COMMERCIAL INSPECTION- 627 SYCAMORE ST- 5-18-23 FOR BILLING INQUIRY: (319)291-4323
Description Total Price j
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23174 06/22/2023 07/25/2023 2023-00011306 $100.00
Less Prepayment $0.00
Total Due $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
C F
WA TERL 00 FIRE RESCUE 40SER[0
0
INSPECTION REPORT `N
MARSH PLACE APARTMENTS,627 SYCAMORE ST,BLDG 627 SYCAMORE-STE 2-6 FLOOR,
WATERLOO IA 50703 44110
DETAILS
Inspection Date:05/18/2023 ( Inspection Type:Residential Common Areas Inspection I Inspection Number:7947E Shift: N/A
Station: N/A ! Unit: N/A ; Lead Inspector:JEREMIAH VANDYKE I Other Inspectors: N/A ; Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1032.4-Exit signs. Exit signs shall be installed and maintained in accordance with the building code that
was in effect at the time of construction and the applicable provisions in Section
1104. Decorations,furnishings,equipment or adjacent signage that impairs the
visibility of exit signs,creates confusion or prevents identification of the exit shall not
be allowed.
Inspector:JEREMIAH VANDYKE-Comments: Exit light tested and failed.Will send
video/picture of working properly.
Location: Near room#202
FAIL 1104.16.5.1 -Examination. Fire escape stairways and balconies shall be examined for structural adequacy and
safety in accordance with Section 1104.16.5 by a registered design professional or
others acceptable to the fire code official every 5 years,or as required by the fire
code official.An inspection report shall be submitted to the fire code official after
such examination.
Inspector:JEREMIAH VANDYKE-Comments:Need copy of last fire escape inspection.
Send via email tojeremiah.vandyke@waterloo-ia.org.
Location: Not Provided
Printed on 05/18/2023 @ 16:08
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 1104.5-Illumination Where means of egress illumination is provided,the power supply for means of
emergency power. egress illumination shall normally be provided by the premises'electrical supply. In
the event of power supply failure,illumination shall be automatically provided from
an emergency system for the following occupancies where such occupancies require
two or more means of egress: 1.Group A having 50 or more occupants. Exception:
Assembly occupancies used exclusively as a place of worship and having an occupant
load of less than 300.2.Group B buildings three or more stories in height,buildings
with 100 or more occupants above or below a level of exit discharge serving the
occupants or buildings with 1,000 or more total occupants.3.Group E in interior exit
access and exit stairways and ramps,corridors,windowless areas with student
occupancy,shops and laboratories.4.Group F having more than 100 occupants.
Exception: Buildings used only during daylight hours and that are provided with
windows for natural light in accordance with the International Building Code.
5.Group I.6.Group M.Exception: Buildings less than 3,000 square feet(279 m2)in
gross sales area on one story only,excluding mezzanines.7.Group R-1. Exception:
Where each sleeping unit has direct access to the outside of the building at grade.
8.Group R-2.Exception:Where each dwelling unit or sleeping unit has direct access to
the outside of the building at grade.
Inspector:JEREMIAH VANDYKE-Comments:Egress on 5th street side tested and
failed.Will send video/picture of working properly.
Location:Suite C
FAIL 506.2-Key box maintenance. The operator of the building shall immediately notify the fire code official and provide
the new key where a lock is changed or rekeyed.The key to such lock shall be secured
in the key box.
Inspector:JEREMIAH VANDYKE-Comments:Unsure if there were any master key
changes. Please respond via email if no changes to email.
Location: Not Provided
FAIL 509.1 -Identification. Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements fire protection systems shall be
identified for the use of the fire department.Approved signs required to identify fire
protection system equipment and equipment location shall be constructed of
durable materials, permanently installed and readily visible.
Inspector:JEREMIAH VANDYKE-Comments:2 signs needed.Located: 1.On main floor
leading into basement with sign stating, "FACP&Sprinkler Riser".2.In basement at
bottom of steps with sign stating"FACP panel to the right"and "Main electrical panel
to the left".Paper sign found on ground.ALL signs to be made of durable materials,
permanently installed and readily visible.
Location:Not Provided
Printed on 05/18/2023 @ 16:08
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 603.2.2-Unapproved Open junction boxes and open-wiring splices shall be prohibited.Approved covers
conditionsOpen electrical shall be provided for all switch and electrical outlet boxes.
terminations.
Inspector:JEREMIAH VANDYKE-Comments: None
Location: Basement
4\` fy
FAIL 610.1.2-Maintenance. The lint trap, mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEREMIAH VANDYKE-Comments:Record log needed for all Clothes dryer
cleanings in building.
Location: Not Provided
FAIL 99999-Inspection Outcome Did the inspection pass or fail?
Inspector:JEREMIAH VANDYKE-Comments:None
Location: Not Provided
GENERAL NOTES
JEREMIAH VANDYKE-05/18/2023 @ 15:49 Fire Extinguishers serviced/compliant by Proshield in August 2022.
JEREMIAH VANDYKE-05/18/2023 @ 15:49 03/22/2023 S-(Annual)Fire Sprinkler CONTINENTAL FIRE SPRINKLER Reviewed
Compliant
JEREMIAH VANDYKE-05/18/2023 @ 15:49 02/15/2023 S-(Annual)Fire Alarm COMMUNITY ELECTRIC/PRIMARY SYSTEMS Reviewed
Compliant
JEREMIAH VANDYKE-05/18/2023 @ 16:07 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address.Phone#319-291-2515.
Printed on 05/18/2023 @ 16:08
Page 3 of 4
GENERAL NOTES
JEREMIAH VANDYKE-05/18/2023 @ 16:07 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-05/18/2023 @ 16:08 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-05/18/2023 @ 16:08 Inspection Fee=$100.00
REINSPECTION DATE
06/17/2023
CONTACT SIGNATURE
Paula Gourley Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Vn)
Signed on:05/18/2023 @ 16:07