COMMERCIAL INSPECTION -45 W JEFFERSON ST- 5-22-23 FOR BILLING INQUIRY: (319)291-4323
[Description I Total Price j
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23124 06/21/2023 07/25/2023 2023-00011286 $100.00
Less Prepayment $0.00
Total Due $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE ;
INSPECTION REPORT
GRAND CROSSING,45 WJEFFERSON ST,BLDG 45 W JEFFERSON,WATERLOO IA 50702
DETAILS
Inspection Date:05/22/2023 ; Inspection Type: Residential Common Areas Inspection Inspection Number: 10284 Shift: N/A ;
Station: N/A j Unit: N/A Lead Inspector:JEREMIAH VANDYKE ( Other Inspectors: N/A ; Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEREMIAH VANDYKE-Comments:Generator report/maintenance needed
of last inspection by contractor.
Location: Not Provided
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments: Fire alarm in trouble mode and must be
addressed by licensed fire alarm contractor.
Location:3rd floor coffee room on Fire alarm panel.
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments:Smoke alarm pulled from ceiling and
hanging by wires.
Location: Near room#401
FAIL 308.1.4-Open-flame cooking Charcoal burners and other open-flame cooking devices shall not be operated on
devices. combustible balconies or within 10 feet(3048 mm)of combustible construction.
Exceptions: 1.One-and two-family dwellings.2.Where buildings,balconies and decks
are protected by an automatic sprinkler system.3.LP-gas cooking devices having LP-
gas container with a water capacity not greater than 21/2 pounds[nominal 1 pound
(0.454 kg)LP-gas capacity].
Inspector:JEREMIAH VANDYKE-Comments: 1.Multiple balconies had Charcoal grills.
2.20 lb.LP gas were on multiple balconies.
Location:Balconies
Printed on 05/22/2023 @ 15:46
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEREMIAH VANDYKE-Comments:All clothes dryers must be cleaned and
either record log of cleaning/or invoice must be provided.
Location:All clothes dryers.
FAIL 703.1 -Maintaining Materials and firestop systems used to protect membrane and through penetrations
protection. in fire-resistance-rated construction and construction installed to resist the passage
of smoke shall be maintained.The materials and firestop systems shall be securely
attached to or bonded to the construction being penetrated with no openings visible
through or into the cavity of the construction.Where the system design number is
known,the system shall be inspected to the listing criteria and manufacturer's
installation instructions.
Inspector:JEREMIAH VANDYKE-Comments:Hole in ceiling must be repaired located
on corner mechanical room.Will send picture of repair.
Location:Corner mechanical room
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEREMIAH VANDYKE-Comments:Door needs to close and latch
automatically.
Location: East stair tower 1st floor.
FAIL 99999-Inspection Outcome Did the inspection pass or fail?
Inspector:JEREMIAH VANDYKE-Comments:Will send pictures/videos/reports of
corrected violations.
Location: Not Provided
GENERAL NOTES
JEREMIAH VANDYKE-05/22/2023 @ 15:44 Discussed lithium batteries/EV's.
JEREMIAH VANDYKE-05/22/2023 @ 15:45 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address.Phone#319-291-2515.
Printed on 05/22/2023 @ 15:46
Page 2 of 4
GENERAL NOTES
JEREMIAH VANDYKE-05/22/2023 @ 15:45 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-05/22/2023 @ 15:45 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-05/22/2023 @ 15:45 Inspection Fee=$100.00
JEREMIAH VANDYKE-05/22/2023 @ 15:01 Fire extinguishers serviced/compliant by Superior Fire in February 2022.
JEREMIAH VANDYKE-05/22/2023 @ 15:39 02/01/2023 S-(Annual)Fire Alarm HAWKEYE ALARM Reviewed Compliant
JEREMIAH VANDYKE-05/22/2023 @ 15:39 11/09/2022 S-5 Year Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS,INC.Reviewed
Compliant
JEREMIAH VANDYKE-05/22/2023 @ 15:39 10/20/2022 S-(Annual)Fire Pump BLACKHAWK AUTOMATIC SPRINKLERS,INC.Reviewed
Compliant
JEREMIAH VANDYKE-05/22/2023 @ 15:40 10/20/2022 S-Private Fire Hydrants BLACKHAWK AUTOMATIC SPRINKLERS,INC.
Reviewed Compliant
REINSPECTION DATE
06/21/2023
CONTACT SIGNATURE
Chris Olsen Reason for not collecting a signature: NA
Printed on 05/22/2023 @ 15:46
Page 3 of 4
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:05/22/2023 @ 15:38 /117