INSPECTION REPORT t 1,11p1'
SUNNYSIDE COUNTRY CLUB,1600 OLYMPIC DR,BLDG 1600 OLYMPIC DR,WATERLOO IA
S0701 \1
DETAILS
Inspection Date:04/11/2023 ( Inspection Type:Annual Inspection(1Yr) I Inspection Number:7874 I Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector:JEFF SIEBEL Other Inspectors: N/A I Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEFF SIEBEL-Comments:Provide documentation of testing and repair of all
egress and exit lights with all discrepancies corrected with signature and date
including:A.exit light above FX by stairs in hall from office to bar. B.egress lights
dining by office.C.egress light by elevator upper level D.egress light by elevator
lower level E.egress light 4'florescent golf simulator room by outside door. F.Exit
light bottom of stairs from kitchen.G. Exit light from employee break room to lower
kitchen. H. Exit/egress light main door.
FAIL 5003.5-Hazard identification Unless otherwise exempted by the fire code official,visible hazard identification signs
signs. as specified in NFPA 704 for the specific material contained shall be placed on
stationary containers and above-ground tanks and at entrances to locations where
hazardous materials are stored,dispensed,used or handled in quantities requiring a
permit and at specific entrances and locations designated by the fire code official.
Inspector:JEFF SIEBEL-Comments:Update NFPA 704 Placards for cold storage
building for items actually stored in the building. Hazzard ratings must match SDS
sheets.
FAIL 5303.5.3-Securing Compressed gas containers,cylinders and tanks shall be secured to prevent falling
compressed gas containers, caused by contact,vibration or seismic activity.Securing of compressed gas
cylinders and tanks. containers,cylinders and tanks shall be by one of the following methods: 1.Securing
containers,cylinders and tanks to a fixed object with one or more restraints.
2.Securing containers,cylinders and tanks on a cart or other mobile device designed
for the movement of compressed gas containers,cylinders or tanks.3.Nesting of
compressed gas containers,cylinders and tanks at container filling or servicing
facilities or in sellers'warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks,if dislodged,do not obstruct
the required means of egress.4.Securing of compressed gas containers,cylinders
and tanks to or within a rack,framework,cabinet or similar assembly designed for
such use. Exception:Compressed gas containers,cylinders and tanks in the process
of examination,filling,transport or servicing.
Inspector:JEFF SIEBEL-Comments:secure all compressed gas cylinders to wall with
chain in lower kitchen on both sides of ice machine.
Printed on 04/12/2023 @ 09:43
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the electrical service
equipment is wider than 30 inches(762 mm),the minimum working space shall be
not less than the width of the equipment.Storage of materials shall not be located
within the designated working space. Exceptions: 1.Where other dimensions are
41 required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove obstructions(furniture)from obstructing
electrical panel by office.
FAIL 603.5.2-Application and Relocatable power taps and current taps shall be directly connected to a
usePower supply. permanently installed receptacle.Exceptions: 1.Where approved for use in a Group A
occupancy or in a meeting room in a Group B occupancy,not more than five
relocatable power taps shall be permitted to be connected together or connected to
an extension cord for temporary use to supply power to electronic equipment.2.
Current taps and relocatable power taps shall not be required to connect directly to
a permanently installed receptacle outlet where used for 90 days or less for the
purpose of testing the performance of such devices.
Inspector:JEFF SIEBEL-Comments:Each power tap under desk in main office must
plug directly into wall outlet,not into another power tap.
FAIL 603.5.3-Installation. Relocatable power tap cords shall not extend through walls,ceilings,floors,under
doors or floor coverings,or be subject to environmental or physical damage.
Inspector:JEFF SIEBEL-Comments:install UL listed cord protectors on power cords
to desk from wall across walk way in pro shop
4
Printed on 04/12/2023 @ 09:43
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 704.1 -Maintaining Where required when the building was originally constructed,materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.Joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:replace missing ceiling tile at bottom of stairs
from kitchen.
GENERAL NOTES
JEFF SIEBEL-04/12/2023 @ 09:41 annual inspection$100
JEFF SIEBEL-04/12/2023 @ 09:14 /Fire Sprinkler Inspection Due 4/18/23
REINSPECTION DATE
05/02/2023
CONTACT SIGNATURE