HomeMy WebLinkAbout2710 CRPSSROADS INVOICE DATE DUE DATE INVOICE# TOTAL DUE
14_► ii,
�411, BIZ 05/02/2023 06/05/2023 2023-00011236 $200.00
Customer#: 5204 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
TIRES PLUS 715 Mulberry St
2710 CROSSROADS WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION -2710 CROSSROADS -4-28-23 FOR BILLING INQUIRY: (319)291-4323
Description I Total Price
REINSPECTION 3 $200.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
5204 05/02/2023 06/05/2023 2023-00011236 $200.00
Less Prepayment $0.00
Total Due— $200.00
City of Waterloo
WATERLOO FIRE RESCUE cbrack �PtER�oa
INSPECTION REPORT tr
TIRES PLUS,2710 CROSSROADS BLVD,BLDG 2710 CROSSROADS BLVD,WATERLOO IA S0702
DETAILS
Inspection Date:04/28/2023 ; Inspection Type:Annual Inspection(1 Yr) ; Inspection Number:9925 Shift: N/A j Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors: N/A Fee:$200.00
STATUS CODE DESCRIPTION
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:JEREMIAH VANDYKE-Comments:Fire alarm in trouble,needs to be
addressed by licensed fire alarm contractor.
Location: Not Provided
•
ga 1{x
4 11
FAIL 509.1 -Identification Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements shall be identified for the use of the
fire department.Approved signs required to identify fire protection equipment and
equipment location shall be constructed of durable materials, permanently installed
tit:tit:t , and readily visible.
Inspector:JEREMIAH VANDYKE-Comments: Door located in main garage going into
tire storage area needs signage. Must have"Sprinkler Riser,FACP,&Main Electrical
ay
on.panel"for description.
p
* Location: Not Provided
Printed on 04/28/2023 @ 13:15
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:Egress lights located in shop and in back
parts area tested and failed.
Location: Not Provided
FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEREMIAH VANDYKE-Comments:Egress lights located in shop and in back
parts area tested and failed.
*•• `
Location: Not Provided
-44
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEREMIAH VANDYKE-Comments: Fire alarm need to be inspected by
licensed fire alarm contractor and inspection report uploaded into Compliance
Engine by servicing contractor.
Location: Not Provided
GENERAL NOTES
JEREMIAH VANDYKE-03/28/2023 @ 14:36 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m. If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
Printed on 04/28/2023 @ 13:15
Page 2of3
GENERAL NOTES
JEREMIAH VANDYKE-03/28/2023 @ 14:36 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-03/28/2023 @ 14:36 RE-inspection fee:$200.00
REINSPECTION DATE
05/28/2023
CONTACT SIGNATURE
Scott Graham-District Manager Contact Refused
Refusal Reason: N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE /3j\IN-'
Signed on:04/28/2023 @ 13:14
QUESTIONS AMOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 04/28/2023 @ 13:15
Page 3of3