HomeMy WebLinkAbout1500 W AIRLINE HWY O F W A TF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
'` o
06/23/2023 07/25/2023 2023-00011326 $100.00
o
4.ds 71'442
�3 e
Customer#: 12024 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
ALTER METAL RECYCLING-WATERLOO 715 Mulberry St
1500 W AIRLINE HWY WATERLOO, IA 50703
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION- 1500 W AIRLINE HWY- 6-6-23 FOR BILLING INQUIRY: (319)291-4323
[Description Total Price]
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
12024 06/23/2023 07/25/2023 2023-00011326 $100.00
Less Prepayment $0.00
Total Due--- $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
. { 6
WATERLOO FIRE RESCUEPSERCO� o
INSPECTION REPORT I 4
ALTER METAL RECYCLING, 1500 WAIRLINE HWY,BLDG 1500 WAIRLINE HWY,WATERLOO IA
50703 4141102b
DETAILS
Inspection Date:06/06/2023 j Inspection Type:Annual Inspection(1Yr) Inspection Number:8941 ; Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments: Exit light tested and failed near east
garage door.
Location:Warerhouse
FAIL 5303.5.3-Securing Compressed gas containers,cylinders and tanks shall be secured to prevent falling
compressed gas containers, caused by contact,vibration or seismic activity.Securing of compressed gas
cylinders and tanks. containers,cylinders and tanks shall be by one of the following methods: 1.Securing
containers,cylinders and tanks to a fixed object with one or more restraints.
2.Securing containers,cylinders and tanks on a cart or other mobile device designed
for the movement of compressed gas containers,cylinders or tanks.3. Nesting of
compressed gas containers,cylinders and tanks at container filling or servicing
facilities or in sellers'warehouses not open to the public. Nesting shall be allowed
provided that the nested containers,cylinders or tanks, if dislodged,do not obstruct
``., the required means of egress.4.Securing of compressed gas containers,cylinders
' { and tanks to or within a rack,framework,cabinet or similar assembly designed for
& ' such use. Exception:Compressed gas containers,cylinders and tanks in the process
# _ �a of examination,filling,transport or servicing.
Inspector:JEREMIAH VANDYKE-Comments:Unsecured tank in warehouse near
warehouse office on west side of building.
Location:Warehouse
Printed on 06/12/2023 @ 10:47
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 603.2.2-Unapproved Open junction boxes and open-wiring splices shall be prohibited.Approved covers
conditionsOpen electrical shall be provided for all switch and electrical outlet boxes.
terminations.
Inspector:JEREMIAH VANDYKE-Comments:Open junction box in warehouse near
warehouse office on west side of building.
Location:Warehouse
i \g
FAIL 901.4-lnstallation.Fire Fire protection systems shall be maintained in accordance with the original
protection and life safety installation standards for that system. Required systems shall be extended,altered
systems. or augmented as necessary to maintain and continue protection where the building
is altered, remodeled or added to.Alterations to fire protection systems shall be
done in accordance with applicable standards. Fire protection and life safety systems
shall be installed,repaired,operated and maintained in accordance with this code
- and the International Building Code.
T
'; Inspector:JEREMIAH VANDYKE-Comments: Fire hose is missing in hose tower.
e' Standpipe in stair tower is to be inspected by contractor and uploaded into
/10% ,
F compliance engine by servicing contractor.
''/ Location:Shredder tower.
Printed on 06/12/2023 @ 10:47
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
, t allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
• - ' ,k` ;° extinguishers that are supervised by a listed and approved electronic monitoring
7, Aigt A• Io. -_ device,provided that all of the following conditions are met:2.1.Electronic monitoring'" _ N �''� shall confirm that extinguishers are properly positioned, properly charged and
3 1 f' Mir:: unobstructed.2.2.Loss of power or circuit continuityto the electronic monitoring
��� �; iN ,�,
•' _;,1 device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
.'tea''' is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEREMIAH VANDYKE-Comments:Tags have multiple punch holes,unsure
of service date.
Location:All fire extinguishers on property
FAIL 906.7-Hangers and brackets. Hand-held portable fire extinguishers,not housed in cabinets,shall be installed on
the hangers or brackets supplied. Hangers or brackets shall be securely anchored to
the mounting surface in accordance with the manufacturer's installation instructions.
---. , Inspector:JEREMIAH VANDYKE-Comments:Fire extinguisher on ground and must be
secured on hanger.
..== lA
- =- a , Location: Back shed
i P \
FAIL 906.8-Cabinets. Cabinets used to house portable fire extinguishers shall not be locked.Exceptions:
1.Where portable fire extinguishers subject to malicious use or damage are provided
with a means of ready access.2.In Group 1-3 occupancies and in mental health areas
in Group 1-2 occupancies,access to portable fire extinguishers shall be permitted to
4 ` - � be locked or to be located in staff locations provided that the staff has keys.
Inspector:JEREMIAH VANDYKE-Comments:Fire extinguisher needs to be in secured
' --- 4 outdoor cabinet in conspicuous location.
' ,i Location: Near refueling tanks
GENERAL NOTES
Printed on 06/12/2023 @ 10:47
Page 3 of 4
JEREMIAH VANDYKE-06/12/2023 @ 10:46 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-06/12/2023 @ 10:46 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-06/12/2023 @ 10:47 Inspection Fee=$100.00
REINSPECTION DATE
07/12/2023
CONTACT SIGNATURE
John Hoefing Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:06/12/2023 @ 09:34 (/