COMMERCIAL INSPECTION-324 FLETCHER AVE- 6-8-23 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price j
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
3360 06/23/2023 07/25/2023 2023-00011330 $80.00
Less Prepayment $0.00
Total Due—> $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE 4,ptER(oc,
INSPECTION REPORT '-) I
AD
KWIK TRIP#732,324 FLETCHER AVE,BLDG 324 FLETCHER AVE,WATERLOO/A 50701 4,40
DETAILS
Inspection Date:06/08/2023 Inspection Type:Annual Inspection(1 Yr) Inspection Number:8592 ! Shift: N/A ; Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 109.2-Testing and operation. Equipment requiring periodic testing or operation to ensure maintenance shall be
tested or operated as specified in this code.
Inspector:JEFF SIEBEL-Comments:provide documentation of testing of all
safeguards and devices in compressed natural gas plant.
Location:Compressed Natural Gas Plant
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
Aft
in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the electrical service
equipment is wider than 30 inches(762 mm),the minimum working space shall be
not less than the width of the equipment.Storage of materials shall not be located
- =:• within the designated working space.Exceptions: 1.Where other dimensions are
` required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
r 'a a that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
e f Inspector:JEFF SIEBEL-Comments:Remove obstructions to all electrical panels on
both sides of room.Maintain a minimum of 36"clearance at all times.REPEAT
VIOLATION
Location: Back room
FAIL 906.6-Unobstructed and Portable fire extinguishers shall not be obstructed or obscured from view. In rooms
unobscured. or areas in which visual obstruction cannot be completely avoided, means shall be
provided to indicate the locations of extinguishers.
Inspector:JEFF SIEBEL-Comments:MAINTAIN A MINIUM OF 36"CLEARANCE TO FIRE
EXTINGUISHERS
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-06/09/2023 @ 13:51 Annual inspection fee$80
Printed on 06/09/2023 @ 13:57
Page 1 of 2
GENERAL NOTES
JEFF SIEBEL-06/09/2023 @ 13:54 Dangerous situation discovered with temperature and pressure relief valve being
obstructed by installed guards.Ordered removed by Mechanical Inspector and
confirmed on 5/9/23
JEFF SIEBEL-06/09/2023 @ 13:54
JEFF SIEBEL-06/09/2023 @ 13:55
REINSPECTION DATE
06/29/2023
CONTACT SIGNATURE
Service Dept K C c 1 Zy
Signed on:06/09/2023 @ 13:51
3
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:06/09/2023 @ 13:51
QUESTIONS ADOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 06/09/2023 @ 13:57