COMMERCIAL INSPECTION- 1503 E SAN MARNAN DR- 5-22-23 FOR BILLING INQUIRY: (319)291-4323
1_Description 1 Total Price]
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24067 07/07/2023 08/10/2023 2024-00000021 $100.00
Less Prepayment $0.00
Total Due -* $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE 41pTER(p0
INSPECTION REPORT I
GREEN LEAF TOBACCO AND E-CIGS,1503 E SAN MARNAN SUITE C DR,BLDG 1503 E SAN
MARNAN DR,WATERLOO IA 50702
DETAILS
Inspection Date:05/22/2023 I Inspection Type:Annual Inspection(1Yr) I Inspection Number:10157 I Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments:Remove shelving and obstructions to rear exit
door or remove exit sign and properly contain wires.Occupant load 41 so second exit
not required..(3120 square feet-669 2451 divided by 60.)
Location:rear exit in back storage room
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
1 ` r, providedin front of electrical service equipment.Where the electrical service
equipment is wider than 30 inches(762 mm),the minimum working space shall be
low
,g,.. not less than the width of the equipment.Storage of materials shall not be located
_ _ _ within the designated working space.Exceptions:1.Where other dimensions are
. , required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
\ ' that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove obstructions to electric panel.maintain a
minimum of 36"clearance at all times.
Location: back of store
Printed an 05/22/2023 @ 15:21
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 704.1 -Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1 Joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:remove combustible storage from above the
ceiling and replace missing ceiling tile.
Location:back room
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance
with this section and NFPA 10.Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned,properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual inspection for fire extinguishers
Location: Front entrance
FAIL 906.6-Unobstructed and Portable fire extinguishers shall not be obstructed or obscured from view. In rooms
unobscured. or areas in which visual obstruction cannot be completely avoided,means shall be
provided to indicate the locations of extinguishers.
Printed on 05/22/2023 @ 15:21
Page 2 of 3
STATUS CODE DESCRIPTION
Inspector:JEFF SIEBEL-Comments:remove obstructions(vending machine)from in front of fire extinguisher or relocate fire extinguisher.Maintain a minimum of 36"
g" E clearance to fire extinguisher at all times.
Location:front by vending machine
GENERAL NOTES
JEFF SIEBEL-05/22/2023 @ 15:16 re-inspection fee$100
REINSPECTION DATE
06/20/2023
CONTACT SIGNATURE
Mo
Signed on:05/22/2023 @ 15:17
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:05/22/2023 @ 15:17