COMMERCIAL INSPECTION - 117 E SAN MARNAN DR- 6-1-23 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
22784 06/23/2023 07/25/2023 2023-00011335 $80.00
Less Prepayment $0.00
Total Due— $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
�ptER�
WATERLOO FIRE RESCUE
INSPECTION REPORT
YESWAY,117 E SAN MARNAN DR,BLDG 117 E SAN MAR/VAN DR,WATERLOO/A 50702
DETAILS
Inspection Date:06/01/2023 Inspection Type:Annual Inspection(1Yr) I Inspection Number:8288 ; Shift: N/A I Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL j Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 304.3.1 -Spontaneous Materials susceptible to spontaneous ignition,such as oily rags,shall be stored in a
ignition. listed disposal container.Contents of such containers shall be removed and
disposed of daily.
Inspector:JEFF SIEBEL-Comments: Provide an approved listed oily waste container
with self-closing lid or a written corporate policy on how oily materials are safely
handled.see attachment
Location: Not Provided
FAIL 305.1 -Clearance from Clearance between ignition sources,such as luminaires,heaters,flame-producing
ignition sources. devices and combustible materials,shall be maintained in an approved manner.
Inspector:JEFF SIEBEL-Comments:remove oil storage to a minimum of 36"clearance
to cooking appliance.
Location:next to auto-fry
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the electrical service
equipment is wider than 30 inches(762 mm),the minimum working space shall be
not less than the width of the equipment.Storage of materials shall not be located
within the designated working space. Exceptions: 1.Where other dimensions are
required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove all obstructions from in front of electrical
panels including oil storage.(it is combustible)
Location:back room in front of electrical panel
FAIL 606.3.3-Cleaning. Hoods,grease-removal devices,fans,ducts and other appurtenances shall be
cleaned at intervals as required by Sections 606.3.3.1 through 606.3.3.3.
Printed on 06/02/2023 @ 10:12
Page 1 of 3
STATUS CODE DESCRIPTION
Inspector:JEFF SIEBEL-Comments:provide current semi-annual kitchen hood
exhaust system cleaning inspection report with all discrepancies corrected.
Contractor must upload online to the compliance engine. 166 days past due
Location:Not Provided
FAIL 904.13.5.2-Extinguishing Automatic fire-extinguishing systems shall be serviced not less frequently than every
system service. six months and after activation of the system.Inspection shall be by qualified
individuals,and a certificate of inspection shall be forwarded to the fire code official
upon completion.
Inspector:JEFF SIEBEL-Comments:provide current semi-annual kitchen hood
exhaust system fire suppression inspection report with all discrepancies corrected.
Contractor must upload online to the compliance engine. 166 days past due
Location: Not Provided
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10.Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned,properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments: Provide annual service for fire extinguishers.
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-06/02/2023 @ 10:11 annual inspection$80
REINSPECTION DATE
06/23/2023
Printed on 06/02/2023 @ 10:12
Page 2 of 3
CONTACT SIGNATURE
Stephanie Adolph r2c(--, .�
Signed on:06/02/2023 @ 10:09
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:06/02/2023 @ 10:09