COMMERCIAL INSPECTION-209 W 5TH ST- 5-18-23 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price J
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4749 06/22/2023 07/25/2023 2023-00011324 $100.00
Less Prepayment $0.00
Total Due—> $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT �' 1
RUSSELL-LAMSON,209 W 5TH ST,BLDG 209 W.5TH ST,WATERLOO IA 50702
DETAILS
Inspection Date:05/18/2023 Inspection Type:Residential Common Areas Inspection I Inspection Number:8489 I Shift: N/A
Station: N/A I Unit: N/A I Lead Inspector:JEREMIAH VANDYKE ( Other Inspectors: N/A j Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1203.4-Maintenance. Emergency and standby power systems shall be maintained in accordance with NFPA
110 and NFPA 111 such that the system is capable of supplying service within the time
specified for the type and duration required.
Inspector:JEREMIAH VANDYKE-Comments:Fire pump generator is OOS and is
scheduled to be repaired.
Location:Generators.
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEREMIAH VANDYKE-Comments:Report needed for generators service
report.
Location: Not Provided
FAIL 1203.4.4-Switch Emergency and standby power system transfer switches shall be included in the
maintenance. inspection,testing and maintenance schedule required by Section 1203.4.2.Transfer
switches shall be maintained free from accumulated dust and dirt. Inspection shall
include examination of the transfer switch contacts for evidence of deterioration.
When evidence of contact deterioration is detected,the contacts shall be replaced in
accordance with the transfer switch manufacturer's instructions.
Inspector:JEREMIAH VANDYKE-Comments:Records needed of confirmed weekly
runs times/transfer switch.Dave R.maintenance manager will talk with Generator
contractors on how to record and track proper operating of generators.
Location: Not Provided
Printed on 05/18/2023 @ 15:45
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 1203.5-Operational Emergency power systems,including all appurtenant components,shall be inspected
inspection and testing. and tested under load in accordance with NFPA 110 and NFPA 111.Exception:Where
the emergency power system is used for standby power or peak load shaving,such
use shall be recorded and shall be allowed to be substituted for scheduled testing of
the generator set, provided that appropriate records are maintained.
Inspector:JEREMIAH VANDYKE-Comments:Dave R.maintenance manager will talk
with Generator contractors on how to record and track proper operating of
generators.
Location: Not Provided
FAIL 1203.6-Supervision of Routine maintenance,inspection and operational testing shall be overseen by a
maintenance and testing. properly instructed individual.
Inspector:JEREMIAH VANDYKE-Comments:Records needed of confirmed weekly
runs times/transfer switch.Dave R. maintenance manager will talk with Generator
contractors on how to record and track proper operating of generators.
Location:Not Provided
FAIL 509.1 -Identification. Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements fire protection systems shall be
identified for the use of the fire department.Approved signs required to identify fire
protection system equipment and equipment location shall be constructed of
durable materials, permanently installed and readily visible.
Inspector:JEREMIAH VANDYKE-Comments:1.All paper signs need to be replaced
with durable materials,permanently installed and readily visible.2.Durable signage
stating"Main electrical panel"needed in basement on door leading into electrical
room with durable material.
Location:Not Provided
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEREMIAH VANDYKE-Comments: Record log of cleaning needed for ALL
clothes dryer vent.
Location: Not Provided
Printed on 05/18/2023 @ 15:45
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEREMIAH VANDYKE-Comments:Doors not closing properly and need to
be adjusted.
Location: Floors 3&4 stair tower where freight elevator is located.
FAIL 99999-Inspection Outcome Did the inspection pass or fail?
Inspector:JEREMIAH VANDYKE-Comments:None
Location: Not Provided
GENERAL NOTES
JEREMIAH VANDYKE-05/18/2023 @ 15:22 Fire Extinguishers serviced/compliant by Superior in August 2022.
JEREMIAH VANDYKE-05/18/2023 @ 15:42 04/12/2023 S-(Quarterly)Fire Sprinkler CONTINENTAL FIRE SPRINKLER Reviewed
Compliant
JEREMIAH VANDYKE-05/18/2023 @ 15:42 03/01/2023 S-(Annual)Fire Alarm HAWKEYE ALARM Reviewed Compliant
JEREMIAH VANDYKE-05/18/2023 @ 15:43 07/20/2022 S-(Annual)Fire Pump CONTINENTAL FIRE SPRINKLER Reviewed Compliant
JEREMIAH VANDYKE-05/18/2023 @ 15:43 07/20/2022 S-(Annual)Standpipe CONTINENTAL FIRE SPRINKLER Reviewed Compliant
JEREMIAH VANDYKE-05/18/2023 @ 15:43 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address.Phone#319-291-2515.
JEREMIAH VANDYKE-05/18/2023 @ 15:43 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-05/18/2023 @ 15:43 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
Printed on 05/18/2023 @ 15:45
Page 3 of 4
GENERAL NOTES
JEREMIAH VANDYKE-05/18/2023 @ 15:44 Inspection Fee=$100.00
REINSPECTION DATE
06/17/2023
CONTACT SIGNATURE
Stacy Long Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:05/18/2023 @ 15:44