
Page 2of3
REINSPECTION DATE
08/12/2023
CONTACT SIGNATURE
T.J.Mcgowan Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:07/13/2023 @ 16:49