COMMERCIAL INSPECTION- 1501 E SAN MARNAN DR- 5-23-23 FOR BILLING INQUIRY: (319)291-4323
Description Total Price j
INSPECTION 100,000 $600.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4661 06/22/2023 07/25/2023 2023-00011303 $610.00
Less Prepayment $0.00
Total Due—* $610.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE 4AP?ER1-o0
INSPECTION REPORT
TARGET SUPER STORE,1501 E SAN MARNAN DR,BLDG 1501 E SAN MARNAN DR,WATERLOO
IA 50702
DETAILS
Inspection Date:05/23/2023 Inspection Type:Annual Inspection(1Yr) I Inspection Number:9644 I Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector:JEFF SIEBEL j Other Inspectors: N/A Fee:$610.00
STATUS CODE DESCRIPTION
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments: Remove obstructions from exit path. Path must
be kept clear at all times and not used for storage.
Location: Former Employees exit
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEFF SIEBEL-Comments:A. Provide documentation of testing and repair of
all egress and exit lights with all discrepancies corrected with signature and date.B.
Provide current annual generator engine service report and a current load bank test
or documentation of monthly testing in accordance with NFPA standards.
Location:A.emergency Lighting B.Generator
FAIL 304.3.1 -Spontaneous Materials susceptible to spontaneous ignition,such as oily rags,shall be stored in a
ignition. listed disposal container.Contents of such containers shall be removed and
disposed of daily.
Inspector:JEFF SIEBEL-Comments: Provide approved listed oily waste receptacle for
all grease laden materials.
Location: Not Provided
Printed on 05/24/2023 @ 09:01
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 305.1 -Clearance from Clearance between ignition sources,such as luminaires,heaters,flame-producing
ignition sources. devices and combustible materials,shall be maintained in an approved manner.
Inspector:JEFF SIEBEL-Comments:Remove storage,obtain a minimum of 36"
clearance to gas water heater.
Location: Front Janitor Closet
FAIL 305.1 -Clearance from Clearance between ignition sources,such as luminaires,heaters,flame-producing
ignition sources. devices and combustible materials,shall be maintained in an approved manner.
Inspector:JEFF SIEBEL-Comments: Remove all storage and combustible materials
sz from top of charging station for floor scrubbers.
Location:maintenance area
FAIL 5.2.1.1.5-Missing Escutcheons and coverplates for recessed,flush,and concealed sprinklers shall be
escutcheons replaced if found missing during the inspection.
Inspector:JEFF SIEBEL-Comments:replace missing fire sprinkler escutcheon.
Location:OPU Cooler
FAIL 509.1 -Identification. Fire protection equipment shall be identified in an approved manner.Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements fire protection systems shall be
identified for the use of the fire department.Approved signs required to identify fire
protection system equipment and equipment location shall be constructed of
durable materials, permanently installed and readily visible.
Inspector:JEFF SIEBEL-Comments: Install permanent sign above obstructions and
visible down hall ways stating"Fire Sprinkler Riser Room"in back storage area.
Location: Back storage area
Printed on 05/24/2023 @ 09:01
Page 2 of 5
STATUS CODE DESCRIPTION
FAIL 509.1 -Identification. Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements fire protection systems shall be
identified for the use of the fire department.Approved signs required to identify fire
protection system equipment and equipment location shall be constructed of
durable materials,permanently installed and readily visible.
Inspector:JEFF SIEBEL-Comments: Install permanent sign above obstructions stating
"Fire Department Connection"or"FDC"
Location:Outside back of store above fire department connection
FAIL 705.2-Inspection and Opening protectives in fire-resistance-rated assemblies shall be inspected and
maintenance. maintained in accordance with NFPA 80.Opening protectives in smoke barriers shall
be inspected and maintained in accordance with NFPA 80 and NFPA 105.Openings in
smoke partitions shall be inspected and maintained in accordance with NFPA 105.
Fire doors and smoke and draft control doors shall not be blocked,obstructed,or
otherwise made inoperable. Fusible links shall be replaced promptly whenever fused
or damaged.Opening protectives and smoke and draft control doors shall not be
modified.
Inspector:JEFF SIEBEL-Comments: Fire door propped open and blocked with table.
Fire Doors to remain operational at all times.
Location:fixture room
FAIL 903.3.1 -Standards. Sprinkler systems shall be designed and installed in accordance with Section
903.3.1.1,unless otherwise permitted by Sections 903.3.1.2 and 903.3.1.3 and other
chapters of this code,as applicable.
Inspector:JEFF SIEBEL-Comments: Install proper zone maps to match fire sprinkler
riser coverage.
Location:fire department riser room
FAIL 904.13.5.2-Extinguishing Automatic fire-extinguishing systems shall be serviced not less frequently than every
system service. six months and after activation of the system.Inspection shall be by qualified
individuals,and a certificate of inspection shall be forwarded to the fire code official
upon completion.
Inspector:JEFF SIEBEL-Comments:Provide current semi-annual kitchen hood fire
suppression inspection report with all discrepancies corrected.Currently 103 days
past due.Contractor must upload online to the compliance engine.
Location: Not Provided
Printed on 05/24/2023 @ 09:01
Page 3 of 5
i
STATUS CODE DESCRIPTION
FAIL 906.7-Hangers and brackets. Hand-held portable fire extinguishers,not housed in cabinets,shall be installed on
the hangers or brackets supplied. Hangers or brackets shall be securely anchored to
the mounting surface in accordance with the manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:mount fire extinguisher 4"to 5'above the floor in
a readily accessible location.
Location: Front stock room
GENERAL NOTES
JEFF SIEBEL-05/23/2023 @ 15:44 annual inspection$610.
JEFF SIEBEL-05/24/2023 @ 08:25 Hood cleaning due 7/20/23
JEFF SIEBEL-05/24/2023 @ 08:29 Fire sprinkler and private fire hydrant inspections due 6/15
JEFF SIEBEL-05/24/2023 @ 08:31 Fire alarm inspection due 6/9
JEFF SIEBEL-05/24/2023 @ 08:33 Fire Inspection completed during major renovation.Other items handled at final fire
building inspection.
REINSPECTION DATE
06/13/2023
CONTACT SIGNATURE
Griffen Cameron Maint 2023
Signed on:05/24/2023 @ 08:31 Q C. C:7; ,
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:05/24/2023 @ 08:31 1,
Printed on 05/24/2023 @ 09:01