COMMERCIAL INSPECTION - 3964 W AIRLINE HWY-3-8-23 FOR BILLING INQUIRY: (319)291-4323
Description I ' Total Price]
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24068 05/02/2023 06/05/2023 2023-00011232 $80.00
Less Prepayment $0.00
Total Due— $80.00
City of Waterloo
WATERLOO FIRE RESCUE ( •°\
INSPECTION REPORT �0
NAJO TRUCKING,3964 WAIRUNE HWY,BLD6 3964 WAIRLINE HWY,WATERLOO IA 50703
DETAILS
Inspection Date:03/08/2023 j Inspection Type:Annual Inspection(1Yr) I Inspection Number:9783 I Shift: N/A ( Station: N/A
Unit: N/A I Lead Inspector:JEREMIAH VANDYKE I Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
1 ..
exit or exit passageway shall not be used for any purpose that interferes with a
k means of egress.
Inspector:JEREMIAH VANDYKE-Comments:Exit door is to be cleared of pallets and
storage tank.The 2x4 wood crossbar is to be removed.
t \\%
S +,x
FAIL 1203.2.15-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination. with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:All Egress emergency lighting are to be
repaired or replaced located in shop/garage area.
)
Printed on 03/082023 @ 15:57
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments:Fire Alarm system is to be inspected
annually by licensed fire alarm contractor. Inspection report is to be uploaded to
Compliance Engine website by servicing contractor.Any deficiencies found by fire
alarm contractor are to be corrected as soon as possible.
mit
FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEREMIAH VANDYKE-Comments:Sprinkler system is to be inspected
annually by licensed sprinkler contractor. Inspection report is to be uploaded to
Compliance Engine website by servicing contractor.Any deficiencies found by
C Sprinkler contractor are to be corrected as soon as possible.
1.7
•
FAIL 506.1 -Where required. Where access to or within a structure or an area is restricted because of secured
openings or where immediate access is necessary for life-saving or fire-fighting
purposes,the fire code official is authorized to require a key box to be installed in an
approved location.The key box shall be of an approved type listed in accordance with
UL 1037,and shall contain keys to gain necessary access as required by the fire code
official.
Inspector:JEREMIAH VANDYKE-Comments:Commercial Knox box must be ordered
and placed in approved location by fire official.CALL fire offical when Knoxbox is
received for proper placement. Knox Box can be ordered from Knoxbox.com.
Recommended on website is Commercial KnoxBoxes KnoxBox®3200 Standard
Capacity Model:3261 For Waterloo Fire Rescue
FAIL 506.2-Key box maintenance. The operator of the building shall immediately notify the fire code official and provide
the new key where a lock is changed or rekeyed.The key to such lock shall be secured
in the key box.
Inspector:JEREMIAH VANDYKE-Comments:Master Key is needed for Knoxbox for
access to building by fire department.
Printed on 03/08/2023 @ 15:57
Page 2 of 5
STATUS CODE DESCRIPTION
FAIL 509.1 -Identification. Fire protection equipment shall be identified in an approved manner.Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements fire protection systems shall be
identified for the use of the fire department.Approved signs required to identify fire
protection system equipment and equipment location shall be constructed of
durable materials,permanently installed and readily visible.
Inspector:JEREMIAH VANDYKE-Comments: Durable legible signage needed for
sprinkler riser room and fire alarm panel to be placed on door.Stating"Sprinkler
Riser&FACP".
FAIL 603.2-Abatement of unsafe Identified electrical hazards shall be abated.Identified hazardous electrical conditions
conditions and electrical in permanent wiring shall be brought to the attention of the responsible code official.
hazards. Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes Conditions that constitute an electrical shock or fire hazard
shall be abated not be used.
Inspector JEREMIAH VANDYKE-Comments:Open wiring splice needs addressed
located on north wall of garage for a light fixture.
FAIL 603.5-Relocatable power Multiplug adapters,such as cube adapters,unfused plug strips or any other device
taps and current not complying with NFPA 70 shall be prohibited.The construction and use of current
taps.Multiplug adapters. taps and relocatable taps shall be in accordance with NFPA 70 and this code.
Inspector:JEREMIAH VANDYKE-Comments:Can use extension cord with multi plug
outlets with multiple power taps plugged into it.Cannot daisy chain power taps.
PIPPIr
Located in back office.
Printed on 03/08/2023 @ 15:57
Page 3 of 5
STATUS CODE DESCRIPTION
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEREMIAH VANDYKE-Comments:Fire Alarm system is to be inspected
annually by licensed fire alarm contractor.Inspection report is to be uploaded to
Compliance Engine website by servicing contractor.Any deficiencies found by fire
alarm contractor are to be corrected as soon as possible.
GENERAL NOTES
JEREMIAH VANDYKE-03/08/2023 @ 15:57 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address.Phone#319-291-2515.
JEREMIAH VANDYKE-03/08/2023 @ 15:57 Re-inspection dates are automatically generated 30 days out from the initial
inspection.Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-03/08/2023 @ 15:57 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-03/08/2023 @ 15:57 Inspection Fee=$80.00
JEREMIAH VANDYKE-03/08/2023 @ 15:02 Fire Extinguishers serviced/compliant by Proshield in November 2022.
JEREMIAH VANDYKE-03/08/2023 @ 15:56 Extension cords were removed from under garage door during inspection.
REINSPECTION DATE
04/07/2023
Printed on 03/08/2023 @ 15:57
Page 4of5
CONTACT SIGNATURE
Rusmir Okanovic Contact Refused
Refusal Reason:N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE (�
Signed on:03/08/2023 @ 15:52 �' L