HomeMy WebLinkAbout310 E 6TH ST INVOICE DATE DUE DATE INVOICE# TOTAL DUE
/%p' rit . 04/27/2023 05/30/2023 2023-00011224 $100.00
IP4V1111#
°l'erloo
Customer#: 13316 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
DEPARTMENT OF CORRECTIONAL SERVICES 715 Mulberry St
310 E 6TH ST WATERLOO, IA 50703
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION-310 E 6TH ST- 1-10-23 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price,
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13316 04/27/2023 05/30/2023 2023-00011224 $100.00
Less Prepayment $0.00
Total Due — $100.00
City of Waterloo
V3D
WATERLOO F/RE RESCUEc737)\ t�
�pSER�pO
INSPECTION REPORT r
DEPARTMENT OF CORRECTIONAL SERVICES,310 E 6TH ST,BLDG 310 E 6TH ST,WATERLOO IA /
S0703
4k4i0
DETAILS
Inspection Date:01/10/2023 I Inspection Type:Annual Inspection(1 Yr) Inspection Number:7309 I Shift: N/A ; Station: N/A
Unit: N/A Lead Inspector:JEREMIAH VANDYKE Other Inspectors:BROCK WELIVER if Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1203.2.6-Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEREMIAH VANDYKE-Comments:Exit light on east wing stairway on main
floor leading outside is not operating. Needs replaced or repaired.Send picture after
repaired.
FAIL 403.4.1 -First emergency The first emergency evacuation drill of each school year shall be conducted within 10
evacuation drill. days of the beginning of classes.
Inspector:JEREMIAH VANDYKE-Comments:Please send date of last fire drill with how
many residents and staff that participated.
FAIL 610.1.2-Maintenance. The lint trap,mechanical and heating components,and the exhaust duct system of a
clothes dryer shall be maintained in accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that prevents the exhaust
of air and products of combustion.
Inspector:JEREMIAH VANDYKE-Comments:Send copy of completed clothes dryer
•
ducts cleaning records.
GENERAL NOTES
JEREMIAH VANDYKE-01/10/2023 @ 14:53 07/21/2022 S-(Annual)Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC.
Reviewed Compliant
JEREMIAH VANDYKE-01/10/2023 @ 14:54 Fire Extinguishers compliant/serviced by Proshield on 1/2022.Contractor is scheduled
for service.
JEREMIAH VANDYKE-01/10/2023 @ 14:54 07/20/2022 S-(Annual)Fire Alarm HAWKEYE ALARM Reviewed Compliant
Printed on 01/10/2023 @ 14:58
Page 1 of 2
GENERAL NOTES
JEREMIAH VANDYKE-01/10/2023 @ 14:54 07/19/2022 S-(Semi-Annual)Kitchen Exhaust PROSHIELD FIRE&SECURITY Reviewed
Compliant
JEREMIAH VANDYKE-01/10/2023 @ 14:55 07/19/2022 S-Kitchen Hood Suppression PROSHIELD FIRE&SECURITY Reviewed
Compliant
JEREMIAH VANDYKE-01/10/2023 @ 14:55 Re-inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections&re-inspections are Monday-
Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on
a weekend,the re-inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days,you can call to set up an earlier
re-inspection.
JEREMIAH VANDYKE-01/10/2023 @ 14:55 Re inspection fees may be assessed for subsequent re-inspections. Re-inspection fees
start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-01/10/2023 @ 14:55 Inspection Fee=$100.00
REINSPECT/ON DATE
02/09/2023
CONTACT SIGNATURE
Blake Burton Contact Refused
Refusal Reason:N/A emailed.
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on:01/10/2023 @ 14:48 /S7f0 L
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available