INSPECTION REPORT
ELK RUN PRESCHOOL,316 MC COYRD,BLD6 316 MC COYRD,ELK RUN HEIGHTS U150707
DETAILS
Inspection Date:02/17/2023 I Inspection Type:Annual Inspection(1Yr) I Inspection Number:9683 I Shift: N/A I Station: N/A
Unit:324-Fire Marshal I Lead Inspector:BROCK WELIVER I Other Inspectors:JEREMIAH VANDYKE I Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 403.4.1 -First emergency The first emergency evacuation drill of each school year shall be conducted within 10
evacuation drill. days of the beginning of classes.
Inspector:BROCK WELIVER-Comments:Monthly fire drill log should be maintained
and kept on the premises.
FAIL 603.5-Relocatable power Multiplug adapters,such as cube adapters,unfused plug strips or any other device
taps and current not complying with NFPA 70 shall be prohibited.The construction and use of current
taps.Multiplug adapters. taps and relocatable taps shall be in accordance with NFPA 70 and this code.
Inspector:BROCK WELIVER-Comments: Daisy chained power taps were found during
the inspection and unplugged during the inspection.
FAIL 704.1 -Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:BROCK WELIVER-Comments:Missing ceiling tiles need to be put back in
place
Printed on 02/17/2023 @ 12:02
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 705.2.4-Door operation. Swinging fire doors shall close from the full-open position and latch automatically.
Inspector:BROCK WELIVER-Comments: Doors in the main hallway were propped
open using foot wedges and door stops.This building is not equipped with a fire
alarm or fire sprinkler system.These doors serve as a primary fire protection feature
of the building.These doors either need to be kept closed or electronic hold open
devices should be installed.
FAIL 907.2.11 -Single-and Listed single-and multiple-station smoke alarms complying with UL 217 shall be
multiple-station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.7 and NFPA 72.
alarms.
Inspector:BROCK WELIVER-Comments:Smoke alarms need to be tested and
maintained.Some devices appear to be dated-follow manufacturers
recommendations for replacement-most need to be replaced every 10 years.
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:BROCK WELIVER-Comments: Manual fire alarm/pull station alarm only.
Annual testing is required.
GENERAL NOTES
BROCK WELIVER-02/17/2023 @ 11:30 Fire Sprinkler:N/A
BROCK WELIVER-02/17/2023 @ 11:32 Fire Alarm:manual pull station only-annual maintenance records not available for
inspection.Annual inspection/service/maintenance should be performed if this has
not been conducted already.
BROCK WELIVER-02/17/2023 @ 11:34 Smoke Alarms:single station smoke alarms were present in many of the class rooms,
some of these appear to be older devices. Manufacturers'recommendations should
be followed in the replacement of these devices-many such devices recommend being
replaced every 10 years
BROCK WELIVER-02/17/2023 @ 11:36 Stage Curtains:documentation for fire retardant application is needed or sample of
the material needs to be sent out for flame retardant verification.
BROCK WELIVER-02/17/2023 @ 11:37 Dryer Vents:sticker log kept by vent-last cleaned by Harris Cleaning 3/15/2022.Annual
cleaning is approaching
BROCK WELIVER-02/17/2023 @ 11:38 Kitchen hood cleaning&suppression system:N/A
Printed on 02/17/2023 @ 12:02
Page 2of3
T• e
GENERAL NOTES
BROCK WELIVER-02/17/2023 @ 11:38 Fire Extinguisher:current,serviced by Superior Fire Protection June 2022
BROCK WELIVER-02/17/2023 @ 11:44 This inspection was conducted on behalf of the Waterloo School District for the City of
Elk Run Heights and The Boys&Girls Club.Waterloo Fire Rescue is not the Authority
Having Jurisdiction(AHJ).Re-inspections of the items listed in this report should be
directed to the Waterloo Community School District and the City of Elk Run Heights
and its inspectors for compliance.
BROCK WELIVER-02/17/2023 @ 11:45 Invoice Contact/Zack Kelly-Waterloo Community Schools/319-404-8085
BROCK WELIVER-02/17/2023 @ 12:01 Inspection Fee=$100
NEXT INSPECTION RATE
02/17/2024
CONTACT SIGNATURE
Steve Santomauro-City Inspector Elk Contact Refused
Run Heights Refusal Reason:N/A
INSPECTOR SIGNATURE
BROCK WELIVER
Signed on:02/17/2023 @ 12:02
QUESTIONS ABOUT YOUR INSPECTION?
BROCK WELIVER
brock.weliver@waterloo-ia.org
3192914460
Printed on 02/17/2023 @ 12:02
Page 3 of 3