COMMERCIAL INSPECTION -2181 LOGAN AVE-2-15-23 FOR BILLING INQUIRY: (319)291-43231
Description J Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4431 04/27/2023 05/30/2023 2023-00011201 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
WATERLOO FIRE RESCUE �PtER�oQ
INSPECTION REPORT t � 1
HY-VEE,2181 LOGAN AVE,BLDG 2181 LOGAN AVE,WATERLOO IA 50703
DETAILS
Inspection Date:02/15/2023 ! Inspection Type:Annual Inspection(1Yr) Inspection Number:8039 ; Shift: N/A I Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL j Other Inspectors: N/A ! Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1032.2-Reliability. Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments:A. relocate booth.Maintain a minimum of 36"
clearance to exit door in dining area.B.remove storage Upper office exit path as
posted
FAIL 1203.4.3-Records. Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEFF SIEBEL-Comments:Provide documentation of generator engine
service,load bank test,and ceiling emergency light testing with all discrepancies
corrected.
FAIL 304.3.1 -Spontaneous Materials susceptible to spontaneous ignition,such as oily rags,shall be stored in a
ignition. listed disposal container.Contents of such containers shall be removed and
disposed of daily.
Inspector:JEFF SIEBEL-Comments:obtain approved listed oily waste container with
self closing lid for all oily materials.
Printed on 02/16/2023 @ 13:15
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 509.2-Equipment access. Approved access shall be provided and maintained for all fire protection system
equipment to permit immediate safe operation and maintenance of such equipment.
Storage,trash and other materials or objects shall not be placed or kept in such a
manner that would prevent such equipment from being readily accessible.
Inspector:JEFF SIEBEL-Comments:maintain a clear 36"path to fire sprinkler riser at
' all times.Remove obstructions.
�- .
'; r,
so �
FAIL 5303.5.3-Securing Compressed gas containers,cylinders and tanks shall be secured to prevent falling
compressed gas containers, caused by contact,vibration or seismic activity.Securing of compressed gas
cylinders and tanks. containers,cylinders and tanks shall be by one of the following methods: 1.Securing
containers,cylinders and tanks to a fixed object with one or more restraints.
2.Securing containers,cylinders and tanks on a cart or other mobile device designed .
for the movement of compressed gas containers,cylinders or tanks.3. Nesting of
compressed gas containers,cylinders and tanks at container filling or servicing
facilities or in sellers'warehouses not open to the public. Nesting shall be allowed
provided that the nested containers,cylinders or tanks,if dislodged,do not obstruct
the required means of egress.4.Securing of compressed gas containers,cylinders
and tanks to or within a rack,framework,cabinet or similar assembly designed for
such use. Exception:Compressed gas containers,cylinders and tanks in the process
of examination,filling,transport or servicing.
Inspector:JEFF SIEBEL-Comments:Secure compressed gas cylinders to wall with
CHAIN:upper chiller room
FAIL 603.2-Abatement of unsafe Identified electrical hazards shall be abated.Identified hazardous electrical conditions
conditions and electrical in permanent wiring shall be brought to the attention of the responsible code official.
hazards. Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes Conditions that constitute an electrical shock or fire hazard
shall be abated not be used.
♦� „
.., Inspector:JEFF SIEBEL-Comments:repair broken conduit and outlet by
bakery/utensil sales rack/chicken area in kitchen.
444,
Printed on 02/16/2023 @ 13:15
Page 2 of 5
STATUS CODE DESCRIPTION
FAIL 603.4-Working space and A working space of not Working space around electrical equipment shall be provided
clearancesclearance. in accordance with Section 110.26 of NFPA 70 for electrical equipment rated 1,000
volts or less,and Section 110.33 of NFPA 70 for electrical equipment rated over 1,000
volts.The minimum required working space shall be not less than 30 inches(762 mm)
i in width,36 inches(914 mm)in depth and 78 inches(1981 mm)in height shall be
II Pi:
= providedin front of electrical service equipment.Where the electrical service
.,, , , -fi equipment•is •wider •than 30 inches(762 mm),the minimum •working space shall be
not less than the width of the equipment.Storage of materials shall not be located
within the designated working space.Exceptions: 1.Where other dimensions are
-t required or allowed by NFPA 70.2.Access openings into attics or under-floor areas
that provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:Remove obstructions,maintain a minimum
` .tj. clearance of 9"on sides and 36"in front of electrical panels,and install permanent
signage stating"No Storage Maintain 36"Clearance"in following areas:A.2 areas in
1
ems-- _ / back storage area B. in bakery and kitchen area.
14E1 1
FAIL 603.4.1 -Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and
legible sign stating"ELECTRICAL ROOM"or similar approved wording.The
disconnecting means for each service,feeder or branch circuit originating on a
switchboard or panelboard shall be legibly and durably marked to indicate its
purpose unless such purpose is clearly evident.Where buildings or structures are
supplied by more than one power source,markings shall be provided at each service
equipment location and at all interconnected electric power production sources
identifying all electric power sources at the premises in accordance with NFPA 70.
Inspector:JEFF SIEBEL-Comments: Install permanent sign stating"Electrical Room"
on door to main disconnect in chiller room.
FAIL 603.6-Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring and
shall be listed and labeled in accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures,extended through walls,ceilings or floors,or
under doors or floor coverings,nor shall such cords be subject to environmental
_ ; _ damage or physical impact.Extension cords shall be used only with portable
II"IllIll111
''� --,'t= appliances. Extension cords marked for indoor use shall not be used outdoors.
"IIIIII_. i ., 1x' -,i , Inspector:JEFF SIEBEL-Comments:A. Remove extension cord, power strip and
,. portable heater by fire sprinkler riser. Install permanent heater with permit and
inspections. B. remove extension cord in accounting C. Remove extension cord to Dr
Pepper cooler by front entrance and install permanent power with permits and
lta'' . inspections.All appliances must plug directly into a permanent outlet.
Printed on 02/16/2023 @ 13:15
Page 3of5
•
STATUS CODE DESCRIPTION
FAIL 603.9.4-Prohibited areas. Portable,electric space heaters shall not be operated within 3 feet(914 mm)of any
combustible materials. Portable,electric space heaters shall be operated only in
locations for which they are listed.
Inspector:JEFF SIEBEL-Comments:remove portable electric heaters:A.fire sprinkler
riser area B.Scan area.
FAIL 606.3.3.3-Records. Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments:Provide current semi-annual kitchen hood
exhaust cleaning and fire suppression inspection reports with all discrepancies
corrected.Contractor must upload online to the compliance engine.
FAIL 704.1 -Maintaining Where required when the building was originally constructed, materials and systems
protection. used to protect joints and voids in the following locations shall be maintained.The
materials and systems shall be securely attached to or bonded to the adjacent
construction,without openings visible through the construction. 1.Joints in or
between fire-resistance-rated walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at the intersection of a
horizontal floor assembly and an exterior curtain wall.4.Voids at the intersection of a
horizontal smoke barrier and an exterior curtain wall.5.Voids at the intersection of a
nonfire-resistance-rated floor assembly and an exterior curtain wall.6.Voids at the
intersection of a vertical fire barrier and an exterior curtain wall.7.Voids at the
intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.
Unprotected joints and voids do not need to be protected where such joints and
voids were not required to be protected when the building was originally
constructed.Where the system design number is known,the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:Replace missing ceiling tile:A.above customer
service B.mailroom C.trim room(prep room)
FAIL 906.5-Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will
have ready access and be immediately available for use.These locations shall be
along normal paths of travel,unless the fire code official determines that the hazard
posed indicates the need for placement away from normal paths of travel.
Inspector:JEFF SIEBEL-Comments: Install fire extinguisher location sign above
shelving height on column in store area in front of customer service area.
Printed on 02/16/2023 @ 13:15
Page 4 of 5
STATUS CODE DESCRIPTION
FAIL 906.6-Unobstructed and Portable fire extinguishers shall not be obstructed or obscured from view. In rooms
unobscured. or areas in which visual obstruction cannot be completely avoided,means shall be
provided to indicate the locations of extinguishers.
Inspector:JEFF SIEBEL-Comments:remove obstructions,maintain a minimum 36"
clearance to fire extinguisher in customer service.
GENERAL NOTES
JEFF SIEBEL-02/16/2023 @ 11:56 Annual inspection$100
JEFF SIEBEL-02/16/2023 @ 11:57 provide corrections to avoid progressive re-inspection fees beginning at$100
REINSPECTION DATE
03/08/2023
CONTACT SIGNATURE
Conor Erickson
Signed on:02/16/2023 @ 11:57 �C
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:02/16/2023 @ 11:57
QUESTIONS AIOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 02/16/2023 @ 131 S
Page 5 of 5