COMMERCIAL INSPECTION-905 FRANKLIN ST- 6-21-23 FOR BILLING INQUIRY: (319)291-4323
L.Description .
I Total Price J
INSPECTION 20,000 $90.00
OCCUPANCY FEE
$10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES .".
10918 07/07/2023 I
08/10/2023 2024-00000010 $100.00
Less Prepayment $0.00
Total Due—* $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE �/
RESCUE � � 40ERC00
INSPECTION REPORT
PEOPLE'S COMMUNITY HEALTH CUNIC,905 FRANKLIN ST,BLDG 905 FRANKLIN ST,
WATERLOO/A 50703
DETAILS
Inspection Date:06/21/2023 ( Inspection Type:Annual Inspection(1Yr) ( Inspection Number:8406 I Shift: N/A Station: N/A
Unit: N/A I Lead Inspector:JEREMIAH VANDYKE I Other Inspectors:BROCK WELIVER I Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:Egress light tested and failed.
Location:X-ray room
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:Exit lights tested and failed.
Location: 1.2 south group room.2.Urgent care area leading out to hallway.
FAIL 315.3.1 -Ceiling clearance. Storage shall be maintained 2 feet(610 mm)or more below the ceiling in
nonsprinklered areas of buildings or not less than 18 inches(457 mm)below
sprinkler head deflectors in sprinklered areas of buildings.Exceptions:1.The 2-foot
(610 mm)ceiling clearance is not required for storage along walls in nonsprinklered
areas of buildings.2.The 18-inch(457 mm)ceiling clearance is not required for
storage along walls in areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1,903.3.1.2 or 903.3.1.3.
Inspector:JEREMIAH VANDYKE-Comments:Storage needs to be cleared near ceiling.
Location: IT room
FAIL 506.2-Key box maintenance. The operator of the building shall immediately notify the fire code official and provide
the new key where a lock is changed or rekeyed.The key to such lock shall be secured
in the key box.
Inspector:JEREMIAH VANDYKE-Comments:Key needed for door into sprinkler riser
room.
Location:Sprinkler riser door.
Printed on 06/21/2023 @ 15:28
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEREMIAH VANDYKE-Comments:Clothes Dryer Exhaust Duct system must
be cleaned from the dryer to the outside DOCUMENTED by who and when serviced.
Location: Not Provided
FAIL 704.1 -Maintaining Where required when the building was originally constructed,materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.Joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEREMIAH VANDYKE-Comments:Missing ceiling tile needs replaced.
Location:Room 1712
GENERAL NOTES
JEREMIAH VANDYKE-06/21/2023 @ 15:16 Addition still in progress with missing ceiling tiles.
JEREMIAH VANDYKE-06/21/2023 @ 15:16 Fire extinguisher serviced/compliant by Superior Fire in February 2023.
JEREMIAH VANDYKE-06/21/2023 @ 15:17 Fire rated roll doors serviced by Overhead doors on 4/26/2023.
JEREMIAH VANDYKE-06/21/2023 @ 15:18 Fire Alarm is past due to construction.
JEREMIAH VANDYKE-06/21/2023 @ 15:19 05/05/2023 S-(Annual)Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS,INC.
Reviewed Compliant
Printed on 06/21/2023 @ 15:28
Page 2of3
GENERAL NOTES
JEREMIAH VANDYKE-06/21/2023 @ 15:24 Adding annunciator panel and Knox box on new addition when completed.
JEREMIAH VANDYKE-06/21/2023 @ 15:26 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-06/21/2023 @ 15:27 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-06/21/2023 @ 15:27 Inspection Fee=$100.00
REINSPECTION DATE
07/21/2023
CONTACT SIGNATURE
Dan Adams-Maintenance Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE Signed on:06/21/2023 @ 15:23 c7a)