HomeMy WebLinkAbout728 COMMERCIAL ST :4""t INVOICE DATE DUE DATE INVOICE# TOTAL DUE
� i� ii0Ne,; 05/08/2023 06/10/2023 2023-00011263 $80.00
A
4torloo 'o
Customer#: 6422 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
AMERICAN LEGION 715 Mulberry StWATERLOO, IA 50703
728 COMMERCIAL ST
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 728 COMMERCIAL ST - 5-1-23 FOR BILLING INQUIRY: (319)291-4323
[Description I Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
6422 05/08/2023 06/10/2023 2023-00011263 $80.00
Less Prepayment $0.00
Total Due -� $80.00
City of Waterloo
WATERLOO FIRE RESCUE .to—too
INSPECTION REPORT 1
AMERICAN LEGION POST 138,728 COMMERCIAL ST,BLDG 728 COMMERCIAL ST,WATERLOO
IA 50702 41001
DETAILS
Inspection Date:05/01/2023 I Inspection Type:Annual Inspection(1Yr) I Inspection Number:7986 I Shift: N/A I Station: N/A I
Unit: N/A I Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 603.9.4-Prohibited areas. Portable,electric space heaters shall not be operated within 3 feet(914 mm)of any
combustible materials. Portable,electric space heaters shall be operated only in
locations for which they are listed.
Inspector:JEFF SIEBEL-Comments:remove portable electric heater from office. Install
permanent heat.
Location:office
FAIL 606.3.3.3-Records. Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments:provide current semi-annual kitchen hood
exhaust system cleaning and fire suppression inspection reports with all
discrepancies corrected.Contractor must upload online to the compliance engine.
Hood cleaning due 5/12/23 and fire suppression overdue by 177 days.
Location:kitchen
Printed on 05/02/2023 @ 11:06
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements. Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10.Exceptions:1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall be
allowed to be once every 3 years for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic monitoring
shall confirm that extinguishers are properly positioned,properly charged and
unobstructed.2.2.Loss of power or circuit continuity to the electronic monitoring
device shall initiate a trouble signal.2.3.The extinguishers shall be installed inside of a
building or cabinet in a noncorrosive environment.2.4.Electronic monitoring devices
and supervisory circuits shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at the
frequency required by NFPA 10.3.In Group 1-3,portable fire extinguishers shall be
permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual service for fire extinguishers.
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-05/02/2023 @ 11:00 annual inspection fee$80
JEFF SIEBEL-05/02/2023 @ 11:01 Check batteries in AED.Appear to be drained.
REINSPECTION DATE
05/23/2023
CONTACT SIGNATURE
Manager 2023
Signed on:05/02/2023 @ 11:05
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:05/02/2023 @ 11:05
Printed on 05/02/2023 @ 11:06
Page 2 of 3
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 05/02/2023 @ 11:06
Page 3 of 3