HomeMy WebLinkAbout1104 WASHINGTON ST (2) 0
W q rF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
to 06/22/2023 07/25/2023 2023-00011316 $80.00
.Al. O
>b O
4S ?ff17��
Customer#: 22022 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
GYRO HUT 715 Mulberry St
1104 WASHINGTON ST WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION- 1104 WASHINGTON ST - 6-1-23 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
•
22022 06/22/2023 07/25/2023 2023-00011316 $80.00
Less Prepayment $0.00
Total Due — $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
TERt,
y1P` pp
,O)L2—
WATERLOO FIRE RESCUE ;f t's
INSPECTION REPORT ° \
E
GYRO HUT,1104 WASHINGTON ST,BLDG 1104 WASHINGTON ST-STE B,WATERLOO IA 50702
DETAILS
Inspection Date:06/01/2023 Inspection Type:Annual Inspection(1Yr) j Inspection Number:8446 { Shift: N/A ! Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL ; Other Inspectors: N/A j Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 509.2-Equipment access. Approved access shall be provided and maintained for all fire protection system
equipment to permit immediate safe operation and maintenance of such equipment.
Storage,trash and other materials or objects shall not be placed or kept in such a
manner that would prevent such equipment from being readily accessible.
Inspector:JEFF SIEBEL-Comments:remove ALL obstructions to Ansul system pull
station.Maintain a minimum of 36"clearance at all times.
Location: Not Provided
FAIL 606.3.3.1 -Inspection. Hoods,grease-removal devices,fans,ducts and other appurtenances shall be
inspected at intervals specified in Table 606.3.3.1 or as approved by the fire code
official. Inspections shall be completed by qualified individuals.
Inspector:JEFF SIEBEL-Comments:provide current semi-annual kitchen hood
exhaust system cleaning inspection report with all discrepancies corrected.
Contractor must upload online to the compliance engine.285 days past due
Location: Not Provided
FAIL 904.13.5.2-Extinguishing Automatic fire-extinguishing systems shall be serviced not less frequently than every
system service. six months and after activation of the system.Inspection shall be by qualified
individuals,and a certificate of inspection shall be forwarded to the fire code official
upon completion.
Inspector:JEFF SIEBEL-Comments:provide current semi-annual kitchen hood
exhaust system fire suppression inspection report with all discrepancies corrected.
Contractor must upload online to the compliance engine. 175 days past due
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-06/02/2023 @ 11:33 annual inspection$80
Printed on 06/02/2023 @ 11:33
Page 1 of 2
REINSPECTION DATE
06/26/2023
CONTACT SIGNATURE
Manager US an
Signed on:06/02/2023 @ 11:30
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:06/02/2023 @ 11:30
r7
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org