HomeMy WebLinkAbout421 OAK AVE OF W A TF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
(o 06/23/2023 07/25/2023 2023-00011336 $80.00
O
Customer#: 23235 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
THE ROSE OF WATERLOO 715 Mulberry St
ATTN: DIANE MURPHY- OPEN ARMS WATERLOO, IA 50703
421 OAK AVE
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION-421 OAK AVE - 5-10-23 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23235 06/23/2023 07/25/2023 2023-00011336 $80.00
Less Prepayment $0.00
Total Due — $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE �PtEA�oo
INSPECTION REPORT t
THE ROSE,421 OAKAVE,BLDG 421 OAKAVE,WATERLOO/A 50703 e- .
DETAILS
Inspection Date:05/10/2023 Inspection Type:Residential Common Areas Inspection Inspection Number:8487 Shift: N/A
Station: N/A Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1104.5-Illumination Where means of egress illumination is provided,the power supply for means of
emergency power. egress illumination shall normally be provided by the premises'electrical supply. In
the event of power supply failure,illumination shall be automatically provided from
an emergency system for the following occupancies where such occupancies require
two or more means of egress: 1.Group A having 50 or more occupants.Exception:
Assembly occupancies used exclusively as a place of worship and having an occupant
load of less than 300.2.Group B buildings three or more stories in height,buildings
with 100 or more occupants above or below a level of exit discharge serving the
occupants or buildings with 1,000 or more total occupants.3.Group E in interior exit
access and exit stairways and ramps,corridors,windowless areas with student
occupancy,shops and laboratories.4.Group F having more than 100 occupants.
Exception: Buildings used only during daylight hours and that are provided with
windows for natural light in accordance with the International Building Code.
5.Group I.6.Group M. Exception: Buildings less than 3,000 square feet(279 m2)in
gross sales area on one story only,excluding mezzanines.7.Group R-1. Exception:
Where each sleeping unit has direct access to the outside of the building at grade.
8.Group R-2. Exception:Where each dwelling unit or sleeping unit has direct access to
the outside of the building at grade.
Inspector:JEREMIAH VANDYKE-Comments:Outside egress light on 1st floor north
stair tower,west side of building,was tested and failed.Will send video of egress light
after repaired.
Location: Not Provided
FAIL 610.1 -Clothes dryer exhaust Clothes dryer exhaust duct systems shall be in accordance with Sections 610.1.1 and
duct systems. 610.1.2.
Inspector:JEREMIAH VANDYKE-Comments:Will send picture of Invoice of last clothes
dryer cleaning..
Location: Not Provided
Printed on 05/10/2023 @ 16:30
Page 1 of 3
s -
STATUS CODE DESCRIPTION
FAIL 705.2.6-Testing. Horizontal and vertical sliding and rolling fire doors shall be inspected and tested
annually to confirm proper operation and full closure. Records of inspections and
testing shall be maintained.
Inspector:JEREMIAH VANDYKE-Comments:Kitchen drop door needs to be tested.
Will send picture of invoice for door testing.
Location: Not Provided
FAIL 99999-Inspection Outcome Did the inspection pass or fail?
Inspector:JEREMIAH VANDYKE-Comments:Will send videos or picture of corrected
violations.
Location: Not Provided
GENERAL NOTES
JEREMIAH VANDYKE-05/10/2023 @ 16:15 Fire Extinguishers serviced/compliant by Continental fire in January 2023.
JEREMIAH VANDYKE-05/10/2023 @ 16:15 04/12/2023 S-(Quarterly)Fire Sprinkler CONTINENTAL FIRE SPRINKLER Reviewed
Compliant
JEREMIAH VANDYKE-05/10/2023 @ 16:15 01/17/2023 S-(Annual)Fire Alarm CONTINENTAL FIRE SPRINKLER CO.Reviewed
Compliant
JEREMIAH VANDYKE-05/10/2023 @ 16:15 01/17/2023 S-Kitchen Hood Suppression CONTINENTAL FIRE SPRINKLER CO. Reviewed
Compliant
JEREMIAH VANDYKE-05/10/2023 @ 16:16 01/17/2023 L-(Semi-Annual)Kitchen Exhaust CONTINENTAL FIRE SPRINKLER CO.
Reviewed Compliant
JEREMIAH VANDYKE-05/10/2023 @ 16:16 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address.Phone#319-291-2515.
JEREMIAH VANDYKE-05/10/2023 @ 16:16 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
Printed on 05/10/2023 @ 16:30
Page 2 of 3
GENERAL NOTES
JEREMIAH VANDYKE-05/10/2023 @ 16:16 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-05/10/2023 @ 16:20 Inspection Fee=$80.00
REINSPECTION DATE
06/09/2023
CONTACT SIGNATURE
Cedric Holmes-maintenance Contact Refused
Refusal Reason:N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:05/10/2023 @ 16:29 L
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 05/10/2023 @ 16:30