HomeMy WebLinkAbout1511 E SAN MARNAN DR INVOICE DATE DUE DATE INVOICE# TOTAL DUE
/iT1Vrir,k 05/02/2023 06/05/2023 2023-00011253 $50.00
°terloo
Customer#: 20996 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
AMERICAN NAILS 715 Mulberry St
1511 E SAN MARNAN DR WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION- 1511 E SAN MARNAN DR-4-5-23 FOR BILLING INQUIRY: (319)291-4323
LDescription Total Price
INSPECTION 1 $40.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
20996 05/02/2023 06/05/2023 2023-00011253 $50.00
Less Prepayment $0.00
Total Due -* $50.00
City of Waterloo
WATERLOO FIRE RESCUE ,C\Ck4
�PtER�oo
INSPECTION REPORT
AMERICAN NAILS,1511 E SAN MARNAN DR,BLDG 1511 E SAN MARNAN DR,WATERLOO/A
50702 40
DETAILS
Inspection Date:04/05/2023 Inspection Type:Annual Inspection(1Yr) Inspection Number:9991 Shift: N/A I Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL j Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 102.4-Application of building The design and construction of new structures shall comply with the International
code. Building Code,and any alterations,additions,changes in use or changes in
structures required by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
•
%di Inspector:JEFF SIEBEL-Comments:Obtain plumbing permit and inspections for
lavatory installed in restroom without permit
71,
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair exit/egress light at front of store.
FAIL 305.1 -Clearance from Clearance between ignition sources,such as luminaires,heaters,flame-producing
ignition sources. devices and combustible materials,shall be maintained in an approved manner.
Inspector:JEFF SIEBEL-Comments:remove storage around water heater.maintain a
minimum of 36"clearance.
Printed on 04/06/2023 @ 10:55
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the electrical service
equipment is wider than 30 inches(762 mm),the minimum working space shall be
e not less than the width of the equipment.Storage of materials shall not be located
within the designated working space.Exceptions: 1.Where other dimensions are
required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:Remove wash machine from in front of electrical
panel and outlet.Nothing GFCI in area.Maintain a minimum of 36"clearance at all
times to electrical panel.
Printed or.04/06/2023 @ 10:55
Page 2 of 5
STATUS CODE DESCRIPTION
FAIL 603.5-Relocatable power Multiplug adapters,such as cube adapters,unfused plug strips or any other device
taps and current not complying with NFPA 70 shall be prohibited.The construction and use of current
taps.Multiplug adapters. taps and relocatable taps shall be in accordance with NFPA 70 and this code.
Inspector:JEFF SIEBEL-Comments:Remove multi-plug adapters throughout building
including behind pedicure chairs,nail stations and to towel warmers.
106‘
' isc ' ' '--'-' c 1 5
tta- -- t - -- -- - --
i
a: 4..
' s
, i A
i
F a .
•fi �
. - as--
21
Printed on 04/06/2023 @ 10:55
Page 3 of 5
STATUS CODE DESCRIPTION
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
damage or physical impact. Extension cords shall be used only with portable
-� appliances. Extension cords marked for indoor use shall not be used outdoors.
Inspector:JEFF SIEBEL-Comments:A. Remove extension cords from towel warmer by
— N Lay.Appliances with motors,that produce heating or cooling must plug directly into
i wall outlet.B.remove all power cords from concealed space(wooden structure built
- ""_ _ behind pedicure chairs.
zg:T j/)++
4.1.44/
GENERAL NOTES )
JEFF SIEBEL-04/06/2023 @ 10:53 annual in ection
JEFF SIEBEL-04/06/2023 @ 10:53 provide corrections to avoid progressive re-inspection fees beginning at$100
REINSPECTION DATE
04/26/2023
CONTACT SIGNATURE
Helen Lac J L12 4____.>
Signed on:04/06/2023 @ 10:53
kl e / cam
Printed on 04/06/2023 @ 10:55
Page 4 of 5
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:04/06/2023 @ 10:54
QUESTIONS AIOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 04/06/2023 @ 10:55
Page 5 of 5