INSPECTION REPORT
BEST WESTERN,205 W 4TH ST,BLD6 205 W 4TH ST,WATERLOO IA 50702 4401
DETAILS
Inspection Date:05/02/2023 Inspection Type:Annual Inspection(1 Yr) I Insp ction Number:8564 Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A ! Fee:$ .00
STATUS CODE DESCRIPTION \ -
FAIL 1010.1.3-Door opening The force for pushing or pulling open interior swinging egress doors,other than fire
force Forces to unlatch and doors,shall not exceed 5 pounds(22 N).These forces do not apply to the force
open doors. required to retract latch bolts or disengage other devices that hold the door in a
closed position. For other swinging doors,as well as sliding and folding doors,the
door latch shall release when subjected to a 15-pound(67 N)force.The door shall be
set in motion when subjected to a 30-pound(133 N)force.The door shall swing to a
full-open position when subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following: 1.Where door hardware operates by push or
pull,the operational force to unlatch the door shall not exceed 15 pounds(66.7 N).
2.Where door hardware operates by rotation,the operational force to unlatch the
door shall not exceed 28 inch-pounds(315 N-cm).The force to open doors shall
comply with the following: 1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force for pushing or pulling
open the door shall not exceed 5 pounds(22 N).2.For other swinging doors,sliding
doors or folding doors,and doors required to be fire rated,the door shall require
not more than a 30-pound(133 N)force to be set in motion and shall move to a full-
open position when subjected to not more than a 15-pound(67 N)force.
Inspector:JEFF SIEBEL-Comments:Repair broken hardware.
Location:door to skywalk from hotel
FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEFF SIEBEL-Comments:Provide current annual fire sprinkler inspection
report with all discrepancies corrected. Report of 8/3/22 from black hawk sprinkler
lists discrepancies including fire sprinkler heads to close together in 1008.Contractor
' must upload online to the compliance engine.
•
Location: Not Provided
Printed on 05/04/2023 @ 10:14
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEFF SIEBEL-Comments:Provide documentation of dryer vent cleaning to
the outside of the building with signature and date. Report may be mailed to fire
inspector.
Location:Commercial house clothes dryers and guest clothes dryers
FAIL 705.2.6-Testing. Horizontal and vertical sliding and rolling fire doors shall be inspected and tested
annually to confirm proper operation and full closure. Records of inspections and
testing shall be maintained.
Inspector:JEFF SIEBEL-Comments:Provide annual fire door drop test for all floors.
Report may be emailed to fire inspector.
Location:elevator lobbies
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEFF SIEBEL-Comments:Provide current annual fire alarm fire inspection
report with all discrepancies corrected.Currently 140 days past due.Contractor must
upload online to the compliance engine.
Location: Not Provided
GENERAL NOTES
JEFF SIEBEL-05/04/2023 @ 10:03 annual inspection$600
JEFF SIEBEL-05/04/2023 @ 10:05 portable heater removed from sales office during inspection.
REINSPECTION DATE
05/24/2023
Printed on 05/04/2023 @ 10:14
Page 2of3
CONTACT SIGNATURE
Don Schlinger c Gr /
Signed on:05/04/2023 @ 10:14
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:05/04/2023 @ 10:05