COMMERCIAL INSPECTION-205 W 4TH ST- 5-2-23 FOR BILLING INQUIRY: (319)291-4323
LDescription Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24079 05/08/2023 06/10/2023 2023-00011272 $80.00
Less Prepayment $0.00
Total Due — $80.00
City of Waterloo
,„
40 )9 3
WATERLOO FIRE RESCUE 4,Pt.RL00
INSPECTION REPORT .\t
BRYAN'S BLUE PLATE,205 W 4TH ST BLD 6 205 W 4TH ST, WATERLOO lA 50703 .'�
DETAILS
Inspection Date:05/02/2023 Inspection Type:Annual Inspection(1Yr) ( Inspection Number:6493 Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
rif I ppipp iwai damage or physical impact. Extension cords shall be used only with portable
1
r '//, ,`,'�` ",41/ it'aL lall appliances. Extension cords marked for indoor use shall not be used outdoors.
isl
ittA Inspector:JEFF SIEBEL-Comments:Remove extension cords to patio lights.
-- . jl`lalk Location:Outside patio lights 2 locations
3wiiiir
lath , . r.-„, .. , i
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
-, :� under doors or floor coverings,nor shall such cords be subject to environmental
$ &Li,
damage or physical impact. Extension cords shall be used only with portable
` , g
a appliances. Extension cords marked for indoor use shall not be used outdoors.
' Inspector:JEFF SIEBEL-Comments: Remove extension cords to patio lights.
i
} I Location:Outside patio lights 2 locations
1a
Printed on 05/04/2023 @ 10:56
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings, nor shall such cords be subject to environmental
damage or physical impact.Extension cords shall be used only with portable
appliances.Extension cords marked for indoor use shall not be used outdoors.
� f
,1 Inspector:JEFF SIEBEL-Comments:Remove extension cords by both stages and•
attached to ceiling for light effects.Utilize power taps plugged directly into wall and
supported by floor or mounted.Extension cords may be used temporarily during
- dirt - performance but must be removed when not in use.
Location:both stages and on ceiling to lights
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings, nor shall such cords be subject to environmental
damage or physical impact.Extension cords shall be used only with portable
appliances.Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEFF SIEBEL-Comments: Remove extension cords by both stages and
�t I
attached to ceiling for light effects.Utilize power taps plugged directly into wall andsupported by floor or mounted. Extension cords may be used temporarily during
performance but must be removed when not in use.
Location:both stages and on ceiling to lights
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
damage or physical impact. Extension cords shall be used only with portable
appliances. Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEFF SIEBEL-Comments:Remove extension cords by both stages and
attached to ceiling for light effects.Utilize power taps plugged directly into wall and
N supported by floor or mounted. Extension cords may be used temporarily during
performance but must be removed when not in use.
Location:both stages and on ceiling to lights
Printed on 05/04/2023 @ 10:56
Page 2 of 5
STATUS CODE DESCRIPTION
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
damage or physical impact. Extension cords shall be used only with portable
appliances.Extension cords marked for indoor use shall not be used outdoors.
as
Inspector:JEFF SIEBEL-Comments:Remove extension cords by both stages and
attached to ceiling for light effects.Utilize power taps plugged directly into wall and
supported by floor or mounted.Extension cords may be used temporarily during
performance but must be removed when not in use.
Location: both stages and on ceiling to lights
FAIL 903.3.3-Obstructed Automatic sprinklers shall be installed with regard to obstructions that will delay
locations. activation or obstruct the water distribution pattern and shall be in accordance with
the applicable automatic sprinkler system standard that is being used.Automatic
sprinklers shall be installed in or under covered kiosks,displays,booths,concession
stands or equipment that exceeds 4 feet(1219 mm)in width. Not less than a 3-foot
(914 mm)clearance shall be maintained between automatic sprinklers and the top of
piles of combustible fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with Section 904.
Inspector:JEFF SIEBEL-Comments:several fire sprinkler heads in kitchen including
above buffet line are loaded with grease. Have fire sprinkler company inspect and
replace or clean according to NFPA standards.
Location:kitchen
FAIL 906.4.2-Class K portable fire Where hazard areas include deep fat fryers,listed Class K portable fire extinguishers
extinguishers for deep fat shall be provided as follows: 1.For up to four fryers having a maximum cooking
fryers. medium capacity of 80 pounds(36.3 kg)each:one Class K portable fire extinguisher
of a minimum 1.5-gallon(6 L)capacity.2.For every additional group of four fryers
having a maximum cooking medium capacity of 80 pounds(36.3 kg)each:one
additional Class K portable fire extinguisher of a minimum 1.5-gallon(6 L)capacity
shall be provided.3.For individual fryers exceeding 6 square feet(0.55 m2)in surface
area:Class K portable fire extinguishers shall be installed in accordance with the
extinguisher manufacturer's recommendations.
Inspector:JEFF SIEBEL-Comments:properly mount k guard fire extinguisher 4"to 5'
above the floor in an accessible location.
Location:kitchen
Printed on 05/04/2023 @ 10:56
Page 3 of 5
STATUS CODE DESCRIPTION
FAIL 906.7-Hangers and brackets. Hand-held portable fire extinguishers,not housed in cabinets,shall be installed on
the hangers or brackets supplied. Hangers or brackets shall be securely anchored to
the mounting surface in accordance with the manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:properly mount red fire extinguisher 4"to 5'
above the floor in an accessible area.
Location:kitchen
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEFF SIEBEL-Comments:past due 140 days
Location:entire hotel
GENERAL NOTES
JEFF SIEBEL-05/04/2023 @ 10:20 annual inspection$80
JEFF SIEBEL-05/04/2023 @ 10:45 obstructions removed from pool exit path to restaurant.
REINSPECTION DATE
05/24/2023
CONTACT SIGNATURE
Bryan Sink L
Signed on:05/04/2023 @ 10:46 1 L
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:05/04/2023 @ 10:46
Printed on 05/04/2023 @ 10:56
Page 4 of 5
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 05/04/2023 @ 10:56
Page 5 of 5