COMMERCIAL INSPECTION -407 E PARK AVE- 5-30-23 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
9492 06/23/2023 07/25/2023 2023-00011337 $100.00
Less Prepayment $0.00
Total Due $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
ELK'S CLUB,407E PARK AVE,BLDG 407 E PARK AVE,WATERLOO IA 50703
DETAILS
Inspection Date:05/30/2023 Inspection Type:Annual Inspection(1Yr) j Inspection Number:9182 I Shift: N/A I Station: N/A
Unit: N/A ( Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
}
Inspector:JEFF SIEBEL-Comments: Remove all storage from egress path and stairs.
maintain clearance to fire extinguisher.
.11
Location: NE entrance to ballroom stairway
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:repair egress light by TV monitor.
Location:upper kitchen
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:repair egress light.
Location:ceiling by door to old bowling alley.
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:repair egress light.
Location:by elevator and red stag directional sign
Printed on 05/31/2023 @ 1012
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair exit light
Location:from stag bar to hall
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair exit light.
Location:bottom of red stag stairs
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEFF SIEBEL-Comments:Annunciator panel has no display.repair display.
Last year display was backwards.
Location:By Sherri's office
FAIL 606.3.3.3-Records. Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments: Provide inspection report with all discrepancies
corrected .Contractor must upload online to the compliance engine.
Location:kitchen hood exhaust cleaning inspection report
FAIL 904.13.5.2-Extinguishing Automatic fire-extinguishing systems shall be serviced not less frequently than every
system service. six months and after activation of the system.Inspection shall be by qualified
individuals,and a certificate of inspection shall be forwarded to the fire code official
upon completion.
Inspector:JEFF SIEBEL-Comments:provide current semi-annual kitchen hood fire
suppression inspection with all discrepancies corrected .Contractor must upload
online to the compliance engine.
Location:Ansul system inspection
Printed on 05/31/2023 @ 10:12
Page 2 of 4
k
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned, properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:Fire extinguishers due for annual service 6/1/23
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-05/31/2023 @ 10:12 Annual inspection$100
REINSPECTION DATE
06/21/2023
CONTACT SIGNATURE
Jeff Hostettler L- C_ 4_ j,
Signed on:05/31/2023 @ 10:09
,J 6-74 )----/-------___
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:05/31/2023 @ 10:09
Printed on 05/31/2023 @ 10:12
Page 3 of 4