COMMERCIAL INSPECTION - 1820 E RIDGEWAY AVE- 5-2-23 FOR BILLING INQUIRY: (319)291-4323
P
L Description I Total Price J
INSPECTION 2,000 HH $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
5591 05/08/2023 06/10/2023 2023-00011262 $100.00
Less Prepayment $0.00
Total Due --� $100.00
City of Waterloo
C- °\\\
�pSER�DO
WATERLOO FIRE RESCUE
INSPECTION REPORT
CROSSROADS SQUARE APARTMENTS,1820 E RIDGEWAYAVE,BLDG 1820 E RIDGEWAYAVE, ,
WATERLOO IA 50702 441
DETAILS
Inspection Date:05/02/2023 Inspection Type:Residential Common Areas Inspection ; Inspection Number:8416 I Shift: N/A !
Station: N/A Unit: N/A I Lead Inspector:JEREMIAH VANDYKE 1 Other Inspectors: N/A ; Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments:Fire Alarm inspection is 55 days past due.
Must have inspected by licensed contractor and report uploaded in compliance
engine by servicing contractor.
Location: Not Provided
FAIL 509.1 -Identification. Fire protection equipment shall be identified in an approved manner.Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements fire protection systems shall be
identified for the use of the fire department.Approved signs required to identify fire
protection system equipment and equipment location shall be constructed of
durable materials,permanently installed and readily visible.
Inspector:JEREMIAH VANDYKE-Comments:Need signage on door where sprinkler
riser is located.Sign must state"Sprinkler Riser".
Location: Not Provided
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEREMIAH VANDYKE-Comments:Need log of last completed clothes dryer
maintenance with date and name of completion.
Location: Not Provided
Printed on 05/02/2023 @ 15:24
Page 1 of 3
•
STATUS CODE DESCRIPTION
FAIL 704.1 -Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.Joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEREMIAH VANDYKE-Comments:Ceiling tiles not in place.
Location: 1.Outside of mechanial room on 1st floor missing tile.2.Men's bathroom
on 1st floor.
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:JEREMIAH VANDYKE-Comments: 1.Door leading to trash chute did not
close properly and must be addressed.2.Double doors leading into 110-116 is
broken and does not close properly.
Location: 1.3rd floor trash chute door.2.Double doors leading into 110-116 is
broken.
FAIL 99999-Inspection Outcome Did the inspection pass or fail?
Inspector:JEREMIAH VANDYKE-Comments:None
Location: Not Provided
GENERAL NOTES
JEREMIAH VANDYKE-05/02/2023 @ 15:20 Fire Extinguishers serviced/compliant by Hawkeye Fire and Safety on February 2022.
JEREMIAH VANDYKE-05/02/2023 @ 15:20 08/12/2022 S-(Annual)Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC.
Reviewed Compliant
JEREMIAH VANDYKE-05/02/2023 @ 15:21 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address.Phone#319-291-2515.
Printed on 05/02/2023 @ 15:24
Page 2 of 3
GENERAL NOTES
JEREMIAH VANDYKE-05/02/2023 @ 15:21 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-05/02/2023 @ 15:21 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-05/02/2023 @ 15:21 Inspection Fee=$100.00
REINSPECTION DATE
06/01/2023
CONTACT SIGNATURE
Eric Fuller-maintenance Contact Refused
Refusal Reason:N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:05/02/2023 @ 15:23
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 05/02/2023 @ 15:24